D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
PHASE DISTANCE THROUGH POWER TRANSFORMERS
CHAPTER 8: APPLICATION OF SETTINGS
8
The Zone 1 settings are:
Eq. 8-9
PHS DIST Z1 REACH
: "0.80"
PHS DIST Z1 RCA
: "85"
PHS DIST Z1 XMFR VOL CONNECTION
: "None"
PHS DIST Z1 XMFR CUR CONNECTION
: "Dy1"
The Zone 3 settings are:
Eq. 8-10
PHS DIST Z3 REACH
: "2.60"
PHS DIST Z3 RCA
: "89"
PHS DIST Z3 XMFR VOL CONNECTION
: "Yd11"
PHS DIST Z3 XMFR CUR CONNECTION
:
"None"