31-5000560   Rev. 5

21

Step 3 - Installation of the Outdoor Unit (Cont.)

Installation Instructions

F.  System Evacuation

NOTE–

 Do not open service valve.

•  

Remove the suction line cap and attach a micron gauge 
and vacuum pump. The port is 5/16”, an adapter may be 
needed.

•  

Evacuate the system to at least 350 microns.

•  

Close the vacuum pump valve and check the micron 
gauge.  If the gauge rises above 150 microns in 60 
seconds, the evacuation is incomplete or there is a leak 
in the system.  If the gauge does not rise above 150 
microns in 60 seconds, the evacuation is complete.

•  

Once evacuation is complete, remove the adapter and 
hose connection from the suction line port and replaced 
the cap.

E.  Leak Test 

Perform the following steps for EACH line set. The primary 
service valve has a 5/16 port, an adapter may be necessary.

•  Remove the cap on the service valve.

•  Using a tank of dry nitrogen and approved regulator, charge 

the system with 150 psig of dry nitrogen using mini-split 
adapter to connect the valve. 

•  Check for leaks at the flare fittings using soap bubbles 

or another detection device.  If a leak is detected, make 
repairs to the fittings and recheck. Proceed if no leaks are 
detected within 3 minutes.

•  Using the same tank/regulator, charge the system to  

300 psig.

•  Check for leaks as earlier. Proceed if no leaks are detected 

within 3 minutes.

•  Using the same tank/regulator, charge the system to  

500 psig.

•  Check for leaks as earlier.  Keep system pressurized for at 

least 20 minutes.

WARNING

 Do not use acetylene, oxygen or 
compressed air or mixtures containing air, 

oxygen, or combustible gases for pressure testing.  Do not 
use mixtures of hydrogen containing refrigerant and air above 
atmospheric pressure for pressure testing as they may 
become flammable and could result in an explosion.  
Refrigerant, when used as a trace gas, should only be mixed 
with dry nitrogen for pressurizing units.  Failure to follow 
these recommendations could result in death or serious injury 
as well as equipment or property damage.

D.  Install Copper Lineset

•  

Line set sizes are determined by the indoor unit. See 
indoor spec for information. The outdoor unit ships with 
port adapters to reduce or enlarge the flare port sizes 
when needed. If connecting to 24K models with 3/8” & 5/8” 
ports, adapters must be ordered separately..

•  

Cut the line set to length.

•  

Place nut over the pipe and then flare with the R-410A 
flaring tool.  

    

NOTE: 

Follow standard practices for creating pipe flares.  

When cutting and reaming the tubing, use caution to 
prevent dirt or debris from entering the tubing.  Remember 
to place nut over the tubing before flaring.

•  

To join the line set, directly align the tubing flare to the 
fitting on the other pipe.  Slide the nut onto the fitting and 
hand tighten.

•  

Torque the fittings according to the specifications shown in 
the torque chart below.

Forced fastening without careful centering will damage the 
threads and cause a refrigerant leak.

Pipe Diameter (ø)

Fastening torque

1/4”

18N.m/13.3Ft.lbs

3/8”

42N.m/30.1Ft.lbs

1/2”

55N.m/40.6Ft.lbs

5/8”

60 N.m/44.3Ft.lbs

•  

Two wrenches are required to join the flare connection; 
one standard wrench and one torque wrench adjusted to 
the proper settings.

•  

Repeat the process for attaching the 
other end of the line set.

CAUTION

Half union

Flare nut

Torque wrench

Spanner

Indoor Unit

Outdoor Unit

itioned 

Indoor Unit

If all indoor unit are
the outdoor units.

e el

di

If the outdoor unit is 

 

than one or more indoor units.
(If lower than one or more indoor units.)

Outdoor Unit

Summary of Contents for ASH218JCDDA

Page 1: ...panish version please visit GEAppliancesairandwater com L aspect peut varier selon le num ro de mod le Ce manuel d installation est uniquement imprim en anglais Pour la version fran aise ou espagnole...

