Figure 5. Wiring.
7. Ensure that the plug in connection is firm and
that the plug is inserted into the correct
terminals.
8. To reinstall the breaker cover rotate the
charging handle down and slide the front cover
over the handle to assemble the front cover to
the housing as shown in Figure 6.
9. Ensure the fascia is aligned properly with the
trip unit and the pad lock features of the breaker.
Figure 6.
10. Fasten the 6 mounting screws of the fascia
with the housing using a Pozidrive screwdriver.
Apply torque of 6Nm (4.42 ft-lbs).
11. When installing a GSST* shunt trip device you
must wire one or more Normally Open (NO)
breaker auxiliary contact(s) in series with the
shunt trip accessory coil. In some cases multiple
contacts in series are required to ensure reliable
performance.
Application Voltage
Required Aux. Contacts
All AC Ratings, 24VDC
One
120VDC
Two
240VDC
Three
GSTG* devices do not require an auxiliary
contact.