46
Advent Commercial Fire System
Battery Test Interval
17073
(System)
(Default = 4 hours) Select how (4 or 24 hours) often the panel
performs a self-test on its backup battery to ensure that it is
adequately charged.
Note
This option is not available in UL-864 version.
To set Battery Test Interval:
Once the item number has been entered, enter
1
for 4 hours, or
0
for 24 hours. Press
ƒ
to apply the new setting.
High Rise Installation
17074
(System)
(Default = off) Set to “on” when the panel is installed in a high
rise building. This will enable zones to have “floor” attributes.
When on, any zone not programmed with a floor attribute will
not
turn on all outputs with a “fire on floor” condition programmed.
When off, any zone not programmed with a floor attribute
will
turn on all outputs with a “fire on floor” condition programmed.
To turn High Rise Installation On/Off:
Once the item number has been entered, enter
1
for on, or
0
for
off. Press
ƒ
to apply the new setting.
Commercial or Residential Installation
17076
(System)
(Default = Commercial: 1, Residential: 0) Select either a
commercial or residential installation. If commercial, LTIME is
set to every 4 hours instead of 24 hours.
Note
This option is not available in UL-864 version.
To set Commercial or Residential Installation:
Once the item number has been entered, enter
1
for commercial,
or
0
for residential. Press
ƒ
to apply the new setting.
Report System Events
17096
(System)
(Default = on) This setting determines if system events are
reported to the central station.
To turn Report System Events On/Off:
Once the item number has been entered, enter
1
for on, or
0
for
off. Press
ƒ
to apply the new setting.
System Report Time (STIME)
17004
(System)
(Default = random) Enter the time of day (in 24-hour format)
when an automatic phone test to the central station is performed.
To set the System Report Time:
Enter the desired item number. Enter the 4-digit system report
time (00:00-23:59) and press
ƒ
.
Enable RF Jam Detect
17072
(System)
(Default = on) Select whether or not the panel will detect an RF
jam.
Note
This setting must be set to “on” in commercial fire and
burglary systems.
To turn Enable RF Jam Detect On/Off:
Once the item number has been entered, enter
1
for on (jam
detection), or
0
for off (no jam detection). Press
ƒ
to apply the
new setting.
Enable Long Range Radio
17075
(System)
(Default = off) Select whether or not you want to enable long
range radio (if connected to panel).
Note
This option can only be programmed through Advent
Downloader.
Percent Full History Buffer Reports
17043
(System)
(Default = 80 percent) This setting allows you to specify how full
(percent) the history buffer may get before generating trouble.
Another trouble is generated when the history buffer overflows.
To set History Buffer Percent:
Once in program mode enter the item number. Enter the desired
percentage (10–100) and press
ƒ
.
Percent Full Report Buffer Reports
17044
(System)
(Default = 80 percent) This setting allows you to specify how full
(percent) the report buffer gets before forcing early reporting of
delayed low priority events. No trouble is generated until the
report buffer overflows.
To set Report Buffer Percent:
1.
Once in program mode enter the item number.
2.
Enter the desired percentage (10–100) and press
ƒ
.
Summary of Contents for Advent
Page 56: ...54 Advent Commercial Fire System ...
Page 88: ...86 Advent Commercial Fire System ...
Page 110: ...108 Advent Commercial Fire System ...