Page 2: ...age To receive a 10 year compressor and parts warranty registration is required within 60 days of installation ____________________________________ Model number ____________________________________ Se...

Page 3: ...ndoor temperature to 68 F 20 C The indoor display will flash BP for five seconds and shut down automatically The system can now be used normally Note The automatic tests can also be by passed by setti...

Page 4: ...ave been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with the heat pump syst...

Page 5: ...ve a collapsed deformed or discolored portion especially on the interior surface Otherwise the expansion valve or capillary tube may become blocked with contaminants Improper line sizing will degrade...

Page 6: ...aring tool Hex wrench Hole saw 2 1 4 Insulation Refrigerant scale Level Manifold gauge set Measuring tape Micron gauge Mini split adapter 5 16 F to 1 4 M Nitrogen Pipe cutter PVC pipe Razor knife Ream...

Page 7: ...k E 12k 12k E 7k 18k D 9k 18k D 12k 18k D THREE ZONE 7k 7k 7k E 7k 7k 9k E 7k 9k 9k E 7k 7k 12k E 9k 9k 9k E 7k 9k 12k E 9k 9k 12k E 7k 12k 12k E 7k 7k 18k D 9k 12k 12k E Models that may require adapt...

Page 8: ...k A B 1 D 2 24k A C 1 2 THREE ZONE 9k 9k 9k E 7k 9k 12k E 9k 9k 12k E 7k 12k 12k E 7k 7k 18k 9k 12k 12k E 7k 9k 18k 9k 9k 18k 12k 12k 12k E 7k 12k 18k 7k 7k 24k A C 1 2 7k 9k 24k A C 1 2 9k 9k 24k A C...

Page 9: ...See Notes 1 and 2 Port E Required Adapter TWO ZONE 7k 24k A C 1 2 9k 18k 9k 24k A C 1 2 12k 18k 12k 24k A C 1 2 18k 18k 18k 24k A C 1 2 24k A C 1 2 24k A C 1 2 THREE ZONE 7k 7k 18k 7k 7k 24k A C 1 2 7...

Page 10: ...7k 18k 7k 7k 7k 24k A C 1 2 7k 7k 9k 9k E 7k 7k 9k 12k E 7k 7k 9k 18k 7k 7k 9k 24k A C 1 2 7k 7k 12k 12k E 7k 7k 12k 18k 7k 7k 12k 24k A C 1 2 7k 7k 18k 18k 7k 7k 18k 24k A C 7k 9k 9k 9k E 7k 9k 9k 1...

Page 11: ...2 7k 7k 7k 9k E 24k A C 1 2 7k 7k 9k 9k E 24k A C 1 2 7k 9k 9k 9k E 24k A C 1 2 9k 9k 9k 9k E 24k A C 1 2 7k 7k 7k 12k E 24k A C 1 2 7k 7k 9k 12k E 24k A C 1 2 7k 7k 7k 12k E 12k E 7k 7k 7k 12k E 18k...

Page 12: ...t 28 700mm between the protection wall and the outdoor unit for air circulation to ventilate Install the outdoor unit in a place where water can drain Contact GEA Ductless for assistance if the above...

Page 13: ...000 Above12 300 Above 40 1000 Above 177 4500 Above 24 600 If wall is half the height of the unit 8 250 If wall is between half the height of the unit and the same height of the unit 12 300 Select the...

Page 14: ...coils Do not install the outdoor unit near the edge of a balcony Otherwise children may climb onto the outdoor unit and fall off of the balcony Do not install the outdoor unit in the following areas A...

Page 15: ...e lower hooks engage the brackets see illustration Verify the unit is secured and flush to the wall Indoor Unit installation is finished at this time F Condensate Drainage Pipe Verify the condensate d...

Page 16: ...iagram only demonstrates the wiring connection between outdoor indoor for dual zone as an example 1 2 3 1 2 3 1 L 2 L A B t i n U r o o d t u O AC 208 230 Volt Supply L1 to L1 L2 to L2 ground to groun...

Page 17: ...the wall bracket and where to cut the hole for piping NOTE Some models may not have a cardboard template in this case a manual measurement is needed to determine the piping hole location When mounting...

Page 18: ...poor terminal connections C Electrical Connections for the Outdoor Unit WARNING RISK OF ELECTRIC SHOCK Could cause injury or death Make sure power is off before touching wires NOTE Be certain all wiri...

Page 19: ...ply L1 to L1 L2 to L2 Outdoor Unit Indoor Unit A Outdoor unit Power Wiring 3 2 1 N L C 2 1 N L Indoor unit A Control Wiring 4 Wire 14 AWG Stranded 4 3 To Service Disconnect 1 2 3 White Black Red Green...

Page 20: ...B Indoor unit C Indoor unit D 3 2 1 N L C 3 2 1 N L C 3 2 1 N L C Strain Relief Brackets E 3 2 1 N L C Model Number Factory Charge Total Pipe Length of factory charge Additional charge rule Branch Ma...

Page 21: ...ining refrigerant and air above atmospheric pressure for pressure testing as they may become flammable and could result in an explosion Refrigerant when used as a trace gas should only be mixed with d...

Page 22: ...move the cap from the liquid line valve Using a hex wrench open the valve then replace and tighten the cap securly to avoid leaks Remove the cap from the suction line valve Using a hex wrench open the...

Page 23: ...g or removing the remote controller from the remote control holder cleaning methods precautions for operation etc Review precautions for operation Recommend that the user read the Operating Instructio...

Page 24: ...been maintained annually by a licensed HVAC technician proof required Damage caused by a used or unapproved component or part by GE Appliances a Haier company e g a used and or unapproved condenser a...

Page 25: ...of a new building but subsequent purchases will receive the remainder of the Standard Base Warranty The remedy provided in this warranty is exclusive and is granted in lieu of all other remedies This...

Page 26: ...26 31 5000560 Rev 5 Notes...

Page 27: ...LIRE ATTENTIVEMENT CONSERVEZ CES INSTRUCTIONS Instructions d installation Multizone sans conduit avec unit s int rieures murales hautes 31 5000560 Rev 5 11 22 GEA...

Page 28: ...jours suivant l installation ASH218JCDDA ASH324JCDDA ASH436JCDDA Cooling 14 F to115 F Heating 4 F to 75 F ASH220NCDDA ASH324NCDDA ASH436NCDDA ASH542JCDDA Cooling 14 F to115 F Heating 15 F to 75 F NOTE...

Page 29: ...mode d int rieur au mode Dry en premier puis r glez la temp rature int rieure 20 C 68 F BP clignotera sur l afficheur int rieur pendant cinq seconds puis s teindra automatiquement Le syst me peut mai...

Page 30: ...es renseignements dans ce manuel doivent tre observ s afin de minimiser le risque d incendie de d charge lectrique ou de blessure Utilisez cet quipement uniquement aux fins auxquelles il est fait ment...

Page 31: ...Un dimensionnement incorrect de la tuyauterie va diminuer le rendement Les pointes de pression du r frig rant R410A sont beaucoup plus lev es que celles du R22 Utilisez une tuyauterie en cuivre dont l...

Page 32: ...A Cl hexagonale Scie cloche 2 1 4 po Isolant Balance de r frig rant Niveau Manom tre de pression d admission d finir Ruban mesurer Microvacuom tre Adaptateur mini split 5 16 po F 1 4 po M Azote Coupe...

Page 33: ...k E 7k 18k D 9k 18k D 12k 18k D TROIS ZONE 7k 7k 7k E 7k 7k 9k E 7k 9k 9k E 7k 7k 12k E 9k 9k 9k E 7k 9k 12k E 9k 9k 12k E 7k 12k 12k E 7k 7k 18k D 9k 12k 12k E 0RGqOHV SRXYDQW QpFHVVLWHU GHV DGDSWDWH...

Page 34: ...8k D 18k 24k A B 1 D 2 18k 24k A B 1 D 2 24k A C 1 2 TROIS ZONE 9k 9k 9k E 7k 9k 12k E 9k 9k 12k E 7k 12k 12k E 7k 7k 18k 9k 12k 12k E 7k 9k 18k 9k 9k 18k 12k 12k 12k E 7k 12k 18k 7k 7k 24k A C 1 2 7k...

Page 35: ...urs varient pour mod le 24K Voir notes 1 et 2 Orifice E Adaptateur requis DEUX ZONE 7k 24k A C 1 2 9k 18k 9k 24k A C 1 2 12k 18k 12k 24k A C 1 2 18k 18k 18k 24k A C 1 2 24k A C 1 2 24k A C 1 2 TROIS Z...

Page 36: ...UATRE ZONE 7k 7k 7k 7k E 7k 7k 7k 9k E 7k 7k 7k 12k E 7k 7k 7k 18k 7k 7k 7k 24k A C 1 2 7k 7k 9k 9k E 7k 7k 9k 12k E 7k 7k 9k 18k 7k 7k 9k 24k A C 1 2 7k 7k 12k 12k E 7k 7k 12k 18k 7k 7k 12k 24k A C 1...

Page 37: ...7k 7k 9k E 12k E 7k 7k 7k 9k E 18k 7k 7k 7k 7k E 24k A C 1 2 7k 7k 7k 9k E 24k A C 1 2 7k 7k 9k 9k E 24k A C 1 2 7k 9k 9k 9k E 24k A C 1 2 9k 9k 9k 9k E 24k A C 1 2 7k 7k 7k 12k E 24k A C 1 2 7k 7k 9k...

Page 38: ...p ex pr s de b timents etc o elle peut tre prot g e de la brise marine qui peut l endommager rigez un mur de protection autour de l unit pour bloquer la brise marine s il est impossible d viter d inst...

Page 39: ...neige ou du vent Installez un coupe vent pour prot ger l unit contre le vent 3 Installation and maintenance space Selection of installation location of outdoor Above 12 300 Above 40 1000 Above 16 400...

Page 40: ...dditifs qui r sistent la corrosion ou la rouille afin de prot ger les serpentins de l unit N installez pas l unit ext rieure pr s du bord d un balcon Autrement les enfants peuvent grimper sur l unit e...

Page 41: ...r de d charge de traction Replacez les deux plaques de recouvrement et abaissez l enveloppe frontale une fois les connexions au bornier termin es eWDSH QVWDOODWLRQ GH O XQLWp LQWpULHXUH 6XLWH Plaque d...

Page 42: ...llustre seulement les connexions entre les unit s int rieure et ext rieure dans le cas d une zone double titre d exemple 1 2 3 1 2 3 1 L 2 L A B t i n U r o o d t u O AC 208 230 Volt Supply L1 to L1 L...

Page 43: ...yauterie REMARQUE Le gabarit en carton n est pas fourni avec certains mod les Il faudra alors effectuer manuellement les mesures afin de d terminer l emplacement du trou pour la tuyauterie Pendant le...

Page 44: ...aque est serr e Assurez vous que le c ble torsad 14 4 est fix sous la ferrure serre c ble Assurez vous que toutes les connexions sont solides REMARQUE L omission de suivre les directives de c blage pe...

Page 45: ...0 volts L1 L1 L2 L2 Unit ext rieure Unit int rieure A Outdoor unit Power Wiring 3 2 1 N L C 2 1 N L Indoor unit A Control Wiring 4 Wire 14 AWG Stranded 4 3 To Service Disconnect 1 2 3 White Black Red...

Page 46: ...ASH324JCDDA 67 100 82 197 ASH436JCDDA 90 131 82 230 ASH220NCDDA 69 66 82 165 ASH324NCDDA 82 100 82 197 ASH436NCDDA 102 131 82 230 ASH542JCDDA 113 164 82 262 Instructions d installation eWDSH QVWDOODWL...

Page 47: ...tez une fuite effectuez la r paration des raccords et faites un nouveau contr le Continuez si n avez pas d tect de fuite pendant 3 minutes En utilisant le m me r servoir r gulateur chargez le syst me...

Page 48: ...de recharge si aucune tiquette n est pr sente Retirez le couvercle de la valve de la tuyauterie de liquide l aide d une cl hexagonale ouvrez la valve puis remettez et ajustez le couvercle Retirez le...

Page 49: ...pr cautions d utilisation Nous recommandons que l usager lise attentivement les Instructions d utilisation 7HVW GX V VWqPH Veuillez expliquer au client comment faire fonctionner le syst me en utilisa...

Page 50: ...ent ou de conditions similaires Un Produit qui n a pas t install ou r par par un technicien agr en chauffage ventilation et climatisation La main d uvre et les services connexes pour la r paration ou...

Page 51: ...mplacement de tout autre recours Cette garantie ne couvre pas les dommages accessoires ou indirects Certains tats ou provinces ne permettent pas l exclusion des dommages accessoires ou indirects donc...

Page 52: ...52 31 5000560 Rev 5 Notes...

Page 53: ...LEA CUIDADOSAMENTE GUARDE ESTAS INSTRUCCIONES Instrucciones de instalaci n Multizona sin ductos con unidades interiores de pared alta 31 5000560 Rev 5 11 22 GEA...

Page 54: ...encuentran en la etiqueta del lado de la bomba de calor as como la fecha de compra Adjunte su comprobante de compra a este manual para ayudarlo a obtener el servicio de garant a si es necesario Para...

Page 55: ...68 F 20 C En la pantalla interior parpadear BP durante cinco segundos y sta luego se apagar de forma autom tica El sistema se podr usar ahora de forma normal Nota Las pruebas autom ticas tambi n se po...

Page 56: ...zar un servicio que requiere el ingreso al sistema de refrigeraci n sellada las regulaciones federales requieren que el trabajo sea realizado por un t cnico que posea una certificaci n Clase II o Univ...

Page 57: ...inadecuado reducir el rendimiento La presi n m xima de R410A es muy superior a R22 Use una tuber a de cobre con el grosor de pared adecuado A fin de evitar la rotura de la tuber a evite realizar curva...

Page 58: ...llador Phillips n 2 Taladro Abocardador de 45 Llave Hexagonal Sierra de Agujero de 2 1 4 Aislante Nivel Calibrador de Colector Cinta de Medici n Medidor de Micrones Adaptador para Mini Split 5 16 H a...

Page 59: ...k D 12k 18k D TRES ZONE 7k 7k 7k E 7k 7k 9k E 7k 9k 9k E 7k 7k 12k E 9k 9k 9k E 7k 9k 12k E 9k 9k 12k E 7k 12k 12k E 7k 7k 18k D 9k 12k 12k E Modelos que pueden requerir adaptadores 1 Estos modelos 24...

Page 60: ...4k A C 1 2 18k D 18k 24k A B 1 D 2 18k 24k A B 1 D 2 24k A C 1 2 TRES ZONE 9k 9k 9k E 7k 9k 12k E 9k 9k 12k E 7k 12k 12k E 7k 7k 18k 9k 12k 12k E 7k 9k 18k 9k 9k 18k 12k 12k 12k E 7k 12k 18k 7k 7k 24k...

Page 61: ...adores var an en relaci n al Modelo de 24K Lea las Notas 1 y 2 Adaptador requerido del puerto E DOS ZONE 7k 24k A C 1 2 9k 18k 9k 24k A C 1 2 12k 18k 12k 24k A C 1 2 18k 18k 18k 24k A C 1 2 24k A C 1...

Page 62: ...uerido del puerto E CUATRO ZONE 7k 7k 7k 7k E 7k 7k 7k 9k E 7k 7k 7k 12k E 7k 7k 7k 18k 7k 7k 7k 24k A C 1 2 7k 7k 9k 9k E 7k 7k 9k 12k E 7k 7k 9k 18k 7k 7k 9k 24k A C 1 2 7k 7k 12k 12k E 7k 7k 12k 18...

