background image

1

 

 

 

 

General 

These instructions apply to the following catalog numbers: 

•  Circuit  breaker  modules  AMC6FEB,  AMC4FEB, 

AMC6FES, or AMC4FES. 

•  Circuit breaker frames FEN, FEH, or FEL. 

 

 

WARNING 

Danger  of  electrical  shock  or  injury.  Turn

 

OFF  power 

ahead of the panelboard or switchboard before working 
inside  the  equipment  or  removing  any  component

Do 

not  remove  or  install  circuit  protective  devices  or  any 
other component until the power is turned OFF. 

Installation 

1.  Phase  balancing  for  two-pole  devices  on  three-phase 

systems.

  Reposition  the  bus  clip  assembly  from  A  or  C 

phase to B phase, as shown in Figures 1 and 2. Remove 
the screws in the bus clip assembly and move the bus clip 
to  the  B-phase  position.  Fasten  the  bus  clip  assembly  in 
the new location with the slotted hex-head SEMS screws 
provided and tighten to 27–32 in-lb. 

 

Figure 1. Repositioning the bus clip assembly. 

Figure 1. Repositionnement de l’assemblage de la pince de 

barre omnibus. 

  2.  Prepare the breaker  module (for two breakers only).

 

Before installing the breakers on the module, remove the 
barriers, as shown in Figures 3 and 4. 

  3.  Install  the  circuit  breaker(s).

  Place  the  Belleville 

washers  and  hex-head  screws  into  the  line  straps  of  the 
circuit  breaker,  as  shown  in  Figure  4.  Position  the  ON 
side of the breaker on the module, as shown in Figure 4. 
Align  the  hex-head  screws  in  the  stud-post  holes  and 
tighten to 90–110 in-lb. Fasten the OFF side of the

  

Généralités 

Ces instructions s’appliquent aux numéros de catalogue suivants: 

•  Modules  de  disjoncteurs  AMC6FEB,  AMC4FEB, 

AMC6FEBH, ou AMC4FEBH. 

•  Cadres de disjoncteurs FEN, FEH, ou FEL.

 

 

 

AVERTISSEMENT 

Danger de choc électrique ou de blessure. Mettre le courant 
en avant du panneau ou du tableau de contrôle à OFF avant 
de  travailler  à  l’intérieur  de  cet  équipement  ou  d’en  retirer 
toute composante. Ne pas retirer ou installer les mécanismes 
de  protection  des  circuits  ou  tout  autre  composante  jusqu’à 
ce que le courant soit à OFF. 

Installation 

 

1.

 

Équilibrage de phase pour mécanismes deux-pôles sur 

systèmes trois-phases.

 Repositionner l’assemblage de la 

pince  de  barre  omnibus  de  phase  A  ou  C  à  phase  B,  tel 
qu’illustré  aux  Figures  1  et  2.  Retirer  les  vis  dans 
l’assemblage  de  barre  omnibus  et  déplacer  la  pince  de 
barre  omnibus  à  la  position  phase  B.  Fixer  l’assemblage 
de  barre  omnibus  dans  son  nouvel  emplacement  avec 
deux  vis  rainurées  à  tête  hexagonales  SEMS  fournies  et 
serrer à 27–32 lb.-po. 

 

Figure 2. Repositioning the bus clip to balance the load. 

Figure 2. Repositionner la pince de barre omnibus pour 

équilibrer la charge.

 

Spectra Series™ Power Panelboards 
Panneaux de distribution Spectra Series™ 

 

 

Circuit Breakers and Modules 
Disjoncteurs et Modules 

DEH40420 

Installation Instructions 

R02 

 

Instructions d’installation 

DEH40402 

Installation Instructions 

R02 

 

Instructions d’installation 

A & C Phase 
As Received 

A & B Phase 

B & C Phase 

Phases A & C 
telles que 
reçues 

Phases A & B 

Phases B & C 

Screws and Bus Assembly 

Assemblage des vis et de 

la barre omnibus 

SEMS Screws 

Vis SEMS 

A and C Phases 

Phases A et C 

B Phase 
Phase B 

  

 

 

  

Summary of Contents for FEL

Page 1: ...éralités Ces instructions s appliquent aux numéros de catalogue suivants Modules de disjoncteurs AMC6FEB AMC4FEB AMC6FEBH ou AMC4FEBH Cadres de disjoncteurs FEN FEH ou FEL AVERTISSEMENT Danger de choc électrique ou de blessure Mettre le courant en avant du panneau ou du tableau de contrôle à OFF avant de travailler à l intérieur de cet équipement ou d en retirer toute composante Ne pas retirer ou ...

Page 2: ...ncteur tel que montré à la Figure 4 Positionner le côté ON du disjoncteur sur le module tel que montré à la Figure 4 Aligner les vis à tête hexagonale dans les trous des colonnes de goujons et serrer à 90 110 lb po Fixer le côté OFF du disjoncteur aux ferrures de montage avec les vis à tête ronde et les rondelles plates et serrer à 27 32 po lb Répéter la procédure pour un deuxième disjoncteur tel ...

Page 3: ...onnector screw to the torque indicated on the rating label 5 Installer les cosses sur les extrémités charge du disjoncteur Utiliser le kit de pièces de cosses numéro FCALK218H pour les disjoncteurs deux bornes et FCALK318H pour les disjoncteurs trois bornes 6 Câbler les circuits Veuillez vous référer à l étiquette sur le disjoncteur pour le couple de serrage approprié 7 Installer les couvercles de...

Page 4: ...eferred to the GE Company g GE Consumer Industrial General Electric Company 41 Woodford Ave Plainville CT 06062 DEH40402 R02 0507 2007 General Electric Company Ces instructions n ont pas pour propos de couvrir tous les détails ou variations de l équipement ni de fournir des solutions pour tous les imprévus reliés avec les opérations causées par l installation ou l entretien Si des informations sup...

Reviews: