background image

47

ge.com

Formula for Calculating Operating Costs Using Above Data:

Normal Yearly Operating Data

(Cooling Hours based on 75°F indoor temperature with air conditioner sized to meet the design conditions.)

 

 

ASHRAE

 

 

Heating 

Estimated

 

 

Degree 

Cooling

 

Location 

Days 

Hours

  ALABAMA

 

  Birmingham 

2,551 

1,90

    Huntsville 

,070 

1,40

    Mobile 

1,560 

1,640

    Montgomery 

2,291 

1,580

  ARIZONA

    Flagstaff 

7,152 

   10

    Phoenix 

1,765 

2,280

    Tucson 

1,800 

1,920

    Yuma 

   974 

2,520

  ARKANSAS

    Fort Smith 

,292 

1,410

    Little Rock 

,219 

1,0

  CALIFORNIA

    Bakersfield 

2,122 

1,50

    Fresno 

2,611 

1,210

    Los Angeles 

2,061 

   10

    Sacramento 

2,502 

1,00

    San Diego 

1,458 

   90

    San Francisco 

,015 

  110

  COLORADO

    Colorado Springs 

6,42 

   520

    Denver 

6,28 

   550

    Grand Junction 

5,641 

   910

  CONNECTICUT

    Hartford 

6,25 

   480

  DISTRICT of COLUMBIA

    Washington 

4,224 

1,010

  DELAWARE

    Wilmington 

4,90 

   770

  FLORIDA

    Jacksonville 

1,29 

1,690

    Miami 

   214 

2,850

    Orlando 

   766 

1,90

    Tallahassee 

1,485 

1,500

    Tampa 

   68 

2,50

  GEORGIA

    Atlanta 

2,961 

1,10

    Augusta 

2,97 

1,400

    Macon 

2,16 

1,440

    Savannah 

1,819 

1,510

  IDAHO

    Boise 

5,809 

   670

    Lewiston 

5,542 

   600

    Pocatello 

7,0 

   570

  ILLINOIS

    Chicago 

6,155 

   780

    Moline 

6,408 

   760

    Springfield 

5,429 

   890

  INDIANA

    Evansville 

4,45 

1,090

    Fort Wayne 

6,205 

   710

    Indianapolis 

5,699 

   820

    South Bend 

6,49 

   600

  IOWA

    Burlington 

6,114 

   70

    Des Moines 

6,588 

   710

    Sioux City 

6,951 

   770

  KANSAS

    Dodge City 

4,986 

1,020

    Goodland 

6,141 

   800

    Topeka 

5,182 

   880

    Wichita 

4,620 

1,070

 

 

ASHRAE

 

 

Heating 

Estimated

 

 

Degree 

Cooling

 

Location 

Days 

Hours

 

 

 

ASHRAE

 

 

Heating 

Estimated

 

 

Degree 

Cooling

 

Location 

Days 

Hours

   KENTUCKY

    Lexington 

4,68 

   80

    Louisville 

4,660 

1,10

  LOUISIANA

    Alexandria 

  1,921 

1,670

    Baton Rouge 

  1,560 

1,860

    New Orleans 

  1,85 

1,790

    Shreveport 

  2,184 

1,470

  MAINE

    Portland 

  7,511 

   290

  MARYLAND

    Baltimore 

  4,654 

   850

  MASSACHUSETTS

    Boston 

  5,64 

   500

  MICHIGAN

    Detroit 

  6,29 

   590

    Flint 

  7,77 

   440

    Grand Rapids 

  6,894 

   50

  MINNESOTA

    Duluth 

10,000 

   200

    Minneapolis 

  8,82 

   550

  MISSISSIPPI

    Jackson 

  2,29 

1,560

  MISSOURI

    Columbia 

  5,046 

   960

    Kansas City 

  4,711 

1,210

    Springfield 

  4,900 

   970

    St. Louis 

  4,900 

1,080

  MONTANA 

    Billings 

  7,049 

   520

    Glasgow 

  8,996 

   410

    Great Falls 

  7,750 

   420

    Missoula 

  8,125 

   50

  NEBRASKA

    Grand Island 

  6,50 

   770

    Omaha 

  6,612 

   750

  NEVADA

    Ely 

  7,7 

   500

    Las Vegas 

  2,709 

1,980

    Reno 

  6,2 

   520

  NEW JERSEY

    Newark 

  4,589 

   710

  NEW MEXICO

    Albuquerque 

  4,48 

1,040

    Clayton 

  5,158 

   720

    Silver City 

  ,705 

1,260

  NEW YORK

    Albany 

  6,875 

   480

    Binghamton 

  7,286 

   10

    Buffalo 

  7,062 

   450

    New York 

  4,811 

   790

    Rochester 

  6,748 

   470

    Syracuse 

  6,756 

   500

  NORTH CAROLINA

    Asheville 

  4,042 

   690

    Charlotte 

  ,191 

1,20

    Raleigh 

  ,9 

1,070

    Winston-Salem 

  ,595 

   960

  NORTH DAKOTA

    Bismarck 

  8,851 

   510

    Fargo 

  9,226 

   490

    Williston 

  9,24 

   580

  OHIO

    Cincinnati 

  5,265 

   840

    Cleveland 

  6,51 

   610

    Columbus 

  5,660 

   810

    Dayton 

  5,622 

   740

    Toledo 

  6,494 

   590

  OKLAHOMA

    Oklahoma City 

  ,725 

1,200

    Tulsa 

  ,860 

1,410

  OREGON

    Medford 

  5,008 

   620

    Pendleton 

  5,127 

   590

    Portland 

  4,65 

   270

  PENNSYLVANIA

    Harrisburg 

  5,251 

   70

    Philadelphia 

  5,144 

   810

    Pittsburgh 

  5,987 

   590

    Scranton 

  6,254 

   440

    Williamsport 

  5,94 

   600

  RHODE ISLAND

    Providence 

  5,954 

   470

  SOUTH CAROLINA

    Charleston 

  2,0 

1,90

    Columbia 

  2,484 

1,440

    Greenville 

  2,980 

1,120

  SOUTH DAKOTA

    Rapid City 

  7,45 

   580

    Sioux Falls 

  7,89 

   610

  TENNESSEE

    Chattanooga 

  ,254 

1,180

    Knoxville 

  ,494 

1,070

    Memphis 

  ,22 

1,20

    Nashville 

  ,578 

1,220

  TEXAS

    Corpus Christi 

   914 

2,80

    Dallas 

  2,6 

1,900

    El Paso 

  2,700 

1,580

    Houston 

  1,96 

1,850

    Lubbock 

  ,578 

1,10

    San Antonio 

  1,546 

1,920

  UTAH

    Milford 

  6,497 

   910

    Salt Lake City 

  6,052 

   80

  VERMONT

    Burlington 

  8,269 

   10

  VIRGINIA

    Norfolk 

  ,421 

1,010

    Richmond 

  ,865 

1,020

    Roanoke 

  4,150 

   870

  WASHINGTON

    Seattle 

  5,145 

   180

    Spokane 

  6,655 

   40

    Yakima 

  5,941 

   50

  WEST VIRGINIA

    Charleston 

  4,476 

   860

    Huntington 

  4,446 

   820

  WISCONSIN

    Madison 

  7,86 

   50

    Milwaukee 

  7,65 

   450

  WYOMING

    Casper 

  7,410 

   600

    Cheyenne 

  7,81 

   420

    Sheridan 

  7,680 

   50

Heating*

 —  

Heat Loss KW x Heating Degree Days x “C” x Cost Per KWH

 = 

Operating Cost

Outdoor Design Temperature Difference

* The above formula is for electric resistance heating only. Power consumption using the Zoneline Heat Pumps should be adjusted by Seasonal Performance Factor (SPF).

The local power supplier should be consulted for recommended value of “C.” This factor will vary between 17 and 24.

Cooling —   Calculated Heat Gain (BTUH)    x = Unit Cooling Watts  x  Cooling Hours  x  Cost per KWH  =  Operating Cost

Installed unit capacity (BTUH)

1000 Watts/KW

Summary of Contents for 3900 Series

Page 1: ...GE Zoneline packaged terminal air conditioners 2008 contract sales architects and engineers data manual ...

Page 2: ...900 Series Heat Pump with Backup Electric Heat MODEL NUMBER COOLING Btuh EER Reverse Cycle BTUH COP AZ39H07DA 7100 6900 12 7 12 7 6400 6200 3 6 3 6 AZ39H09DA 9400 9150 12 0 12 0 8550 8300 3 6 3 6 AZ39H12DA 11850 11500 11 5 11 5 11000 10700 3 4 3 4 AZ39H15DA 14800 14400 10 0 10 0 13900 13600 3 2 3 2 AZ39H07EA 7100 12 7 6400 3 6 AZ39H09EA 9000 12 0 8550 3 6 AZ39H12EA 11700 11 5 10900 3 4 AZ39H15EA 1...

Page 3: ...3900 5000 4090 22 3 20 3 30 Electric Heat Amps include electric heater and fan motor current draw Units connected through sub base do not require a LCDI or AFCI device since they are not considered to be line cord connected Each 230 208 volt sub base kit consists of sub base with appropriate receptacle for minimum circuit amperage chaseway to route power connector from sub base to chassis wiring t...

Page 4: ...out power consumption This assembly uses R 22 as the refrigerant and is not connected to the regular Zoneline refrigerant circuit As warm humid air is pulled through the pre cool front section of the heat pipe the heat removed from the air is absorbed by the refrigerant causing the refrigerant to change to a gas and flow to the re heat rear section of the heat pipe The air leaving the pre cool sec...

Page 5: ... Cooling Heat Pump Performance Data 45 Latent System Capacity 46 Normal Yearly Operating Data 47 Schematics 48 51 Product Specifications Suggested Bid Form Specifications 52 53 Zoneline Chassis Nomenclature Receptacles Sub bases 54 Specifications 55 Complete Accessory List 56 General Installation Suggestions 57 58 Warranty 58 Alphabetical Index 59 Back Cover 60 Important Notice Equipment used as a...

Page 6: ...n Interface Reverse Cycle Defrost and Simultaneous Supplemental Resistance Heat on Heat Pumps Quick Heat Recovery Deluxe Line Optional Features Corrosion Protection Internal Condensate Removal on 3900 Series Heat Pump without Corrosion Protection NOTE Dry Air 25 models include all the standard features of the 2900 Series plus standard corrosion protection Premium Line Standard Features All the Sta...

Page 7: ...f failure not covered by the warranty Components of the Zoneline System Typical Installation Deluxe Series shown See pages 22 and 32 for information on electrical sub bases and chaseway See pages 37 39 for information on ducted installations RAK601 602 For Deluxe Series Duct Extension Register and Trim Flange RAK6052 Duct Adapter For Deluxe Series Wall Case RAB71A Steel Insulated RAB77A4 SMC Molde...

Page 8: ...AUTO HIGH LOW AUTO HIGH LOW AUTO Fan Only Setting HIGH LOW Standard Standard Standard Fan Cycle Switch Smart Fan Smart Fan Smart Fan Constant Run Fan Selectable Selectable Selectable Rotary Compressor Standard Standard Standard Automatic Compressor Restart Delay Standard Standard Standard Freeze Sentinel Standard Standard Standard Heat Sentinel Standard Standard Standard Indoor Coil Frost Control ...

Page 9: ...Automatically uses electric resistance heat if the heat pump output is not sufficient to maintain selected room temperature Reverse Cycle Heat Pump Defrost System Standard on all Zoneline 3900 and 5800 Series heat pumps Enables heat pump to operate at lower temperatures when other systems switch to more expensive electric resistance heat See pages 18 and 19 for discussion of heat pump operation an...

Page 10: ... off when the room temperature reaches 80 F This will help dehumidify the air and lower high temperatures so the guest will not be entering an extremely hot room Indoor Coil Frost Control Prevents indoor coil from freezing and causing complaints due to lack of cooling Frost can form on the indoor coil when the unit is operated in cooling when outdoor temperatures are low The unit automatically shu...

Page 11: ...hstand damage from salt air and salt water in seacoast areas Corrosion protection is standard on the 5800 Series and on Dry Air 25 models Heat Pump units with ICR are not available with corrosion protection and should not be installed in seacoast or corrosive environments Units installed in corrosive areas should be examined and cleaned more frequently than normal installations Internal Condensate...

Page 12: ...f page TL4 TL6 Heating temperature limiting See table at bottom of page 7 Heat Sentinel switch Down Heat Sentinel OFF Up Heat Sentinel ON 8 Heat Boost 3900 series only Down Heat Boost OFF Up Heat Boost ON Auxiliary 2900 and 3900 series HIGH COOL 1 2 3 4 5 6 1 2 3 4 5 6 7 8 UP DOWN UP DOWN ALLI2 R All Electric Heat 3900 Series models only C FAN CN Cooling Smart Fan H FAN CY Heating Smart Fan CLASS ...

Page 13: ...ches TL1 TL3 Cooling temperature limiting See table at bottom of page TL4 TL6 Heating temperature limiting See table at bottom of page 7 Diagnostics Switch 8 Heat Sentinel switch Down Heat Sentinel OFF Up Heat Sentinel ON 9 Heat Boost Down Heat Boost OFF Up Heat Boost ON Cooling and Heating temperature limits are set independently temperature limiting switches are in factory set down position exce...

Page 14: ...tems Consult with the provider of other energy management systems to be sure they are compatible with the GE Zoneline Zonelines have standard connectors factory installed to provide a CDC interface that permits the unit to be connected to most of the energy management systems The devices connected to the Zoneline units require no power supply or transformers external to the unit Important CDC Comm...

Page 15: ...t wiring should not be run parallel to line voltage wires since induced current may cause erratic operation All Zoneline 2900 3900 and 5800 Series units are adaptable to Class 2 remote low voltage thermostat The only additional field supplied components are the remote thermostat and wiring necessary to connect it The controls on the unit are not functional when the remote control function is used ...

Page 16: ... the fan wire from the thermostat to either the HIGH or LOW terminal on the unit See the sketch of the unit terminals for the location of the HIGH and LOW fan speed terminals Operating the unit in low fan speed reduces the operating sound level of the unit When connected to a remote thermostat the indoor air temperature sensing is shifted from the unit to the remote thermostat For this reason the ...

Page 17: ...Digital Single Stage Cooling 2 Stage Heating 6 RAK148P1 Digital Programmable 6 Thermostat wire size up to 60 feet AWG20 up to 66 feet AWG18 Remote Thermostat Control Selection Chart For Zoneline Packaged Terminal Units Common Ground White Heater Yellow Compressor Black Not Used On 2800 Green High Speed Fan Green Low Speed Fan Red 24VAC CDC Terminal R GL GH B Y W C Common Ground White Heater Yellow...

Page 18: ...kup to heat pump operation At some point the heat pump is unable to provide sufficient heat to adequately warm the room Many Packaged Terminal Heat Pumps cease heat pump operation and change to more expensive resistance heat at some pre determined outdoor temperature to compensate for the inability of the heat pump to maintain room temperature This point called the switchover point is usually at a...

Page 19: ...t is designed to provide heat pump savings without sacrificing room comfort The Quick Heat Recovery feature is not affected by the Heat Source Logic shown in the chart above For more information about the Quick Heat Recovery Feature see page 9 The full heat output of the resistance heater is dependent upon circuit amperage and the power connection kit used See pages 3 and 42 43 for information on ...

Page 20: ...ized cooling capacity is greater than required for the specific application the unit will typically cool the space down to the desired temperature thermostat set point too quickly The compressor then begins to cycle on and off Dehumidification only takes place when the compressor is operating A typical result in a hot humid climate could be a cool but excessively humid space Heating Undersizing ca...

Page 21: ...hs RAB7116 16 RAB7124 24 RAB7128 28 RAB7131 31 42 13 3 4 16 1 1 2 TYP 1 2 6 21 36 A 1 2 SQ HOLE 2 REQ D 1 2 DIA HOLE 3 REQ D 2 3 4 5 5 8 4 6 19 36 16 1 4 13 7 8 1 1 2 42 1 8 1 2 SQ HOLE 2 REQ D 9 16 2 7 8 5 5 8 4 1 2 DIA 3 REQ D RAB71 42 RAB77 42 1 8 RAB71 13 3 4 RAB77 13 7 8 42 TOP VIEW GRILLE ROOM CABINET INSIDE ROOM CABINET SIDE VIEW RAB71 20 7 8 RAB77 21 OUTSIDE RAB71 16 RAB77 16 1 4 GRILLE 7 ...

Page 22: ...ust conform to any and all local electrical codes and regulations Permanent Connection generally means wiring to the unit must be contained in an enclosed chaseway where access to the wiring connections is more restrictive than a normal line cord plugged into a receptacle NEC requirements may be met by using flexible or rigid conduit to contain the wiring between the unit and a junction box that c...

Page 23: ...h in the wall and these installations usually require a remote thermostat and are discussed on pages 15 and 16 Regardless of the installation there are several things to consider when selecting a location for installing the unit For instance drapery location could interfere with air discharge and placement of furniture may have an impact on the performance of the unit The following information is ...

Page 24: ... be located both near the wall and at the front of the wall case Sub base RAK204 Series with four leveling legs provides an excellent support for the unit in this type of installation See page 28 for details of this type of installation In existing construction common practice is to remove a pane of glass metal wood or other construction material and build a frame around the wall case Similar fill...

Page 25: ...s greater than the case dimensions spacers must be used on the sides between the wall case and the wall support structure to prevent distorting the wall case 3 Caulk or gasket the entire opening on the outside between the wall case and exterior wall surface 4 sides to provide total water and air seal 4 Caulk or gasket room side opening between wall case and interior wall surface 4 sides Opening be...

Page 26: ...ed MAIN STUDS JACK STUD HEADER MOUNTING SCREW HOLE LINTEL Framing detail for this construction is as shown in Figure 1 Note use of lintel under first course of brick above the Zoneline case Do not use the case as a lintel Mounting screw holes shown are to be made by the installer NO HOLES PERMITTED IN BOTTOM OF CASE EXCEPTION RAD10 DRAIN KIT Choice of attachment devices through both ends of case o...

Page 27: ... RECEPTACLE BY OTHERS FINISHED FLOOR OR TOP OF CARPET Caulk around perimeter of wall case all four sides where it joins the building Interior and Exterior CAULK 1 4 CAULK LINTEL RAB71 13 3 4 RAB77 13 7 8 20 7 8 RAB71 21 RAB77 ROOM CABINET 2 MIN MOUNTING SCREWS BY INSTALLER RAB71 16 RAB77 16 1 4 WALL CASE OUTDOOR GRILLE SIDE CHANNEL 3 MIN 5 MAX 1 5 16 FINISHED FLOOR OR TOP OF CARPET SUB BASE RAK204...

Page 28: ...CASE ANGLE FIELD SUPPLIED RAB71 22 1 4 RAB77 22 3 8 WITH RAG61 66 RAB71 21 1 8 RAB77 21 1 4 WITH RAG60 RAB71 16 RAB77 16 1 4 RECEPTACLE BY OTHERS MIN 2 SUPPORTS FIELD SUPPLIED FLOOR USE NO SCREWS IN BOTTOM OF CASE 16 ROOM CABINET WALL CASE OUTDOOR GRILLE CASE ANGLE FIELD SUPPLIED RAB71 22 1 4 RAB77 22 3 8 WITH RAG61 66 RAB71 21 1 8 RAB77 21 1 4 WITH RAG60 RAB71 16 RAB77A 16 1 4 16 WALL OR WINDOW G...

Page 29: ...77 42 1 8 FINISHED EXTERIOR WALL ROOM CABINET RAB71 13 3 4 RAB77 13 7 8 ADJACENT WALL ADJACENT WALL D A C D 27 1 4 TOP VIEW 2 1 2 Caulk around perimeter of wall case all four sides where it joins the building Interior and Exterior ROOM CABINET LINTEL FRONT VIEW ELECTRICAL RECEPTACLE BY OTHERS FLUSH MOUNTED WALL OPENING 16 1 4 x 42 1 4 MIN FOR RAB71 16 1 2 x 42 3 8 MIN FOR RAB77 See page 43 for lin...

Page 30: ...dditionally sealed with a quality grade sealant 2 T he wall case and extension should be connected prior to installation in the wall opening A quality grade sealant should be applied to all four 4 butting flanges Use bolts and nuts or oversized self tapping screws driven from the wall case to the extension to attach the two assemblies Clean all drain holes of excess sealant The assembly must be fr...

Page 31: ...TED TO WALL SURFACE A SPLITTERS MUST BE USED SEE PAGE 30 B D C A B Caulk around perimeter of wall case all four sides where it joins the building Interior and Exterior 1 WIDE 45 DRIP LIP FLASHING OUTDOOR GRILLE CASE For an installation that will provide better protection against water infiltration GE recommends the use of one of the deeper RAB71 wall cases offered as special order items See page 2...

Page 32: ...EE NOTE LEFT SIDE INTERIOR ADJACENT WALL 12 3 4 12 7 8 13 LEVELING SCREW KNOCKOUT SIZE LARGE 1 1 8 DIA SMALL 7 8 DIA KNOCKOUTS ENCLOSURE 4 REAR 4 BOTTOM SHOWN WITH ACCESS COVERS REMOVED NOTE CAUTION REMOVE KNOCKOUTS FROM INSIDE OUT SIDE VIEW WITH WALL CASE SHOWN IN PLACE FINISHED FLOOR 3 MIN ADJUSTABLE TO 5 1 5 16 2 3 8 INTERIOR WALL RAB71 16 RAB77 16 1 4 7 8 1 1 2 FINISHED FLOOR RAB71 16 RAB77 16...

Page 33: ...G TYPE A SCREWS 6 TYPE A SCREW TYPE C SCREW ACCESS PLATES TYPE C SCREW TYPE B SCREW SIDE CHANNELS ARE ADJUSTABLE FROM 13 3 4 TO 2 3 8 IN LENGTH BY BREAKING OFF SECTIONS OF SIDE CHANNELS NOTE IF METAL CASE DOES NOT HAVE SCREW HOLES 5 32 DIA HOLES MUST BE DRILLED 6 FROM EACH SIDE IN FRONT FLANGE SEE INSERT Electrical wiring may enter the sub base through any of the knockout holes provided in the sub...

Page 34: ...ing cooling operation Since the dew point is humidity as well as temperature related there may be more condensate on days when the relative humidity is high Heat Pump Condensate Disposal Since the outdoor coil is cold during heat pump operation the condensate water cannot be deposited on the outdoor coil as the water would cause frost to form on the coil This frost would block the airflow through ...

Page 35: ... water or precipitation to flow into the wall case and drain through two drain holes in the rear of the wall case If there is more water in the wall case than can be drained through these holes it will drain through the three overflow drain holes These drain holes must not be blocked when mounting or caulking the wall case For those installations where water draining from the drain holes is object...

Page 36: ...e bottom of the wall case prior to installation of the case in the wall It may be located anywhere on the room side portion except for sub base installations For these the drain should be at least 3 from the indoor edge of the case so as to adequately clear the sub base 3 A template is furnished with the kit for locating the necessary 3 holes in the case bottom two to provide a securing means and ...

Page 37: ...ations providing the sum of the two duct lengths necessary do not exceed the 44 length Even in single applications the mounting flange must be cut off one end of the duct to accept the collar and supply register Mounting Collar and Supply Register RAK602 These components are included in the Duct Extension Kit RAK601 They may be ordered separately for installations where two duct extensions are mad...

Page 38: ...ille mounting collar and discharge grille Duct extension must be cut to required length Two ducted installations may be made from one kit if the combined ducted length is less than 44 RAK602 kit contains mounting collar discharge grille and mounting hardware necessary for second installation 5 F iller strip field supplied actual width depends upon wall case projection into room A flush installatio...

Page 39: ...LOCATIONS CAULK RAG60 1 4 RAG61 63 1 3 8 Caulk around perimeter of wall case all four sides where it joins the building Interior and Exterior 1 4 MIN 2 29 32 2 3 8 min when installed with RAK204 RAG60 1 4 RAG61 63 1 3 8 3 11 16 RAK 204 3 MIN 5 MAX FINISHED FLOOR 16 1 8 TRANSITION ROOM CABINET WALL CASE Caulk around perimeter of wall case all four sides where it joins the building Interior and Exte...

Page 40: ... Maple RAG63 Bittersweet Chocolate RAG67 Extruded Aluminum Grille The RAG67 is made from extruded anodized aluminum for use where an aluminum architectural grille is preferred The RAG67 is available in a clear finish and may be special ordered from GE in other colors Minimum order quantities may be required Contact your General Electric salesperson for details All grilles are installed and secured...

Page 41: ...d directly to the wall case a field supplied splitter or gasket is required between the chassis and the louver to prevent recirculation It is important that the above criteria be followed since a louver that is too restrictive or allows recirculation will reduce the unit s capacity and efficiency increase the electrical current draw cause intermittent operation due to the compressor overload prote...

Page 42: ... the receptacle in the sub base Permanent or direct wired installation of a 230 208 volt unit requires a junction box kit RAK4002A which attaches to the chassis to form an enclosed junction box The short sub base line cord may not be used without the sub base For 2900 and 3900 Series 230 208 volt units where a permanent installation using flexible conduit is desired the RAK4002A forms an enclosed ...

Page 43: ...was first introduced Some of these changes require alterations to be made when replacing an older unit with a new chassis Line Cord Connected Units The plug configuration of new line cord connected units complies with the current NEC standards Older installations may have wall receptacles that conformed to NEC standards at the time the building was constructed and may not match the configuration o...

Page 44: ... AZ58H07DA 11 5 10 5 15 5 14 1 N A N A AZ58H09DA 11 5 10 5 15 5 14 1 22 3 20 3 AZ58H12DA 11 6 10 6 15 5 14 1 22 3 20 3 AZ58H15DA 11 6 10 6 15 6 14 2 22 4 20 4 All versions Electric Heat Amps include electric heater and fan motor current draw Values shown in table above are also the total connected loads for units installed with sub bases RAK204D15P same as RAK3153 RAK204D20P same as RAK3203 RAK204...

Page 45: ...9000 12000 15000 65 7500 3 85 10000 3 85 12950 3 65 15950 3 45 60 7200 3 80 9600 3 80 12500 3 60 15300 3 40 55 6900 3 75 9100 3 75 11850 3 55 14650 3 35 50 6600 3 65 8700 3 65 11300 3 45 13850 3 25 47 6400 3 60 8400 3 60 10900 3 40 13400 3 20 45 6250 3 55 8200 3 55 10600 3 35 13050 3 15 40 5950 3 45 7700 3 45 9800 3 20 12250 3 05 35 5600 3 35 7100 3 35 9200 3 10 11300 2 95 30 5250 3 20 6500 3 20 8...

Page 46: ...ts except 63 0 46 0 62 0 77 0 92 1 00 1 00 1 00 1 00 Dry Air 25 67 0 42 0 60 0 75 0 88 1 00 1 00 1 00 71 0 42 0 54 0 66 0 78 0 90 1 00 AZ29E07DAP EAP 59 0 38 0 49 0 65 0 80 0 95 1 00 1 00 1 00 1 00 Dry Air 25 63 0 38 0 54 0 68 0 80 1 00 1 00 1 00 1 00 67 0 35 0 52 0 66 0 79 0 92 1 00 1 00 71 0 32 0 45 0 58 0 73 0 85 1 00 All 9000 BTUH 59 0 42 0 59 0 77 0 93 1 00 1 00 1 00 1 00 1 00 units except 63...

Page 47: ...049 520 Glasgow 8 996 410 Great Falls 7 750 420 Missoula 8 125 350 NEBRASKA Grand Island 6 530 770 Omaha 6 612 750 NEVADA Ely 7 733 500 Las Vegas 2 709 1 980 Reno 6 332 520 NEW JERSEY Newark 4 589 710 NEW MEXICO Albuquerque 4 348 1 040 Clayton 5 158 720 Silver City 3 705 1 260 NEW YORK Albany 6 875 480 Binghamton 7 286 310 Buffalo 7 062 450 New York 4 811 790 Rochester 6 748 470 Syracuse 6 756 500...

Page 48: ...Typical 2900 Series 208 230 Volt Wiring Diagram Typical 2900 Series 208 230 Volt Schematic Diagram 48 3900 Series 208 230 Volt Wiring Diagrams ...

Page 49: ...49 ge com 3900 Series 208 230 Volt Wiring Diagrams continued ...

Page 50: ...50 3900 Series 208 230 Volt Schematic Diagrams Schematic Diagram of AZ39H AC motor model 07 Schematic Diagram of AZ39H AC motor model 09 12 15 Schematic diagram of AZ39H DC motor model ...

Page 51: ... OR 265V 208 230V COLOR BK BLACK BL BLUE BR BROWN GR GREEN GY GRAY OR ORANGE RD RED WH WHITE YL YELLOW RD 1 RED 208 230V BLUE 265V WH O L P COMP MOTOR RUNNING CAPACITOR C S R HEATER PROTECTOR RY102 RY109 RY103 OUTDOOR FAN MOTOR INDOOR FAN MOTOR FAN MOTOR CAPACITOR FAN MOTOR CAPACITOR CN102 CN101 RY106 RY107 RY104 RY105 CN8 CN103 Varistor NR101 Capacitor C101 C102 FUSE FU101 DRIVE BOARD UNIT REGULA...

Page 52: ... R I Standard 310 04 for Packaged Terminal Air Conditioners and 380 04 for Packaged Terminal Heat Pump 80 F dry bulb 75 F wet bulb 80 relative humidity Suggested Bid Form Specifications Condenser and evaporator coils to be constructed of copper tubing and aluminum plate fins designed to achieve EER and COP rating of the unit Indoor and outdoor airflows that match the capacity of the coils for effi...

Page 53: ... outdoor air louvers and chassis are installed at which time they are to be removed and discarded by the installer Outside Grille Each unit shall be equipped with a standard exterior grille that has been designed to allow unit operation in high ambient conditions Grilles shall be of material and design specified Special grilles or customer louver sections to be supplied by others will conform to a...

Page 54: ...265 volt cord set units must be installed in compliance with National Electrical Code Power connection kits required on all models See specification sheet for heater KW and branch circuit ampacity RAK3153 RAK3203 RAK3303 230 208 volt line cord connection kit RAK4157 RAK4207 RAK4307 230 208 volt universal power supply kit The Zoneline chassis is identified by a model number defining the type of uni...

Page 55: ... 0 11 7 10 3 Dehumidification Pts Hr 1 7 2 7 3 6 4 5 2 1 3 0 4 0 4 8 Sensible heat ratio 265 volts 75 68 67 67 75 67 68 65 CFM indoor fan high 250 270 300 310 250 265 350 365 CFM indoor fan low 215 235 260 260 220 270 310 330 Vent CFM full open partial open 50 40 70 45 75 45 75 45 40 35 65 60 70 65 70 65 Power Ratings Power factor 88 88 87 92 95 96 94 95 Watts 560 785 1 020 1 480 560 760 1 010 1 4...

Page 56: ...eway included 23 RAK204E30 Sub Base 265 Volt with NEMA 7 30R 30 Amp Receptacle Chaseway included 23 RAK204U Sub Base non electrical Chaseway not included 22 RAK205CW Chaseway for Sub Base 22 RAK3153 Universal Power Cord 2900 3900 5800 series 15 Amp 230 208 V 2 55 2 09 kW heat 42 RAK3203 Universal Power Cord 2900 3900 5800 20 Amp 230 208 V 3 45 2 82 kW heat 42 RAK3303 Universal Power Cord 2900 3900...

Page 57: ...e run through the sub base entering the rear and exiting through one of the front panels When the room cabinet is in place the CDC or remote thermostat wiring is usually not visible to someone standing or sitting in the room Do not run the low voltage wiring in conduits with line voltage wiring or near uninsulated line voltage wiring since induced current can interrupt the low voltage controls Con...

Page 58: ... components If the existing chassis is a slope front discharge and the duct dimensions are 7 3 32 high by 6 1 2 wide only the RAK7022 transition piece is required to install a 2900 or 3900 Series unit in the ducted installation There were a number of Zoneline units installed in ducted installations that did not use a GE duct adapter The easiest way to determine if the existing duct adapter is a GE...

Page 59: ...tallation Suggestions 57 58 Heat Pumps and Energy Savings 18 19 Introduction to Zoneline 6 Latent System Capacity 46 Maximum Connected Load 44 Mini Specs 2900 2 Mini Specs 3900 2 Mini Specs 5800 2 Mini Specs Power Connection Kits and Nomenclature 3 Normal Yearly Operating Data 47 Remote Thermostat Control 15 17 Schematics 48 51 Specifications 55 Suggested Big Form Specifications 52 53 Table of Con...

Page 60: ...of quality and innovation continues GE has a policy of continuous improvement of its products and reserves the right to change materials and specifications without notice 2008 GE Company Pub No 20 S048 PC51901 Before purchasing an appliance read important information about its estimated annual energy consumption or energy efficiency rating that is available from your retailer or ge com GE Consumer...

Reviews: