CHAPTER 5: SETTINGS
GROUPED ELEMENTS
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
5-189
5
Each of the six setting group menus is identical. Setting group 1 (the default active group) is active automatically when no
other group is active.
If the device incorrectly switches to group 1 after power cycling, upgrade the firmware to version 7.31 or later to correct
this issue.
5.7.3 Line pickup
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
LINE PICKUP
POWER SWING
DETECT
LOAD ENCROACHMENT
PHASE CURRENT
NEUTRAL CURRENT
WATTMETRIC
GROUND FAULT
GROUND CURRENT
NEGATIVE SEQUENCE
CURRENT
VOLTAGE ELEMENTS
LINE PICKUP
LINE PICKUP
FUNCTION: Disabled
Range: Disabled, Enabled
LINE PICKUP SIGNAL
SOURCE: SRC 1
Range: SRC 1, SRC 2
PHASE IOC LINE
PICKUP: 1.000 pu
Range: 0.020 to 30.000 pu in steps of 0.001
LINE PICKUP UV PKP:
0.700 pu
Range: 0.004 to 3.000 pu in steps of 0.001
LINE END OPEN PICKUP
DELAY: 0.150 s
Range: 0.000 to 65.535 s in steps of 0.001
LINE END OPEN RESET
DELAY: 0.090 s
Range: 0.000 to 65.535 s in steps of 0.001
LINE PICKUP OV PKP
DELAY: 0.040 s
Range: 0.000 to 65.535 s in steps of 0.001
AR CO-ORD BYPASS:
Enabled
Range: Disabled, Enabled
AR CO-ORD PICKUP
DELAY: 0.045 s
Range: 0.000 to 65.535 s in steps of 0.001
AR CO-ORD RESET
DELAY: 0.005 s
Range: 0.000 to 65.535 s in steps of 0.001
TERMINAL OPEN:
Off
Range: FlexLogic operand
AR ACCELERATE:
Off
Range: FlexLogic operand
Summary of Contents for D30 series
Page 10: ...x D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 534: ...5 324 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 670: ...iv D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Page 686: ...xvi D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL INDEX ...