DigitalFlow™ GF868 Programming Manual (2-Channel)
21
Chapter 1. Programming Site Data
Editing K Factors
1.
Press
[F2] = MULTK
to enter the MultiK option.
2.
Press
[F1] = NO
to disable or
[F2] = YES
to enable
Multiple K-factors
.
•
If you press
NO
, the GF868 returns to the
Advanced Features
prompt.
•
If you press
YES,
complete the steps below.
a.
The GF868 asks for the type of K factor. Press
[F1]
to select
CstV (
Custom velocity) or
[F2]
to select
CstR
(Custom Reynolds number).
•
If you enable
CstR
, you must also enter the
Kinematic Viscosity
of your gas, as listed in
Sound Speeds and Pipe
Size Data.
Use the numeric keys to enter a value, and press
[ENT].
b.
Press
[F1]
= NO
to retain the current K-factor table and return to the
Advanced Features
prompt, or press
[F2]
=
YES
to
Edit The K-factor Table.
Note:
If velocity vs. K-factor data was not provided with the Model GF868, the K-factor table can not be edited.
c.
Enter the
Number of K-factors
to be entered into the table. Press
[ENT]
. (The meter will only accept values from
2 to 20.)
IMPORTANT:
When editing the K-factor table, the velocities must be entered in increasing order.
d.
Enter the
Velocity Value
for K-factor number “x”. Press
[ENT]
. (The meter will only accept values from –30,000
to +30,000 ft/sec.)
e.
Enter the
K-factor
corresponding to velocity number “x”. Press
[ENT]
.
3.
Repeat steps c and d until all of the data points have been entered.
1.6.5e Procedure Options
After completing the above steps, the meter returns to the
ADVANCED FEATURES
prompt. Continue as follows:
•
To continue programming the meter, refer to the menu maps in Appendix A and navigate to the desired menu.
Then, proceed to the appropriate section of this manual for instructions.
•
To leave the
User Program
and retain the previous settings, press
[EXIT]
twice and then press
[F1] = NO
at the
SAVE
prompt. Any programming changes will be discarded and you will be returned to the data display.
•
To leave the
User Program
and return to measurement mode, press
[EXIT]
twice and then press
[F2] = YES
at the
SAVE
prompt. Your programming changes will be entered into the meter’s memory, and you will be returned to
the data display.
Summary of Contents for DigitalFlow GF868
Page 2: ......
Page 4: ...ii no content intended for this page ...
Page 95: ...DigitalFlow GF868 Programming Manual 2 Channel 85 Appendix A Menu Maps Appendix A Menu Maps ...
Page 96: ...86 DigitalFlow GF868 Programming Manual 2 Channel no content intended for this page ...
Page 104: ...Appendix A Menu Maps DigitalFlow GF868 Programming Manual 2 Channel 94 ...
Page 108: ...98 DigitalFlow GF868 Programming Manual 2 Channel no content intended for this page ...
Page 146: ...Warranty 136 DigitalFlow GF868 Programming Manual 2 Channel no content intended for this page ...
Page 150: ......
Page 151: ......