750/760 FEEDER MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP
CHAPTER 4: MODBUS MEMORY MAP
PHASE INSTANTANEOUS OVERCURRENT 2 (read/write setpoints)
1510
2
Phase Instantaneous Overcurrent 2 Function
---
---
F37
Disabled
1511
2
Phase Instantaneous Overcurrent 2 Relays
---
---
F57
None
1512
2
Phase Instantaneous Overcurrent 2 Pickup
0.05 to 20.00
x CT
F3
1.00 x CT
1513
2
Phase Instantaneous Overcurrent 2 Delay
0.00 to 600.00
s
F3
0.00 s
1514
Phases Required for Operation
---
---
F41
Any One
1515
1
Phase Instantaneous Overcurrent 2 Direction
---
---
F84
Disabled
PHASE DIRECTIONAL OVERCURRENT (read/write setpoints)
1520
Phase Directional Function
---
---
F38
Disabled
1521
Phase Directional Maximum Torque Angle
0 to 359
° Lead
F1
30° Lead
1522
1
Minimum Polarizing Voltage
0.00 to 1.25
x VT
F3
0.05 x VT
1523
Phase Directional Relays
---
---
F57
None
1524
4
Block OC When Voltage Memory Expires
---
---
F30
Disabled
PHASE TIME OVERCURRENT 2 (read/write setpoints)
1530
1
Phase Time Overcurrent 2 Function
---
---
F37
Disabled
1531
1
Phase Time Overcurrent 2 Relays
---
---
F57
None
1532
1
Phase Time Overcurrent 2 Curve
---
---
F36
Ext. Inverse
1533
1
Phase Time Overcurrent 2 Voltage Restraint
---
---
F30
Disabled
1534
1
Phase Time Overcurrent 2 Pickup
0.05 to 20.00
x CT
F3
1.00 x CT
1535
1
Phase Time Overcurrent 2 Multiplier
0.00 to 100.00
---
F3
1.00
1536
1
Phase Time Overcurrent 2 Reset Time
---
---
F68
Instantaneous
1537
1
Phase Time Overcurrent 2 Direction
---
---
F84
Disabled
GROUND TIME OVERCURRENT (read/write setpoints)
1600
Ground Time Overcurrent Function
---
---
F37
Disabled
1601
Ground Time Overcurrent Relays
---
---
F57
None
1602
Ground Time Overcurrent Curve
---
---
F36
Ext. Inverse
1603
1
Ground Time Overcurrent Pickup
0.05 to 20.00
x CT
F3
1.00 x CT
1604
1
Ground Time Overcurrent Multiplier
0.00 to 100.00
---
F3
1.00
1605
1
Ground Time Overcurrent Reset Time
---
---
F68
Instantaneous
1606
6
Ground Time Overcurrent Direction
---
---
F84
Disabled
GROUND INSTANTANEOUS OVERCURRENT (read/write setpoints)
1608
2
Ground Instantaneous Overcurrent Function
---
---
F37
Disabled
1609
2
Ground Instantaneous Overcurrent Relays
---
---
F57
None
160A
2
Ground Instantaneous Overcurrent Pickup
0.05 to 20.00
x CT
F3
1.00 x CT
160B
2
Ground Instantaneous Overcurrent Delay
0.00 to 600.00
s
F3
0.00 s
160C
6
Ground Instantaneous Overcurrent Direction
---
---
F84
Disabled
GROUND DIRECTIONAL OVERCURRENT (read/write setpoints)
160E
6
Ground Directional Function
---
---
F38
Disabled
160F
6
Ground Directional Maximum Torque Angle
0 to 359
° Lead
F1
315°
1610
6
Ground Directional Minimum Polarizing Voltage
0.00 to 1.25
x VT
F3
0.05 x VT
1611
6
Ground Directional Polarizing
---
---
F50
Voltage
1612
6
Ground Directional Relays
---
---
F57
None
NEUTRAL TIME OVERCURRENT 1 (read/write setpoints)
1630
Neutral Time Overcurrent 1 Function
---
---
F37
Disabled
1631
Neutral Time Overcurrent 1 Relays
---
---
F57
None
1632
Neutral Time Overcurrent 1 Curve
---
---
F36
Ext. Inverse
1633
1
Neutral Time Overcurrent 1 Pickup
0.05 to 20.00
x CT
F3
1.00 x CT
Table 3: Modbus Memory Map (Sheet 25 of 40)