CHAPTER 3: ELECTRICAL INSTALLATION
16
EPM 5000 series Advanced Power Meters
GE Multilin
Note: Unless otherwise specified, standard KYZ setup for Pulse Output 0 is positive Watt Hour,
Pulse Output 1 is negative Watt-Hour, and Pulse Output 2 is VA-hour. See table below for
standard rate.
Note: With Option R (available only with the EPM 5200P) the setup for Pulse Output 0 is positive
Watt-Hour, Pulse output 1 is positive VAR-hour, and Pulse output 2 is negative VAR-hour.
The scale factor for Wattage (KW or MW) and Full Scale Decimal Point Placement is selectable in
Programming Mode GROUP 1, FUNCTION
2
. Follow the Decimal Point Placement corresponding to the
Change in Level. A multiplication or division factor can be programmed. See Programming GROUP 0,
FUNCTION 6 for a different rate.
STANDARD RATE TABLE FOR WATTS
*
DECIMAL POINT PLACEMENT
(KW/MW)
CHANGE IN LEVEL
9999.0
1.0 Units W Hour
999.9
0.1 Units W Hour
99.99
0.01 Units W Hour
9.999
0.001 Units W Hour
*Units could be KiloWatts or MegaWatts.
2 0
2 1
2 2
2 3
2 4
2 5
2 6
2 7
2 8
K
Y
Z
K
Y
Z
K
Y
Z
P U L S E
O U T P U T 2
P U L S E
O U T P U T 1
P U L S E
O U T P U T 0
Figure 3.2
: KYZ Relay Connection for -NL2 Option
KYZ relay output (Form C), rated 200V, 100mA:
3 separate KYZ Outputs (labeled 0 through 2).
Summary of Contents for EPM 5300
Page 2: ......
Page 30: ...CHAPTER 4 COMMUNICATION INSTALLATION 26 EPM 5000 series Advanced Power Meters GE Multilin...
Page 70: ...CHAPTER 10 PROGRAMMING GROUP 1 66 EPM 5000 series Advanced Power Meters GE Multilin...
Page 88: ...CHAPTER 14 EXITING PROGRAMMING MODE 84 EPM 5000 series Advanced Power Meters GE Multilin...
Page 94: ...CHAPTER 15 PROGRAMMING QUICK REFERENCE 90 EPM 5000 series Advanced Power Meters GE Multilin...