background image

GEH-12668 

Type 

IAV 

Undervoltage  and  Overvoltage  Relays 

Maintenance 

These  relays  are  adjusted  at  the  factory  and  it  is 

advisable not  to  disturb  the adjustments.  If,  for  any 
reasons,  they  have  been  disturbed,  the  following 
points should be  observed in restoring them: 

Disk  and  Bearings 

The  lower  jewel  may  be  tested  for  cracks  by  ex­

ploring  its  surface  with  the  point  of  a  fine  needle. 
If  it  is  necessary  to  replace  the  jewel,  a  very  small 

drop of  G-E meter jewel oil; Cat. No. 

66X728 

should 

be placed on  the new jewel  before  it  is  inserted.  The 

jewel  should  be  turned  up  until  the  disk  is  centered 

in  the  air  gap,  after. which  it  should  be  locked  in 

position  by  the  set  screw  provided  for  the  purpose. 

Contacts  (Cleaning) 

If  the  contacts  become  dirty  or  slightly  pitted, 

they  should  be  cleaned  by  scraping  the  surface 

lightly  with  a  sharp  knife  or  by  using  a  fine  clean 

file.  Under  no  circumstances should emery  or  crocus 
cloth  be  used  on  fine-silver  relay  contacts.  Finish 
by  wiping  the  contacts  with  a  clean,  soft  cloth  and 

avoid touching  them with the fingers. 

:-Jame  of  Part 

Periodic  Testing 

An  operation  test  and  inspection  of  the  relay  at 

least  once  every  six  months  are  recommended.  Test 
connections  are  shown  in  Fig. 

12 

and 

13. 

Renewal  Parts 

It  is  recommended  that  sufficient  quantities  of 

renewal  parts  be  can ied  in  stock  to  enable  the 
prompt  replacement  of  any  worn,  broken,  or  dam­

aged  parts.  Those  most  subject  to  wear  in  ordinary 

operation  and  to  damage  due  to  possible  abnormal 
conditions  are  listed  below.  For  illustration  of  parts 
see  Fig. 

14 

and 

15. 

Ordering  Directions 

When  ordering  renewal  parts,  address  the  nearest 

Sales Office of  the General Electric  Company,  specify 
quantity  required,  name  of  part  wanted  as  shown 
by Fig. 

14 

and 

15 

and give complete nameplate data, 

including  serial  number.  If  possible  give  the  General 
Electric  Company's  requisition  on  which  the  relay 

was  furnished. 

Quantity 

per  Relay 

Recommended  Stock 

Relay 

Relays 

Coil,  l\Iagnet,  and  Tap-block  Assembly ........................ . 

l\lain  :\loving  Contact  and  Carrier. 

. .......

.

......

. .

.

. .

.. . 

:\lain  Stationary  Brush  and  Contact  Tip  Assembly ... . 
Seal-in  Element  Holding  Coil. . . 

.  . 

. . . 

.

..

.

.. 

Seal-in  Element  Stationary  Contact  Right .. . 
Seal-in  Element  Stationarv  Contact  Left ... 

Seal-in  Element  :\loving  Contact  Assembly. 
Lower  J ewe!  Screw ... . 
Top  Pivot .. ........... . 
Disk  and  Shaft ........ . 

APPARATUS  DEPARTMENT 

GENERAL

ELECTRIC 

SCHENECTADY,  N.  Y. 

8-48  (6500) 

Supersedes GEH-1266A 

www . ElectricalPartManuals 

. com 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for IAV51A

Page 1: ...LTAGE AND OVERVOLTAGE RELAYS TYPES IAVSlA IAVS3A IAVS2A IAVS4A IAVSSA IN THE DRAWOUT CASE GENERAL flELECTRIC GEH 12668 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 2: ... for every possible contingency to be met in connection with installation operation or maintenance Should further in formation be desired or should particular problems arise which are not covered sufficiently for the purchas er s purposes the matter should be referred to the General Electric Company w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l...

Page 3: ... removed Then the connecting plug can be drawn out In so doing the trip circuit is first opened then the voltage circuits are opened After the connecting plug has been removed the lower latch can be re leased and the cradle easily drawn out To replace the cradle the reverse order should be followed Note Care must be taken to insert the connecting plug slowly on relays that have contacts which are ...

Page 4: ...on the seal in element is determined by the current drawn by the trip coil The 0 2 ampere tap is for use with trip coils that operate on currents ranging from 0 2 up to 2 0 am peres at the minimum control voltage If this tap is used with trip coils requiring more than two amperes there is a possibility that the seven ohms resistance will reduce the current to so low a value that the breaker will n...

Page 5: ...on the curve I I I I I I I I I I I I I I I I I I I I I Time to close left contacts when voltage is suddenly increased from zero to the values on the curve v 1 Q i r u o t CI f 1 1 Left contact closed r r 8 fi 0 0 f O J5l _o I 50 0 e r 60 g J r 70 E e 80 0 g 90 95 0 0 0 0 20 40 60 80 100 120 140 180 200 160 Per cent of voltag e required to close l eft contact Fig 3 Time voltage curves for TypeIAV53...

Page 6: ...ake 2 0 amperes or more at minimum control voltage provided the tripping current does not exceed 30 amperes at the maximum control voltage If the tripping current exceeds 30 amperes an auxiliary relay should be used the connections being such that the tripping current does not pass through the contacts or the target and seal in coil of the protective relay Burdens Burdens for the various relay typ...

Page 7: ...tely they should be stored in their original carton in a place that is free from moisture dust and metallic chips Foreign matter collected on the outside of the case may find its way inside when the cover is re moved and cause trouble in the operation of the relay Installation Location The location should be clean and dry free from dust and excessive vibration and well lighted to facilitate inspec...

Page 8: ...d at the factory to operate from any time dial position at a minimum voltage within five per cent of the tap plug setting The relay resets at 90 per cent of the 8 minimum operating value on all relays listed except the IAVS3A which will be explained later Operating voltage for the IAVS1A and the IAV52A is the minimum voltage for a given tap setting at which the contacts just make Operating voltage...

Page 9: ...he desired characteristic by turning it until the number lines up with the notch in the adjacent frame The time indicated by the curves is the time required to close the relay contacts when the voltage is suddenly increased from a value below pickup to the value on the curve Time settings on the IAV54A and the IAVSSA are quite similar except that their characteristics as shown in Fig 4 indicate th...

Page 10: ...mmended test connections for the above tests are shown in Fig 12 for the lAV51A and the lAV 52A Fig 13 shows test connections for the lAV54A and the lAVSSA The lAV53A can be checked for time of closing left contacts by using connections shown in Fig 12 and for closing right contacts 10 R A c supply of correct frequency c O M Synchronous timer type MF 2 Fig 12 Connectio s for testing Types IAV51A a...

Page 11: ...s GEH 12668 Seal in element holdin g coil Main stationary brush and contact assem bly Top pivot Fig 14 Front view of Type lAVSIA relay withclrawn from case _ _ _ Coi I m agnet and tap bl o ck assembly Fig 15 Bade view of Type IAV51A relay withclrawn from case 11 t w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 12: ...months are recommended Test connections are shown in Fig 12 and 13 Renewal Parts It is recommended that sufficient quantities of renewal parts be can ied in stock to enable the prompt replacement of any worn broken or dam aged parts Those most subject to wear in ordinary operation and to damage due to possible abnormal conditions are listed below For illustration of parts see Fig 14 and 15 Orderin...

Reviews: