DigitalFlow™ GF868 Startup Guide (1 and 2-Channel)
13
Chapter 1. Installation
1.7.5 Wiring an Alarms Option Card
The GF868 can accommodate 1 to 6 alarm option card(s). Each alarm option card provides three Form C relays
(A, B and C). The alarm relays on the option card are available in two types:
•
general-purpose
•
hermetically-sealed for Class I, Division 2 hazardous areas.
Chapter 4,
Specifications,
lists the maximum electrical ratings for the relays. Each alarm relay can be wired as
Normally Open
(NO) or
Normally Closed
(NC).
In setting up an alarm relay, it may be wired for either
conventional
or
fail-safe
operation. In fail-safe mode, the alarm
relay is constantly energized, except when it is triggered or a power failure or other interruption occurs. See Figure 6
for the operation of a NO alarm relay in both conventional and fail-safe mode.
Figure 6: Conventional and Fail-Safe Operation
C
NO
NC
NC
C
NO
NC
NC
C
NO
C
NO
Monitoring
Alarm
Device
Monitoring
Alarm
Device
Monitoring
Alarm
Device
Monitoring
Alarm
Device
not triggered
Conventional,
not triggered
Fail-Safe,
triggered
Conventional,
triggered or power failure
Fail-Safe,
Summary of Contents for DigitalFlow GF868
Page 2: ......
Page 4: ...ii no content intended for this page...
Page 30: ...Chapter 1 Installation DigitalFlow GF868 Startup Guide 1 and 2 Channel 20...
Page 42: ......
Page 58: ...48 DigitalFlow GF868 Startup Guide 1 and 2 Channel no content intended for this page...
Page 62: ...52 DigitalFlow GF868 Startup Guide 1 and 2 Channel no content intended for this page...
Page 68: ...Appendix C Optional Enclosures DigitalFlow GF868 Startup Guide 1 and 2 Channel 58...
Page 74: ...Warranty 64 DigitalFlow GF868 Startup Guide 1 and 2 Channel no content intended for this page...
Page 78: ......
Page 79: ......