If a High/Low voltage condition exists for longer than 5 seconds, the
compressor will be de-energized. The controller display will flash “Lo
LinE“ o and off while the condition exists.
•
Re-energization is automatic upon correction of the fault condition and af-
ter a delay cycle of about 2 minutes.
High and Low Voltage Protection at 115 VAC
Voltage Cutout: +/- 12.5 % (101 - 129 VAC)
Voltage Cut-In: +/- 7.5 % (106 - 124 VAC)
High and Low Voltage Protection at 230 VAC
Voltage Cutout: +/- 12.5 % (203 - 257 VAC)
Voltage Cut-In: +/- 7.5 % (213 - 247 VAC)
•
See the Caution in the front of this manual for additional information.
13.2
CE Comments
13.2.1
EMC Directive
This instrument has been tested to meet the European Electromagnetic Compat-
ibility Directive ( EMC Directive, 89/336/EEC). The Declaration of Confor-
mity for your instrument lists the specific standards to which the unit was
tested.
13.2.2
Low Voltage Directive (Safety)
In order to comply with the European Low Voltage Directive (73/23/EEC), this
instrument has been designed to meet the IEC 1010-1 (EN 61010-1) and IEC
1010-2-010 (EN 61010-2-010) standards.