CHAPTER 5: DNP COMMUNICATIONS
DNP IMPLEMENTATION
750/760 FEEDER MANAGEMENT RELAY – COMMUNICATIONS GUIDE
5 - 3
Note 1: The data link layer confirmation mode, confirmation time-out, and number of
retries are all configurable. Refer to the
DNP Configuration
section in Chapter 5 of
the instruction manual for more details.
DNP Implementation
The table below gives a list of all objects recognized and returned by the relay. Additional
information is provided on the following pages including a list of the default variations
returned for each object and lists of defined point numbers for each object.
Implementation Table Notes:
1.
For this object, the quantity specified in the request must be exactly 1 as there is only
one instance of this object defined in the relay.
2.
All static input data known to the relay is returned in response to a request for Class 0.
This includes all objects of type 1 (Binary Input), type 10 (Binary Output) and type 30
(Analog Input).
3.
The point tables for Binary Input and Analog Input objects contain a field which
defines to which event class the corresponding static data has been assigned.
4.
For this object, the qualifier code must specify an index of 7 only.
Default Counter Object/Variation:
No Counters Reported
Configurable
Default Object / Default Variation
Point-by-point list attached
Counters Roll Over at:
No Counters Reported
Configurable
16 Bits
32 Bits
Other Value
Point-by-point list attached
Sends Multi-Fragment Responses:
Yes
No
DNP 3.0: DEVICE PROFILE DOCUMENT (Continued)
Ë
Ë
Ë
Ë
Ë
Ë
Ë
Ë
Ë
Ë
Ë
Ë
Table 1: DNP Implementation Table
Object
Request
Response
Obj
Var
Description
Func Codes
Qual Codes
(Hex)
Func Codes
Qual Codes
(Hex)
1
0
Binary Input - All Variations
1
06
1
1
Binary Input
1
00, 01, 06
129
00, 01
1
2
Binary Input With Status (Note 6)
1
00, 01, 06
129
00, 01
2
0
Binary Input Change - All Variations
1
06, 07, 08
2
1
Binary Input Change Without Time
1
06, 07, 08
129
17, 28
2
2
Binary Input Change With Time
1
06, 07, 08
129
17, 28
10
0
Binary Output - All Variations
1
06
10
2
Binary Output Status
1
00, 01, 06
129
00, 01
12
1
Control Relay Output Block
3, 4, 5, 6
17, 28
129
17, 28
30
0
Analog Input - All Variations
1
06
30
1
32-Bit Analog Input With Flag
1
00, 01, 06
129
00, 01
30
2
16-Bit Analog Input With Flag
1
00, 01, 06
129
00, 01
30
3
32-Bit Analog Input Without Flag
1
00, 01, 06
129
00, 01
30
4
16-Bit Analog Input Without Flag
1
00, 01, 06
129
00, 01
1, 2, 3, 4, 5, 6: see the IMPLEMENATION TABLE NOTES above.