background image

Becker VRP-SB-PID Series Natural Gas Controllers Instruction Manual  |  12

© 2016 General Electric Company. All rights reserved.

 

In either case (reverse or direct acting), a quick response  
of the output needle suggests the sensitivity of the PID  
still needs tuning.

I.   For a direct acting controller, turn the sensitivity drum  

to the right until the pressure just increases again. For a  
reverse acting controller, turn the sensitivity drum to the left  
until the pressure just decreases again.

J.   Repeat steps H and I until output pressure is stationary 

between atmospheric pressure and maximum power  
gas pressure.

K.  When the controller output is stationary between atmospheric 

and power gas pressure, and the sensitivity drum is adjusted 
such that any movement to the right would vent gas, the 
controller is approximately at “zero” dead band. “Zero” dead 
band is defined when a slow growing bubble (10-30 seconds) 
is detected from the exhaust port. Make small adjustments in 
adjustment drum until “zero” dead band condition is met. 

L.  To lock the deadband setting in place, insert the locking  

set screw into one of the radial holes in the adjustment  
drum. Using a torque wrench, torque to 1-2 inlb. Care  
should be taken not to exceed this level, as if the screw is  
over-tightened it may affect the calibration of the pilot. If a 
torque wrench is not available then torque the screw just 
enough so that it provides a light grip on the inner shaft.  
Recheck the vent port on the controller.

M.   Reconnect all tubing disconnected in step E. Refer to  

Table 8 on page 13 for correct derivative orifice and  
metering valve settings. Open the measured variable valve. 
Open the output block valve in order to begin control and 
make fine adjustments.

2.   Proportional Band Test
The purpose of this test is to check the proper operation of  
the feedback chamber. Leaks, misalignments or wrong internal 
parts can cause the PID to not function properly. The output  
valve must stay open to allow output pressure to communicate 
with the feedback chamber.

For a Direct Acting Controller:
The integral (top) chamber must be at atmospheric pressure.

A.  Remove plug from integral chamber and close reset valve 

(Figure 7). Tubing between derivative orifice and reset 
metering valve should stay connected.

Close reset 

valve 

Plug 

Feedback Module 

Derivative 

orifice 

Remove this 

plug  

Figure 7 - Proportional Band Test

B.   Change the sensing pressure until the output pressure is 

approximately 30% away from the power gas. For example,  
a VRP-PID- 40 needs the output adjusted to 30 psig, while a 
VRP-PID-80 and VRP-PID-125 need outputs of 60 psig and  
90 psig respectively.

C.   Consult the appropriate table from pages 6-8 depending  

on which model PID you have. Look at the left side of the  
table for the correct model number. Associate that model 
number with the corresponding control spring. Look at 
the chart under “Proportional Band” and choose the 
corresponding gain configuration of the PID. Look down for 
the point where the model and control spring row intersects 
with the proportional band/gain configuration column. This 
number is the amount of sensing pressure that must be input 
in order to see a 12 psig output change for a PID-40, 24 psig 
output change for a PID-80, or 30 psig change for a PID-125.

Example of Step C:
VRP-600-SB-PID-40, direct acting, high gain, yellow control spring

1.   Turn to page 6 and look in the left hand column to find 

VRP-600-SB-PID-40.

2.   The second column to the right shows the control spring 

range, and the third column reads “yellow control spring, 
25- 1306” for the model VRP-600-SB-PID-40.

3.   “With Small Ring” for a high gain pilot.

4.   Where the rows and columns intersect is “23 psig (159 kPa)”.

5.   Take note of the initial sensing pressure and initial output 

pressure. Change the sensing pressure 23 psig (159 kPa) from 
the initial value. The output gauge should only have changed  
12 psig (83 kPa) from its initial value.

D.   Reinstall the top feedback chamber plug. Open the reset valve, 

and check for leaks around the feedback module. 

For a Reverse Acting Controller:
The integral (bottom) chamber must have full output pressure.

A.   Adjust the sensing pressure such that the output is at full power 

gas pressure. Wait a couple of minutes, and close the integral 
valve. This locks full power gas pressure in the integral chamber.

B.   Follow steps B and C for a direct acting controller.

C.   Re-open the metering valve.

3.   Controller Test in PID Mode
Isolate controller from the actuator by positioning MCV in manual 
mode. The derivative orifice block should be set at 6. The power 
gas should be the maximum allowed for your controller (i.e. a 
PID-125 should have its power gas at 125 psig). The object of this 
test is to make sure the output pressure reaches zero or max in 
specified time.

This test is to be done once with the integral valve wide open, and 
once with the integral valve at #7. This test requires a timer.

To check that the output pressure drops to zero in specified time:
Start the test with sensing pressure 20% above setpoint (i.e., if  
the setpoint is 200 psig, raise it to 240 psig). The output pressure 
should reach its maximum (equal to power gas). Allow the PID 
chamber to become fully loaded by waiting 1-2 minutes. Lower 
the sensing pressure to 3% of the maximum spring range below 
the setpoint (i.e., if the setpoint is 200 psig, and the top of the 
control spring’s range is 320 psig, set your pressure to 200 - 
.03x320 = 190.4 pisg, approximately). Start your timer. The output 
pressure should jump down a little and then continue to lower 
steadily. Stop your timer when the output pressure has gone down 
to approximately 10% of its full range (i.e., ˜12.5% for a PID-125). 
This should take 10-20 seconds if the integral valve is wide open, 
and 1-2 minutes if it is at #7.

Summary of Contents for Becker VRP-SB-PID Series

Page 1: ...GE Oil Gas Becker VRP SB PID Series Natural Gas Controllers Instruction Manual GE Data Classification Public...

Page 2: ...REGULATIONS APPLICABLE AT THE SITE AND THE PARTICULAR REQUIREMENTS FOR OPERATION OF OTHER EQUIPMENT AT THE SITE THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT NOR TO...

Page 3: ...oportional plus derivative controller or VRP SB PD In VRP SB PD mode the controller can be used for highly unstable systems for example double stage cuts Table of Contents Page Page Introduction 1 Des...

Page 4: ...tive Ambient Temperature Range 20 F to 160 F 29 C to 71 C Steady State Gas Consumption Zero Approximate Weight 20 pounds 9kg Pressure Connections 1 4 inch female NPT Housing Meets NEMA 3 Classificatio...

Page 5: ...sing pressure decreases the net force on the diaphragm is up When spring and sensing diaphragm forces are equal to each other the controller is balanced and at steady state In the additional diagrams...

Page 6: ...output pressure has time to equalize on both sides of the orifice The adjustability of the orifice allows us to optimize the system If the restriction is too great the feedback delay will be too long...

Page 7: ...reserved Sensing Pressure Integral Derivative Output Derivative Integral Output Output Block Valve Exhaust P2 4 P 3 P P1 P4 P3 P2 P1 Feedback Module Power Gas Exhaust Sensing Pressure Figure 2 Direct...

Page 8: ...a 155 320 psig 1069 2206 kPa Pink 25 8240 24 psig 165 kPa 132 psig 910 kPa 165 psig 1138 kPa 295 600 psig 2034 4137 kPa Yellow 25 1306 85 psig 586 kPa 405 psig 2792 kPa 405 psig 2792 kPa VRP 1000 SB P...

Page 9: ...psig 2206 4137 kPa Yellow 25 1306 85 psig 586 kPa 380 psig 2620 kPa 380 psig 2620 kPa VRP 1000 SB PID 80 155 370 psig 1069 2551 kPa Burgundy 25 8239 174 psig 1200 kPa 122 psig 841 kPa 78 psig 538 kPa...

