14 mm Proximity Transducer System 7200 Series Installation Manual
24
J. Output Noise
K. Indication of Fault Conditions
L. Effects of Incorrect Field Wiring
M. Materials
Coaxial
Connector
Barrier Strip
Case
Calibration
Terminals
Calibration
Resistor
Sealant
Calibration
Terminal
Grommet
Label
N. Environmental
Restrictions
Storage Temperature
Operating Temperature Range
Relative Humidity from
35° F to 212° F
(2° C to 100° C)
Less than 10 millivolts peak-to-peak when
terminated into a 0.01 microfarad capacitor
load or a standard Bently Nevada monitor plus
any high frequency noise which may be
present on the supply
If the probe or extension cable opens or
shorts, the output goes to within 2 volts of
supply or within 1 volt of common
When used with 7200 or 9000 monitors, the
Proximitor can be wired incorrectly in any
manner with no resulting damage
Gold-plated stainless steel
Polypropylene
Aluminum; Finish -
gold chromate
conversion process
Gold-plated brass
Silicone
FEP
Mylar (acetate laminate finish
)
-60° F to 212° F (-51° C to 100° C)
-60° F to 212° F (-51° C to 100° C)
100%
non-submerged (except connector)
Summary of Contents for Bently Nevada 7200 Series
Page 22: ...APPENDIX A 17 Figure A 1 14 mm Probe Ordering Information ...
Page 24: ...APPENDIX B 19 Figure A 3 14mm Extension Cable Ordering Information ...
Page 34: ...APPENDIX C 29 6 APPENDIX C SCALE FACTORS AND SENSITIVITY CURVES ...
Page 36: ...APPENDIX C 31 Figure C 2 Probe and One Foot Cable at Temperature ...
Page 38: ...APPENDIX C 33 Figure C 4 9 Metres Cable at Temperature ...
Page 42: ...APPENDIX C 37 Figure C 8 Effects of Flat Surface Side Clearance ...