GFK-2571A
Chapter 5 Diagnostics
5-3
5
Problems During Powerup and Reset
Certain conditions can prevent the module from powering up and becoming operational or entering
firmware update mode:
Problem
Indication
Action
Hardware failure
All LEDs off. Module unresponsive.
Return the
module to GE
Intelligent
Platforms.
Invalid bootstrap image
Invalid boot image
No LEDs turn on and the module is
unresponsive, or
The STATUS LED is solid Green and is
the only LED that is on.
Power-up
diagnostics/hardware
initializations fail that are
considered fatal
LED Fatal Error blink code, as described in
this chapter.
Note the blink
code and contact
Customer
Service.
Non-Fatal diagnostic/hardware
initialization faults
The module continues normal power-up, but
an entry is added to the Local Log table and
the RX3i
CPU’s fault table (if backplane
communications have been established).
Note the fault
and contact
Customer
Service.
The module does not contain
hardware identity information
LED Fatal Error blink pattern, as described in
this chapter.
Note the blink
code and contact
Customer
Service.