2
7. (Optional) Connect the open collector output to an external
signalling device or panel to have an independent fault
supervisory.
8. Connect the flat cable
between the control panel (connector
J20) and the ATS7300 (connector CON1or CON2).
9. Connect the antenna to the GSM module
10. Insert the SIM module into the SIM socket (CON5).
11. Apply power to the control panel and the GSM module.
12. Check the field strength (FS LED). When required, move the
antenna in order to get the best signal.
D
ESCRIPTION OF THE
ATS7300 (R
EF
.
TO FIGURE
)
No. Description
Function
1
GSM module
Sony Ericsson GM47 GSM
module. Includes antenna
connection (MMCX
connector)
CON5
SIM socket. Holds GSM SIM
card.
CON3
Feature connector. Only for
factory use.
F1, Automatic fuse
Used to protect the GSM
module against
shorts/reversed connections
on the battery input.
CON 1, BATT IN +
B connection
CON 1, BATT IN -
Battery – connection
CON 1 NC
Not connected
CON 1 OC
Open collector (see fault
indicator output description
below).
CON 2/CON 4
(System connector)
Communicates between the
ATS7300 and the main
panel.
LEDs LED’s
indicating
status.
F
AULT INDICATOR OUTPUT
(
REF
.
TO FIG
.
CON
1
SYMBOL
)
OC
Open collector state:
The open collector is controlled by the state of the battery fuse
(F1), presence of the battery and the presence of the GSM
network.
The open collector is low (active) if the battery is present, the
battery fuse is ok and the GSM network is detected.
This low state can sink current and is compared to + 12V. In case
of any error condition the output is high.
IMPORTANT:
After power up the open collector is always high for some time, this
is because the ATS7300 has not yet detected the GSM network.
The open collector has the same functionality as the line fault,
which is reported to the panel, except that the open collector is not
delayed.
Line fault reported to the panel is delayed with 1 minute.
LED'
S
MI
The MI LED (green) displays the status of the communication
interface to the panel.
Table 1. MI LED status
LED
Description
Duty
cycle
Rate
(+/- 10%)
100%
-
Power ON (in case none of the
cases below are valid)
0%
-
No Power or Power Failure
25%
1 sec
Initialisation OK, waiting for
communication
50%
1 sec
Everything OK, communication
running
75%
500 ms
Hardware failure
50%
250 ms
Failure in communication, waiting for
re-initialisation.
CS
The CS LED (Red) indicates status of the audio information
transmitted to the central station
Table 2. CS LED status
LED
Description
Duty
cycle
Rate
(+/- 10%)
100% - Connected
0% -
Off
line
10% 1
sec Connecting
50%
1 sec
Ringing present
FS
The FS LED (green) indicates the field strength or signal strength
found by the GSM module. The number of flashes indicates the
level. Between each set of flashes a pause of 1 second is inserted.
Table 3. FS LED status
LED
Description
Off
No field strength (no network
detected)
Blink (1 – 5)
Field strength indication from poor
(1) to excellent (5)
On
Power on, not connected to a
network
GSM
The GSM LED (green) indicates the status of the GSM module.
Table 4. GSM LED status
LED
Description
Off
No power or the module is in the off
state
Blink
Power on, connected to a network
On
Power on, not connected to a
network
The GSM module will signal a line fault to the control panel if the
GSM module does not detect the home network for 1 minute.
.Technical Specifications
Power supply
Via ribbon cable from control panel
Via CON1, BAT from backup battery
10 – 15 V
10 – 15 V
Current Consumption (at 13.8 V
± 5%)
MI Bus
GSM Offline
GSM Online
GSM Online Peak
20 mA
15 mA
110 mA
2A
Open collector output current (CON13, OC)
15 mA max. at 13.8 V
.