background image

 

Introduction 

 

Shunt Trip (Extended Range): 

 

A device designed to switch the Power Circuit 
Breaker OFF remotely. When energized a Shunt 
Release instantaneously activates the circuit 
breaker mechanism ensuring a rapid 
disconnection of the main contacts.  

Two Shunt trips can be mounted in each Power 
Circuit Breaker. The devices are available as 
factory mounted components or as field 
mountable devices. It is an easy-to-fit, clip-on unit, 
with simple plug-in connectors to the Secondary 
Disconnect Block. 

 

Table 1. Catalog Numbers and Ratings 

Catalog 

No. 

DC 

Voltage 

AC 

Voltage 

Rating* 

GSTG024D 

24V 

 

Continuous 

GSST024D 

24V 

 

Momentary 

GSTG048 

48V 

48V 

Continuous 

GSTG072 

70-72V 

 

Continuous 

GSTG120 

110-125V  120-125V 

Continuous 

GSST120 

110-130V  110-130V 

Momentary 

GSTG208A 

 

208V 

Continuous 

GSTG240 

220V 

240V 

Continuous 

GSST240 

220-240V  220-240V 

Momentary 

GSTG250D 

250V 

 

Continuous 

 

* Momentary Rated shunt trip requires wiring one or more NO 
(Normally Open) breaker aux contact(s) in series with the accessory to 
avoid coil damage. 

 

Use the following procedure to install the Shunt 
Trip accessory into the circuit breaker. 

 
1.   Verify that the rating on the Shunt Trip 
Mechanism identification plate matches the 
voltage rating required for the application, as listed 
in Table 1.  

 

2. Turn the breaker off and discharge the closing 
springs by depressing the OFF and ON buttons in 
the sequence OFF-ON-OFF. Verify that the breaker 
OFF-ON indicator shows OFF on a green 
background and that the charge indicator shows 
DISCHARGE on a white background. If installing in 
a draw-out type breaker remove breaker from 
adaptor (cassette) before continuing.  
 
3. Loosen the 6 screws on front cover (fascia) using 
a posidrive screw driver as shown in Fig 1.B  
Rotate the charging handle down and slide the 
front cover over the handle to remove the front 
cover as shown in Fig. 1.C . 
 
 
 
 
 
 
 

Summary of Contents for GSTG024D

Page 1: ...240V 220 240V Momentary GSTG250D 250V Continuous Momentary Rated shunt trip requires wiring one or more NO Normally Open breaker aux contact s in series with the accessory to avoid coil damage Use the following procedure to install the Shunt Trip accessory into the circuit breaker 1 Verify that the rating on the Shunt Trip Mechanism identification plate matches the voltage rating required for the ...

Page 2: ...s shown in Fig 3 Tilt the device backwards until the rear hooks engage in the slots on the mechanism top support plate as shown in Fig 4 Figure 3 Shunt Trip Inserting Figure 4 Shunt Trip Assembly 6 After installing the shunt release on the mechanism top plate connect the input wire assembly plug to the A5 A6 if installed in the first location or A12 A13 if installed in the fourth location location...

Page 3: ...e pad lock features of the breaker Figure 6 10 Fasten the 6 mounting screws of the fascia with the housing using a Pozidrive screwdriver Apply torque of 6Nm 4 42 ft lbs 11 When installing a GSST shunt trip device you must wire one or more Normally Open NO breaker auxiliary contact s in series with the shunt trip accessory coil In some cases multiple contacts in series are required to ensure reliab...

Page 4: ...Reference GSTG type Continuously Rated Shunt Trip Connection Scheme 4 ...

Page 5: ...0VDC Two 240VDC Three GE 41 Woodford Ave Plainville CT 06062 www geindustrial com 2019 General Electric Company DEH 41411 R2 05 19 5 These instructions do not purport to cover all details or variations in equipment nor to provide contingency to be met in connection with installation operation or maintenance Should further information be desired or should particular problems arise which are not cov...

Reviews: