Introduction
GFK-2785C
PACSystems* RXi Box IPC
3
Environmental Specifications
Note:
The Box IPC shall be installed in a location that is not exposed to corrosive gases or
liquids, rain, or direct sunlight, and that meets the environmental specifications listed
below.
Vibration
1
IEC60068-2-6
10 - 57 Hz, 0.006 in. displacement peak-peak
57 - 500 Hz, 1.0 g acceleration
Shock
IEC60068-2-27
15 g, 11ms
Ambient Operating Temperature
2
ICRXIBNxE00xA
ICRXIBNxM00xA
-25
C to +65
C: [inlet] (-13° F to 149°F)
0
C to +40
C: [inlet] (32° F to 104°F)
Storage Temperature
-40
C to +85
C (-40°F to 185°F)
Humidity
5% to 95%, non-condensing
Environment
UL60950-1
Pollution Degree 2
Altitude
UL60950-1
0–2000 m
1
Applies only to IPCs with solid state hard drive (ICRXIBNxE00xA).
2
For ambient temperatures greater than 50°C (122°F), the unit must be installed in a
restricted access area,
as defined below.
Warning
If the Box IPC is operating in ambient temperatures greater than 50°C (122°F),
its exterior temperatures may be too hot to touch safely. To avoid burn
hazards, the unit must be installed in a
restricted access area,
as defined by:
Access can only be gained by
service persons
or by
users
who have been instructed
about the reasons for the restrictions applied to the location and about any
precautions that shall be taken; and
Access is through the use of a tool or lock and key, or other means of security, and
is controlled by the authority responsible for the location.
Pollution Degree 2
A Pollution Degree 2 environment as defined by UL60950-1:
Pollution Degree 2 applies where there is only non-conductive pollution that might
temporarily become conductive due to occasional condensation.
Note:
For additional product standards and agency approvals, refer to Appendix A.