Page 10: ...165 psig 1138 kPa 355 600 psig 2448 4137 kPa Yellow 25 1306 85 psig 586 kPa 345 psig 2379 kPa 345 psig 2379 kPa VRP 1000 SB PID 125 215 430 psig 1482 2967 kPa Burgundy 25 8239 217 5 psig 1500 kPa 52 p...

Page 11: ...e a permanent offset due to an absence of the integral function Figure 4 Direct Acting VRP SB PID Controller Figure 5 Reverse Acting VRP SB PID Controller Power Gas Exhaust Vent Output Output Integral...

Page 12: ...61 psig 421 kPa 850 1350 psig 5861 9308 kPa 39 psig 270 kPa 227 psig 1565 kPa Violet 25 8073 1000 1500 psig 6895 10342 kPa 950 1500 psig 6550 10342 kPa 950 1500 psig 6550 10342 kPa 276psig 1903 kPa N...

Page 13: ...the VRP SB PID 80 there are higher pressure applications such as the Welker Jet Regulator or high pressure spring and diaphragm actuators And for even higher pressure applications such as ball valves...

Page 14: ...ber Associate that model number with the corresponding control spring Look at the chart under Proportional Band and choose the corresponding gain configuration of the PID Look down for the point where...

Page 15: ...d derivative orifice and controller gain for your specific application Derivative orifice can be adjusted by turning between numbers 0 and 6 0 represents the fastest response of the controller and 6 t...

Page 16: ...cy low amplitude fluctuations in the flow On the other hand the primary regulator will handle low frequency high amplitude flow changes The Trim run regulator of choice for power plants is the 900TE R...

Page 17: ...dQ Flexflo however in the case of P 50 psig 345 kPa the monitor regulator will be a Globe valve TO POWER PLANT INTEGRAL 12 HIGH GAIN SMALL RINGS DEAD BAND 1 4 SPRING TO CLOSE BALL VALVE MONITOR REGULA...

Page 18: ...E GLOBE VALVE TO COMPRESSOR TURBINE WORKING REGULATOR SPRING TO OPEN BALL VALVE VRP SB PID 125 REVERSE ACTING MONITOR REGULATOR SPRING TO CLOSE BALL VALVE WORKING REGULATOR SPRING TO OPEN GLOBE VALVE...

Page 19: ...GLOBE VALVE DEAD BAND 0 INTEGRAL CLOSED DEAD BAND 1 4 DEAD BAND 1 4 INTEGRAL 7 VRP SB PID 40 REVERSE ACTING INTEGRAL 12 HIGH GAIN SMALL RINGS VRP SB PID 40 DIRECT ACTING DERIVATIVE S 2 DERIVATIVE S 3...

Page 20: ...ating regulator Monitor serves as a security device that protects power plant in case of a failure in the regulator TO COMPRESSOR TURBINE VRP SB PID 40 REVERSE ACTING VRP SB PID 40 DIRECT ACTING INTEG...

Page 21: ...s preferred for better noise and vibration control but it results in a highly unstable system In order to compensate for this instability the first stage cut involves the conversion of the VRP SB PID...

Page 22: ...ler For a 3 15 psig 21 103 kPa output the proportional band is 23 psig 159 kPa In case of failure of working regulator the working monitor regulator will takeover control such acting as monitor VRP SB...

Page 23: ...ings to their original configurations Adjust orifice to original setting before disassembly procedure 3 Balance Valve Seat Inspection A Close output block valve Change the control pressure at least 5...

Page 24: ...8 O Ring 115 95 2670 9 8 32 x 1 2 SHCS 316 SS 98 2614 10 1 4 20 x 3 4 HHCS 98 3137 11 600 Spring Cartridge 30 7002 12 0 Ring 141 95 2671 13 Inner Tube 30 7003 14 600 1000 Inner Tube Cap 30 7007 VRP 1...

Page 25: ...5 1177 3 O Ring 012 95 2615 4 1 2 20 SS Jam Nut 98 3056 5 600 Top Space 30 7050 6 1 4 NPT Vent Elbow 01 2572 VRP 1000 1500 Sensing Assembly MAOP 1500 psig 6 2 1 3 4 6 8 5 7 4 9 10 Key Description Part...

Page 26: ...n w o Hole 30 7059 3 Small Washer 30 7014 4 O Ring 012 95 2615 5 Diaphragm w Hole 30 7011 6 8 32 x 1 1 2 SHCS 98 3145 7 Upper Feedback Chamber 30 7035 8a High Gain Ring 30 7051 8b Middle Gain Ring 30...

Page 27: ...agm w Conv 25 1027 6 1 4 NPT Top Body 35 1557 7 Top Inside Piston 35 1528 8 Sensitivity Spacer 25 1015 9 Lexan Cover 25 1034 10 Adjusting Drum 35 1534 11 Thrust Bearing 25 1062 12 1 4 NPT Bottom Body...

Page 28: ...82 PID 80 Bottom Cap Assembly 1 2 4 6 3 7 5 Key Description Part No 1 1 4 20 x 3 4 HHCS 98 3137 2 SS Spring Nut 30 7048 3 Fixed Spring 135 Wire 30 7069 4 3 8 16 x 3 4 HHCS 98 2580 5 Bottom Spring Cart...

Page 29: ...leed Control The AB maintains minimum pressure differential across the cylinder AB control is required to provide the necessary output to operate the control valve under all design conditions VB 250 V...

Page 30: ...G Step 2 Insert the Spacer B into the Strainer C as shown in Figure 2 Place the Spacer Strainer combination onto the Seat Assembly A Step 3 Insert a Balance Valve Assembly D Step 4 Secure the assembl...

Page 31: ...around the valve seat and the back end of the retainer as shown in Figure 4 and Figure 5 Step 11 If a leak is found check the o ring integrity contamination between the balance valve D and the seat A...

Page 32: ...the Pilot Post Outside Piston combination through the Top Body G and attach it to the Top Inside Piston M with 2 8 32 x 1 2 SHCS I Bottom Body Piston Assembly Figure 7 Step 15 Install 012 O rings K i...

Page 33: ...from the Bottom Body H Step 23 Install one Convoluted Diaphragm R oriented as shown in Figure 9 onto each Washer Q Step 24 Install another Washer Q onto each Piston J M with grooves facing the Diaphr...

Page 34: ...27 Press fit the Thrust Bearing W into the Adjusting Drum V Make sure that the stamp lettered surface of the Thrust Bearing W is fit with the bottom Drum V surface as shown in Figure 10 V W Confirm t...

Page 35: ...kwise until they stop D Mark the Bodies G and H with Extensions from lines already on the Diaphragms R as shown in Figure 13 E Finally by drawing a line exactly between the two lines on the Bodies G a...

Page 36: ...o lines from Step 29E Fasten the Top Body G assembly to the Sensitivity Spacer X with 6 1 4 20 x 3 4 HHCS Z Torque to 100 110 in lbs Step 32 Secure the Bottom Body H assembly to the Sensitivity Spacer...

Page 37: ...80 Figure 18 place the Fixed Spring DD onto the Spring Nut T Secure the Fixed Spring DD by fastening the Bottom Spring Cartridge CC to the Bottom Body H with 6 1 4 20 x 3 4 HHCS Z Torque to 100 110 in...

Page 38: ...s 20 22 Step 34 Take the VRP SB PID that you assembled after step 33 and turn right side up again Mount the PID to the Bracket CCCC using 2 SS 3 8 Washers DDDD SS 3 8 Lockwashers EEEE and 3 8 16 x 3 4...

Page 39: ...Install a Small Washer KK onto the Small Piston LL with grooves facing the Convoluted Diaphragm JJ Step 39 Place the Diaphragm JJ Piston LL and Washer KK on top of the PID Spring Spacer MM Step 40 Se...

Page 40: ...L from Diaphragm Assembly 2 all the way into the Outside Piston J of the Top Body G thereby compressing the spring Feedback Chamber Assembly Figures 27 31 Step 47 Bolt the Lower Feedback Chamber TT on...

Page 41: ...n of the chamfer on each of the Middle Gain Rings AAA shown in Figure 30 Move to Step 51 C For a High Gain Pilot Figure 31 follow Step 50A except add the High Gain Rings BBB on both sides of Diaphragm...

Page 42: ...he Bottom Piston EEE while holding it in a vise Torque to 140 160 in lbs Move to Step 52 B For a VRP 1000 1500 SB PID Figure 33 36 fasten the Thread Extension FFF to the Inner Tube CCC using a 1 2 20...

Page 43: ...all Piston LL Place a Convoluted Diaphragm R onto the Small Piston LL using the orientation shown in Figure 35 Slide a Small Washer KK onto the Small Piston LL D Insert a 145 O Ring GGG into the Botto...

Page 44: ...embly from Step 52 onto the Adjusting Screw JJJ Step 54 Thread the Aluminum Bearing Nut LLL onto the Screw JJJ from the bottom Leave some room below the Bearing Nut LLL and thread a 1 2 20 SS Left Han...

Page 45: ...tep 56 This step is dependent on the model of PID being assembled A For a VRP 600 SB PID place the Top Spacer PPP below the assembly from Step 51A Thread the Small Piston II from Diaphragm Assembly 1...

Page 46: ...VRP 1000 1500 SB PID place the Bottom Spacer SSS below the Adapter Block HHH Thread the Small Piston ll from Diaphragm Assembly 1 into the Small Piston LL from Step 51D Thread the Small Piston II all...

Page 47: ...assembly from Step 55 into the Spring Chamber DDD or FFF Fasten the Tube Cap OOO to the Inner Tube CCC with 4 8 32 x 1 2 SHCS 316 SS I Use Tube Cap SS 000 and 8 32 x 1 2 SHCS Alloy I for the 1500 Mod...

Page 48: ...g top cap assembly down You will feel a firm engagement of the cap assembly in place At this time orient the cap assembly such that the mounting holes are in line with the pressure ports Bolt the Cap...

Page 49: ...ools 1 Allen wrenches 9 64 3 16 1 8 2 Open wrenches 7 16 3 4 11 16 5 16 3 Socket wrenches 3 8 drive 7 16 3 4 Deepwell 13 Pt 4 6 adjustable wrench 5 Screwdrivers Philips head standard 6 Soft blow hamme...

Page 50: ...as Controllers Instruction Manual 48 2016 General Electric Company All rights reserved 98 3231 98 3232 98 3230 98 3238 98 2614 316 SS 98 3269 Alloy 98 3237 98 2684 98 3181 98 3227 98 2761 Appendix B P...

Page 51: ...49 GE Oil Gas 2016 General Electric Company All rights reserved Appendix B Parts Silhouettes Cont d Washers and Nuts 30 7053 25 1016 25 1065 98 3056 30 7014 30 7017 98 2500 98 3213...

Page 52: ...Becker VRP SB PID Series Natural Gas Controllers Instruction Manual 50 2016 General Electric Company All rights reserved 30 7011 25 1027 30 7032 Appendix B Parts Silhouettes Cont d Diaghragm...

Page 53: ...51 GE Oil Gas 2016 General Electric Company All rights reserved 95 2674 95 2670 95 2615 95 2609 95 2671 95 2665 95 2672 Appendix B Parts Silhouettes Cont d O Rings...

Page 54: ...ax 81 03 6890 4620 KOREA Phone 82 2 2274 0748 Fax 82 2 2274 0794 MALAYSIA Phone 60 3 2161 0322 Fax 60 3 2163 6312 MEXICO Phone 52 55 3640 5060 THE NETHERLANDS Phone 31 15 3808666 Fax 31 18 1641438 RUS...

Reviews: