61
Advent Commercial Fire System
Sensors/Zones (
see also
wireless smoke sensors)
Zone # Tamper
is indicated.
Replace the zone sensor cover if it is off. Trip and reset the sensor.
Zone # Supervisory
Failure
is indicated.
The zone/sensor is not communicating with the panel.
Zone # Trouble
Low Battery
is indicated.
Replace the indicated zone sensor battery.
Tamper Indications
1. Check that wireless sensor covers are in place.
2. Check that surface tampered wireless PIRs, Smoke, and Sound sensors are securely mounted.
3. Check that hardwired sensor loop end of line (EOL) resistors are installed.
4. Check for hardwire sensor loop shorts or opens.
5. If panel door is tampered, check that the panel cover is closed.
6. If phone jack is tampered, check that phone line cords are plugged in.
7. Check that Commercial RF Transceiver antennas are not bent, cut, or missing and that
antenna and ground connections are tight.
8. Check for multiple incorrect access code entries from touchpad or phone.
Trouble Beeps (see also
Panel
)
Check system status for an indication of the problem. Troubles must be individually
acknowledged to silence the beeps.
Wireless Sensors (also see RF Transceiver Module)
The panel does not respond to sensor activity. There are no alarm, chime, or sensor test sounds.
1. Check that the wireless sensor battery is installed.
2. Check the sensor battery for low voltage. Replace batteries if necessary.
3. Use an RF Sniffer tool (60-401) to verify that the sensor is transmitting.
4. Check that the sensor is programmed (added/learned) into panel memory. Add the sensor if
necessary.
5. Verify that both RF Transceiver module antennas are installed and that the connections are
tight.
The panel responds intermittently to wireless sensor signals.
1. Rotate the sensor position from 90 to 180 degrees.
2. Mount the sensor in a different location.
3. Verify that both RF Transceiver Module antennas are installed and connections tight.
Wireless Smoke Sensor (see also RF Transceiver Module)
Beeps once every minute.
Sensor batteries are low. Replace all of the smoke sensor batteries.
Zone # Trouble
is indicated.
Replace the zone/sensor cover, if it is off. Trip the sensor.
Check for blocked dirty sensor screen and clean if necessary.
Zone # Supervisory Failure
is indicated.
The sensor is not communicating with the panel.
Zone # Trouble Low Battery
is indicated.
Replace the indicated sensor battery.
Wireless Touchpads
The panel does not respond to wireless touchpad commands.
1. Operate touchpads from different locations to locate areas of intermittent operation.
2. Check and/or replace wireless touchpad battery.
3. Program or reprogram the touchpad(s) into the panel.
Feature
Problem
Solution