GFK-2571A
Chapter 2 Installation
2-9
2
Powerup LED Patterns
At powerup, the LEDs show the blink patterns described below. The LEDs also blink diagnostic
patterns for certain operating errors and for module identification. See
“Chapter 5, Diagnostics” for a
description of the special blink patterns.
Step
LED/ Blink pattern
Description
1
2
3
4
PNC001
ACTIVE
USB
OK
LAN
STATUS
CONFIG
USB
RESTART
IP ADDRESS
INTERFACE MAC
PORTS
FRONT
TO INSTALL, TORQUE TO
6 IN-LB. TO UNINSTALL,
REVERSE MOTION
3 4
1 2
!
1
All LEDs off
Normal operation
2
STATUS LED solid Green
Normal operation
OK LED blinks Amber with
special blink code
Fatal Initialization or Diagnostics
Failure, H/W Module Identity
Information not available
OK, LAN, and STATUS
LEDs blink green in unison
(0.5 second ON/ 0.5
second OFF)
Invalid firmware detected. Module is
waiting for firmware update. Blink
pattern continues during firmware
update.
3
LAN and STATUS LED
solid Green
Normal operation
4
LAN LED solid Green
Normal operation
LAN and STATUS LED
blink Green (0.5 second
ON and 0.5 second OFF)
Update of module firmware. After the
automatic update completes, the LEDs
blink Amber and the module resets,
which restarts the powerup process.
5
OK LED solid Green
Normal operation. Powerup completed
and backplane communications
established.
OK LED blinks Green (0.5
second ON and 0.5 second
OFF)
Module powerup completed, but
communication not yet established
over the RX3i backplane.
Note:
Under certain ambient operating temperatures, the PROFINET Controller may momentarily
display the overtemperature pattern during power up, while it is calibrating its thermal protection
functions. This indication may be ignored, and no overtemperature entry is added to the Local Log
table, the Controller Fault table or I/O Fault table.
For details, see “Special LED Blink Patterns” in chapter 5.