Page 63: ...7k 9k E 9k E 7k 7k 7k 9k E 12k E 7k 7k 7k 9k E 18k 7k 7k 7k 7k E 24k A C 1 2 7k 7k 7k 9k E 24k A C 1 2 7k 7k 9k 9k E 24k A C 1 2 7k 9k 9k 9k E 24k A C 1 2 9k 9k 9k 9k E 24k A C 1 2 7k 7k 7k 12k E 24k...

Page 64: ...n un lugar tal como edificios cercans etc donde se encuentre protegida de la brisa del mar la cual podr da ar la misma Si no es posible evitar la instalaci n de la unidad exterior cerca de la costa ma...

Page 65: ...nstale un deflector de viento para evitar la exposici n a este ltimo 3 Installation and maintenance space Selection of installation location of outdoor Above 12 300 Above 40 1000 Above 16 400 Above 16...

Page 66: ...aditivos a prueba de corrosi n y antioxidantes para proteger las bobinas de la unidad No instale la unidad externa cerca del extremo de un balc n De otro modo los ni os podr n trepar sobre la unidad e...

Page 67: ...s protectoras y baje la carcasa frontal una vez completado el cableado del bloque terminal C Instale el Agujero de la Tuber a Siempre use tuber as de cobre nuevas y limpias Nunca vuelva a usar una tub...

Page 68: ...exi n del cableado entre interior y exterior para zona dual 1 2 3 1 2 3 1 L 2 L A B t i n U r o o d t u O AC 208 230 Volt Supply L1 to L1 L2 to L2 ground to ground C 3 L 2 N 1 A t i n U r o o d n I C...

Page 69: ...ara la tuber a NOTA Es posible que algunos modelos no cuenten con una plantilla de carb n en este caso ser necesaria una medici n manual para determinar la ubicaci n del agujero de la tuber a Al monta...

Page 70: ...e el suministro de voltaje de este sistema sea el correcto Conecte el cableado de la fuente de alimentaci n y el cableado interno usando un soporte para cables conductores sobre el lado de la unidad d...

Page 71: ...ios L1 a L1 L2 a L2 Unidad exterior Unidad interior A Outdoor unit Power Wiring 3 2 1 N L C 2 1 N L Indoor unit A Control Wiring 4 Wire 14 AWG Stranded 4 3 To Service Disconnect 1 2 3 White Black Red...

Page 72: ...L C 3 2 1 N L C Strain Relief Brackets E 3 2 1 N L C Informaci n de Carga de Refrigerante y Longitud de la Tuber a N mero de Modelo Carga de F brica Longitud Total de la Tuber a con carga de f brica R...

Page 73: ...ice un control de p rdidas en los accesorios abocinados usando burbujas de jab n u otro dispositivo de detenci n Si una p rdida es detectada realice las reparaciones de los accesorios y vuelva a hacer...

Page 74: ...as unidades exteriores Si no encuentra el adhesivo escriba las cantidades en la unidad exterior con un marcador indeleble sobre el puerto de carga Retire la tapa de la v lvula de la tuber a de l quido...

Page 75: ...e uso Recomendamos que el usuario lea las Instrucciones de uso detenidamente Prueba del Sistema Por favor expl quele al cliente c mo utilizar el sistema usando el Manual del Propietario el cual se enc...

Page 76: ...ctrica incorrecta Da o resultante de inundaciones incendios viento iluminaci n accidentes o condiciones similares Un producto que no fue instalado o su servicio t cnico no fue realizado por un t cnico...

Page 77: ...garantizada en lugar de todas las dem s soluciones Esta garant a no cubre da os incidentales o consecuentes Algunos estados y provincias no permiten la exclusi n de da os incidentales o consecuentes...

Page 78: ...78 31 5000560 Rev 5 Notas...

Page 79: ...31 5000560 Rev 5 79 Notas...

Page 80: ...Not Return This Product To The Store If you have a problem with this product please call 1 844 487 9443 for the name and telephone number of the nearest authorized service center DATED PROOF OF PURCH...

Reviews: