CHAPTER 6: DNP POINT LISTS
ANALOG INPUT / ANALOG INPUT CHANGE
750/760 FEEDER MANAGEMENT RELAY – COMMUNICATIONS GUIDE
6 - 5
Analog Input / Analog Input Change
In the following table, the entry in the “Format” column indicates that the format of the
associated data point can be determined by looking up the entry in the Memory Map Data
Formats table. For example, an “F1” format is described in that table as a (16-bit) unsigned
value without any decimal places. Therefore, the value read should be interpreted in this
manner.
The point list for Analog Input (Object 30) and Analog Input Change (Object 32) is shown
below. Refer to the notes following the table for additional details.
Table 3: Analog Inputs DNP Points (Sheet 1 of 8)
Index when Point
Mapping is:
Format
Description
Event
Class
Assigned
Disable
d
Enabled
n/a
0
-
User Map Value 1
n/a
1
-
User Map Value 2
↓
↓
↓
↓
n/a
118
-
User Map Value 119
n/a
119
-
User Map Value 120
0
120
F49
Phase Time Overcurrent 1
Class 1
1
121
F49
Phase Instantaneous Overcurrent 1
Class 1
2
122
F49
Phase Instantaneous Overcurrent 2
Class 1
3
123
F49
Ground Time Overcurrent
Class 1
4
124
F49
Ground Instantaneous Overcurrent
Class 1
5
125
F49
Neutral Time Overcurrent 1
Class 1
6
126
F49
Neutral Time Overcurrent 2
Class 1
7
127
F49
Neutral Instantaneous Overcurrent 1
Class 1
8
128
F49
Neutral Instantaneous Overcurrent 2
Class 1
9
129
F49
Phase Directional Is Reverse
Class 1
10
130
F49
Neutral Directional Is Reverse
Class 1
11
131
F49
Manual Close Blocking
Class 1
12
132
F49
Cold Load Pickup Blocking
Class 1
13
133
F49
Bus Undervoltage 1
Class 1
14
134
F49
Bus Undervoltage 2
Class 1
15
135
F49
Line Undervoltage 1
Class 1