Troubleshooting Tips. 

Normal Operating Sounds

„

You may hear a pinging noise caused by 
water being picked up and thrown against the 
condenser on rainy days or when the humidity  
is high. This design feature helps remove 
moisture and improve efficiency.

„

You may hear the thermostat click when the 
compressor cycles on and off.

„

Water will collect in the base pan during 
high humidity or on rainy days. The water 
may overflow and drip from the outdoor side 
of the unit.

„

The fan may run even when the compressor  
does not.

Problem 

Possible Causes 

What To Do

Air conditioner

 

The air conditioner 

• 

Make sure the air conditioner plug is pushed 

does not start

 

is unplugged. 

  completely into the outlet.

 

The fuse is blown/circuit 

 Check the house fuse/circuit breaker box and replace 

 

breaker is tripped. 

  the fuse or reset the breaker.

 Power 

failure. 

The unit will automatically restart in the settings last  

 

 

  used after the power is restored.

 

 

There is a protective time delay (approximately   

 

 

 

  3 minutes) to prevent tripping of the compressor  

 

 

 

  overload. For this reason, the unit may not start  

 

 

 

  normal cooling for 3 minutes after it is turned    

 

  

 

back 

on.

 The 

current 

interrupter 

Press the 

RESET

 button located on the power cord plug.

 

device is tripped. 

If the 

RESET

 button will not stay engaged, discontinue  

 

 

  use of the air conditioner and contact a qualified  

  

 

service 

technician.

Air conditioner does

 

Airflow is restricted. 

 Make sure there are no curtains, blinds or furniture 

not cool as it should

 

 

  blocking the front of the air conditioner.

 

The temp control may 

 In the 

Cool

 mode, press the 

Decrease 

d

pad.

 

not be set correctly.

 

The air filter is dirty. 

 Clean the filter at least every 30 days. 

  

 

See 

the 

Care and Cleaning

 section.

 

The room may have been hot. 

 When the air conditioner is first turned on, you need  

 

 

  to allow time for the room to cool down.

 

Cold air is escaping. 

 Check for open furnace registers and cold air returns.

 

Cooling coils have iced up. 

See “

Air conditioner freezing up

” below.

Air conditioner

 

Ice blocks the air flow 

• Set the controls at 

High Fan

 or 

High Cool

 and set the  

freezing up

 

and stops the air conditioner 

  thermostat to a higher temperature.

 

from cooling the room.

The remote control  

 

The batteries are inserted 

 Check the position of the batteries. They should be  

is not working

 

incorrectly. 

  inserted in the opposite (+) and (–) direction.

 

The batteries may be dead. 

• 

Replace the batteries.

Water drips outside

 

Hot, humid weather.  

 This is normal.

Water drips indoors

 

The air conditioner is not 

 For proper water disposal, make sure the air conditioner 

 

tilted to the outside. 

  slants slightly from the case front to the rear.

Water collects in 

 

Moisture removed from air  

 This is normal for a short period in areas with little 

base pan

 

and drains into base pan. 

  humidity; normal for a longer period in very humid areas.

Summary of Contents for AEL14AV

Page 1: ...Cover Warranty 16 49 7722 1 11 15 GE Owner s Manual and Installation Instructions Write the model and serial numbers here Model _________________________ Serial __________________________ Find these...

Page 2: ...safety do not store or use combustible materials gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance All air conditioners contain refrigerants which under fede...

Page 3: ...ified electrician to make sure the outlet is properly grounded Where a 2 prong wall outlet is encountered it is your personal responsibility and obligation to have it replaced with a properly grounded...

Page 4: ...onditioner is off it can be set to automatically come on in 1 to 24 hours at its previous mode and fan settings HOD 2 When the air conditioner is on it can be set to automatically turn off in 1 to 24...

Page 5: ...the speed needed to provide optimum comfort settings with the set temperature If the room needs more cooling the fan speed will automatically increase If the room needs less cooling the fan speed will...

Page 6: ...iding it back into position NOTES Use 2 AAA 1 5 volt alkaline batteries Do not use rechargeable batteries Remove the batteries from the remote control if the system is not going to be used for a long...

Page 7: ...s your responsibility to have it replaced with a properly grounded 3 prong wall outlet Some models require 230 208 volt AC protected with a time delay fuse or circuit breaker These models should be in...

Page 8: ...pearance may vary Type E bolt with nut 4 Type A screws 10 Type B screws 2 Type C screws 4 Type F bolt with nut 2 V supports 2 Top mounting rail Air conditioner Top mounting rail seal strip Foam top wi...

Page 9: ...the dimensions in the table and illustration for your model 1 18 1 2 With accordion panels PREPARE THE AIR CONDITIONER Pull down the front panel and remove the filter Remove the front panel by liftin...

Page 10: ...rdion panel and side retainer assembly relative to the case from a top view of the unit Remove the backing from the accordion seal two short strips Stick one sealing strip respectively on the left sid...

Page 11: ...crews Drill pilot holes if necessary Assemble the V support and V support bracket with Type F nut and bolt 5 PREPARE THE WINDOW AND INSTALL THE CASE continues Position the V supports on the case botto...

Page 12: ...NDITIONER IN THE CASE continues Replace the 1 screw removed earlier in the side of the case IMPORTANT THE GROUND SCREW MUST BE REINSTALLED TO ENSURE PROPER GROUND Reinstall the control to the panel ho...

Page 13: ...in the window measure the length of the accordion for both sides Cut the foam insulation to the measured length of the left and right side accordion NOTE Be sure to measure each accordion because the...

Page 14: ...tain that a wall receptacle is available close to the hole location or make arrangements to install a receptacle Place the case in the wall opening and place wood support strips between the case botto...

Page 15: ...r conditioner and contact a qualified service technician Air conditioner does Airflow is restricted Make sure there are no curtains blinds or furniture not cool as it should blocking the front of the...

Page 16: ...le for service by an individual technician Replacement of house fuses or resetting of circuit breakers Failure due to corrosion on models not corrosion protected Damage to the product caused by improp...

Page 17: ...rucciones de instalaci n 23 30 Solucionar problemas 31 Sonidos de operaci n normales 31 Servicio al consumidor Garant a 34 Servicio al consumidor 35 Escriba los n meros de modelo y serie aqu de Modelo...

Page 18: ...idos inflamables en la proximidad de ste o alg n otro electrodom stico Todos los acondicionadores de aire contiene refrigerantes los que por Ley Federal deben ser removidos antes de desecharlos Si ust...

Page 19: ...tomacorriente y el circuito para cerciorarse de que el tomacorriente est conectado a tierra de la manera apropiada Donde exista un tomacorriente de dos tomas es su responsabilidad y obligaci n person...

Page 20: ...de 1 24 heures de l appareil ou Delay pad Touches de D lai de la t l commande Chaque fois que vous effleurez les touches Increase Decrease sur l appareil ou les touches Increase Decrease de la t l com...

Page 21: ...vitesse n cessaire l obtention des r glages apportant un niveau de confort optimal la temp rature programm e Si la pi ce demande un refroidissement suppl mentaire la vitesse du ventilateur augmente a...

Page 22: ...Coloque la cubierta otra vez desliz ndola en su lugar NOTAS Use 2 pilas alcalinas AAA de 1 5 voltios No use pilas recargables Retire las pilas del control remoto si no va a usar el sistema por un per...

Page 23: ...acondicionador de aire Los cables caseros de aluminio podr an presentar problemas especiales Consulte a un t cnico electricista calificado ANTES DE INICIAR Lea estas instrucciones completa y cuidados...

Page 24: ...n derecho Panel de acorde n izquierdo PARTES INCLUIDAS Apariencia puede variar Tipo A tornillos 10 Tipo C tornillos 4 Perno tipo F con 2 tuercas 2 Soportes en V 2 Perno tipo E con 2 tuercas 4 Riel lat...

Page 25: ...or del marco de la ventana de tormentas o del marco vinilo P guelo firmemente con clavos o con tornillos proporcionados por el instalador 1 2s m s alto que el marco de ventana de tormentas Marco de ve...

Page 26: ...bandas cortas Adhiera una banda de sellado respectivamente del lado izquierdo y del lado derecho de los paneles de acorde n como se muestra Deslice los paneles de acorde n de izquierda a derecha sobr...

Page 27: ...re orificios piloto si fuera necesario 5 Instrucciones de instalaci n A PREPARE LA VENTANA E INSTALE LA CAJA Enlace el soporte en V y la ficha del soporte en V con una tuerca y un tornillo Tipo F Colo...

Page 28: ...Deslice el acondicionador de aire dentro de la carcasa de la bandeja inferior No haga presi n sobre los controles carcasa de poliestireno de la descarga de aire o las serpentinas de aletas Verifique...

Page 29: ...e de ventana mida la longitud del acorde n de ambos lados Corte el aislante de gomaespuma en la longitud medida del lado izquierdo y derecho del acorde n NOTA Aseg rese de medir cada acorde n ya que l...

Page 30: ...un tomacorriente cerca de la ubicaci n del orificio o efect e arreglos para instalar un tomacorriente Coloque la carcasa en la abertura de la pared y coloque gu as de soporte de madera entre la parte...

Page 31: ...caliente necesita darle tiempo para que enfri la habitaci n El aire fr o se est escapando Cerci rese de que los registros de la calefacci n no est n abiertos y se encuentran retornando el aire fr o La...

Page 32: ...32 Notas...

Page 33: ...33 Notas GEAppliances com...

Page 34: ...cubierto Esta garant a se extiende al comprador original y cualquier comprador posterior de productos comprados para uso residencial dentro de Estados Unidos Si el producto est situado en un rea que n...

Page 35: ...con dificultades auditivas favor de llamar al 800 TDD GEAC 800 833 4322 Piezas y accesorios GEAppliances com Aquellos individuos con la calificaci n necesaria para reparar sus propios electrodom stico...

Page 36: ...es check out our Website today For the hearing impaired please call 800 TDD GEAC 800 833 4322 Parts and Accessories GEApplianceParts com Individuals qualified to service their own appliances can have...

Reviews: