15 | GE Oil & Gas
© 2016 General Electric Company. All rights reserved.
Example Application #1
Power Plant Station with Globe Style Control Valve
(4” & 6” Globe - 2” Start-up/Trimmer Run)
(8” & 10” Globe - 3” Start-up/Trimmer Run)
4”, 6”, 8” and 10” Globe Valves require assistance from a Low
Flow/Trimmer Run.
A Low Flow/Trimmer Run is used for the start of power plants.
It is also used in handling small variations in the load from
power plants.
For this example, the typical Low Flow/Trimmer Run setup using
RedQ™ Flexflo 900TEs is shown. Here the monitor regulator is a
RedQ™ Flexflo, however, in the case of ΔP < 50 psig (345 kPa) the
monitor regulator will be a Globe valve.
TO POWER
PLANT
INTEGRAL
=12
HIGH GAIN
(SMALL RINGS)
DEAD BAND
= -1/4
SPRING TO CLOSE BALL VALVE
MONITOR REGULATOR
WORKING REGULATOR
SPRING TO OPEN GLOBE VALVE
VRP-SB-PID-125
REVERSE ACTING
DERIVATIVE
S=2
DEAD BAND = 0
HIGH GAIN
(SMALL RINGS)
INTEGRAL=7
DERIVATIVE
S=3
VRP-SB-PID-40
DIRECT ACTING
S=3
S=3
POWER GAS LINE
JACKET LINE
OUTPUT LINE
SENSING LINE
KEY
(1)
FLOW
(1)
ALL LINES ARE SEPARATE, INTERSECTING LINES DO NOT IMPLY CONNECTIONS
FEP 600-CH w/
SMALL INLET
ORIFICE
FEP 600-CH w/
SMALL INLET
ORIFICE
VB-250
VOLUME
BOOSTER
900TE FLEXFLO REGULATORS
Recommended Applications:
A. Moderate pressure drops 300 - 500 psi
B. Pipeline Heater and Filter recommended.