4 - 40
750/760 FEEDER MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP
CHAPTER 4: MODBUS MEMORY MAP
1B74
Underfrequency Restoration Delay
0 to 10000
s
F1
10 s
1B75
Underfrequency Restoration Incomplete Sequence Time
1 to 10,000
min.
F1
100 min.
TRANSFER (read/write setpoints)
1B80
Transfer Function
---
---
F56
Disabled
1B81
Transfer Delay This Source
0.0 to 10.0
s
F2
1.0 s
1B82
Transfer Delay Other Source
0.0 to 10.0
s
F2
3.0 s
1B83
Block Trip On Double Loss
---
---
F30
Disabled
1B84
Transfer Delay Select to Trip
0.0 to 10.0
s
F2
0.0 s
1B85
Transfer Ready Operate Relay 3
---
---
F30
Disabled
1B86
Bus Transfer Logic Scheme
0 to 1
---
F94
Scheme 1
AUTORECLOSE SETUP (read/write setpoints, 760 only)
1BA0
Autoreclose Function
---
---
F30
Disabled
1BA1
Number of Reclosure Shots
1 to 4
1
F1
1
1BA2
Autoreclose Reset Time
1 to 1000
s
F1
60 s
1BA3
Autoreclose Block Time Upon Manual Close
0 to 200
s
F1
10 s
1BA4
Incomplete Sequence Time
1 to 1000
s
F1
30 s
1BA5
Reclosure Enabled Relays
---
---
F57
None
1BA6
Reclose In Progress Relays
---
---
F57
None
1BA7
Reclosure Lockout Relays
---
---
F57
None
1BA8
8
Autoreclose External Close Logic
---
---
F30
Disabled
AUTORECLOSE RATE SUPERVISION (read/write setpoints, 760 only)
1BAA
8
Rate Supervision Function
---
---
F38
Disabled
1BAB
8
Max Autoreclose Rate
1 to 50
/hr.
F1
25
1BAC
8
Rate Supervision Relays
---
---
F57
None
CURRENT SUPERVISION (read/write setpoints, 760 only)
1BB0
Current Supervision Function
---
---
F30
Disabled
1BB1
2
3 Shots For Current Above
0.00 to 20.00
x CT
F3
17.00 x CT
1BB2
2
2 Shots For Current Above
0.00 to 20.00
x CT
F3
18.00 x CT
1BB3
2
1 Shot For Current Above
0.00 to 20.00
x CT
F3
19.00 x CT
1BB4
Current Supervision To Lockout
---
---
F30
Disabled
1BB5
2
Lockout For Current Above
0.00 to 20.00
x CT
F3
20.00 x CT
ZONE COORDINATION (read/write setpoints, 760 only)
1BB8
1
Zone Coordination Function
---
---
F30
Disabled
1BB9
1
Phase Current Increase
0.05 to 20.00
x CT
F3
1.00 x CT
1BBA
1
Neutral Current Increase
0.05 to 20.00
x CT
F3
1.00 x CT
1BBB
1
Maximum fault Clearing Time
1 to 1000
s
F1
10 s
RECLOSURE SHOT 1 (read/write setpoints, 760 only)
1BC0
2
Deadtime Before Reclosure 1
0.00 to 300.00
s
F3
0.50 s
1BC1
1
Select Setpoint Group
---
---
F80
Active Group
1BC2
2
Overcurrent Blocking Flags
---
---
F59
None blocked
1BC3
1
Phase Time Overcurrent 1 Raised Pickup
0 to 100
%
F1
0%
1BC4
1
Neutral Time Overcurrent 1 Raised Pickup
0 to 100
%
F1
0%
1BC5
1
Ground Time Overcurrent Raised Pickup
0 to 100
%
F1
0%
1BC6
1
Negative Sequence Time Overcurrent Raised Pickup
0 to 100
%
F1
0%
1BC7
3
Sensitive Ground Time Overcurrent Raised Pickup
0 to 100
%
F1
0%
RECLOSURE SHOT 2 (read/write setpoints, 760 only)
1BD0
2
Deadtime Before Reclosure 2
0.00 to 300.00
s
F3
3.00 s
1BD1
1
Select Setpoint Group
---
---
F80
Active Group
1BD2
2
Overcurrent Blocking Flags
---
---
F59
None blocked
Table 3: Modbus Memory Map (Sheet 35 of 40)
ADDR
DESCRIPTION
RANGE
UNITS
TYPE
DEFAULT
1 2 3 4 5 6 7 8 9 10 11 12 13
For explanation of Table footnotes, see the Memory Map Notes at the end of this table.