23
Advent Commercial Fire System
Partitions/Arming
Audible Verification at Close Report
xx098
(Partitions-Reporting)
(Default = off) When on, the panel will locally verify that a
closing report has been sent to the central station with an audible
signal.
Note
In order for this setting to work,
Exterior Arming Verifica-
tion
setting (xx097) must be set to “on.”
To turn Audible Verification at Close Report On/
Off:
Once the item number has been entered, enter
1
to turn the
setting on or
0
to turn it off. Press
ƒ
to apply the new setting.
Enable Arming Level 2
Enable Arming Level 3
Enable Arming Level 4
Enable Arming Level 5
2: xx025, 3: xx026,
4: xx027, 5: xx028
(Partitions-Arming)
(Default = on) If on, the selected arming level will be enabled
(level 1 is always enabled) in the selected partition/area. Users
will then have access to this arming level. An arming level is the
degree of security protection set at the panel.
To Enable Arming Level:
Once the item number has been entered, enter
1
to turn the
setting on (level enabled) or
0
to turn it off. Press
ƒ
to apply the
new setting.
Default Keyfob Schedule Arming Level
xx118
(Partitions-Arming)
(Default = 3) This setting allows you to select the arming level
(2–5) the panel arms to when armed by a keyfob or schedule (auto
arming).
Specifying Default Keyfob Schedule Arming
Level:
Once the item number has been entered, enter the keyfob/
scheduled arming level (2–5). Press
ƒ
to apply the new setting.
Default Keyswitch Arming Level
xx120
(Partitions-Arming)
(Default = 3) This setting allows you to select the arming level
(2–5) the panel arms to when armed by a keyswitch.
Specifying Default Keyswitch Arming Level:
Once the item number has been entered, enter the keyswitch
arming level (2–5). Press
ƒ
to apply the new setting.
Activity Fault Threshold 1
Activity Fault Threshold 2
Activity Fault Threshold 3
1: xx018, 2: xx019, 3: xx020
(Partitions-Arming)
(Defaults = Threshold 1-10, Threshold 2-30, Threshold 3-50)
This setting allows you to specify the number of disarms without
any activity before zone activity trouble is generated.
Specifying Activity Fault Thresholds:
Once the item number has been entered, enter the number of
disarms before zone activity trouble is generated (2–255). Press
ƒ
to apply the new setting.
Enable Scheduled Arming
xx094)
(Partitions-Arming)
(Default = on) This setting allows you to select whether or not to
allow the system to arm/disarm according to a schedule.
To turn Enable Scheduled Arming On/Off:
Once the item number has been entered, enter
1
to enable
scheduled arming or
0
to turn it off. Press
ƒ
to apply the new
setting.
Time Between Arming Notification and Arming
xx007
(Partitions-Arming)
(Default = 10 minutes) This is the amount of time between the
start of arming notification and when the partition/area is armed
by a schedule (auto arming). This notifies users that a scheduled
arm is about to occur and allows time for users to vacate the
premises.
To set the Time Between Arming Notification and
Arming:
Once the item number has been entered, enter the number of
minutes (05–30) that will pass between notification and arming.
Press
ƒ
to apply the new setting.
Extension Time
xx008
(Partitions-Arming)
(Default = 30 minutes) This is the amount of time by which a
scheduled arming period will be suspended during the arming
notification period. For example, let’s say the extension is entered
when there is four minutes left in the delay. Once the extension
has expired the system will start counting down the remaining
four minutes.
To set the Extension Time:
Once the item number has been entered, enter the number of
minutes (15–120) users will be able to extend the notification
period and press
ƒ
.