Programming the Panel
28
The following describes how to program the
PHONE OPTION
settings that appear under
PARTITION 1
.
Dialer Abort (02005)
Phones Options-Global (Default=on)
This setting determines whether or not users can stop the first dialing attempt
of the panel (within the Dialer Abort Delay time setting) to report to the cen-
tral station. When this feature is on, alarm reports from sensors in groups 00-
20, 34, and 35 can be aborted by entering
CODE
(or
1
+
CODE
)
within
the Dialer Abort Delay time setting (defaulted to 30 seconds). Cancel and
restoral reports from these sensor groups are also aborted if the related alarm
report was aborted. Other reports that can be aborted include System Alarm
Tamper/Cancel, No Activity Alarm/Cancel, Touchpad Police and Auxiliary
Panic/Cancel, Recent Closing, and Two Trip Error. Fire alarm reports to the
central station cannot be aborted.
¾
To turn Dialer Abort off or on:
1. With the display showing
DIALER ABORT
OFF/ON
(current setting)
, press
1
(off) or
2
(on). The display flashes the entered setting.
2. Press
ƒ
and the display shows the new set-
ting.
Dialer Abort Delay (02006)
Phones Options-Global (Default=30 sec.)
This setting determines how much time (15 to 45 seconds) the user has to
enter the disarm command in order to prevent the panel from reporting to the
central monitoring station.
Note
For UL Listed systems, the combined time for the Entry Delay (0310) and Dialer
Abort Delay must not exceed 60 seconds.
¾
To change the Dial Abort Delay:
1. With the display showing
DIAL ABORT DELAY
nn
(current setting)
, enter the desired time
(15 to 45 seconds). The display flashes the
entered setting.
2. Press
ƒ
and the display shows the new set-
ting.
Cancel Message (02007)
Phones Options-Global (Default=on)
This setting determines whether or not the panel displays a cancel message
after the user disarms the system to clear an alarm condition.
¾
To turn Cancel Message off or on:
1.
With the display showing
CANCEL MESSAGE
OFF/ON
(current setting)
, press
1
(off) or
2
(on). The display flashes the entered setting.
2.
Press
ƒ
and the display shows the new set-
ting.
Pager Delay (02008)
Phones Options-Global (Default=15 sec.)
This setting determines how long a report is delayed to a pager (00-30 sec-
onds) after the panel dials the pager number.
Note
The Pager Delay time should not be set below 5 seconds unless absolutely neces-
sary.
¾
To set the Pager Delay time:
1. With the display showing
PAGER DELAY nn
(current setting)
, enter a two-digit time (00-
30). The display flashes the entered setting.
2. Press
ƒ
and the display shows the new set-
ting.
Call Wait Cancel (02009)
Phones Options-Global (Default=none)
This feature lets you set up a dialing prefix to disable the call waiting feature
before the panel makes its first dialing attempt to any programmed central
monitoring station, pager, or downloader phone number. The prefix can be up
to eight digits. For prefixes that require dialing * or #, press and hold for two
seconds
7
(for *) or
9
(for #).
¾
To set up Call Wait Cancel:
1. With the display showing
CALL WAIT CANCEL
__
(or current setting)
, enter the desired pre-
fix. The display flashes the entered setting.
2. Press
ƒ
and the display shows the new set-
ting.
DO NOT change this option from its default if the customer doesn’t
have call waiting. Verify with the customer that they have call waiting
with their phone service provider before changing this option from its
default. Changing this option from its default without call waiting will
prohibit the panel from calling the central station.