A–62
3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
PIXIT
PIXIT for GOOSE publish model
ID
Ed
Description
Value / Clarification
Gp1
1,2
Can the test (Ed1) / simulation (Ed2) flag in the
published GOOSE be set
N
Gp2
1
What is the behaviour when the GOOSE publish
configuration is incorrect
DUT keeps GoEna=F
Relay will not send GOOSE message.
Gp3
1,2
Published FCD supported common data classes
are
SPS, INS, ENS, ACT, ACD, MV, CMV, SAV, WYE, DEL, SEQ, INC, ENC, SPC,
DPC, INC, ENC. (Only the elements with FC=ST or MX will be
published).
Gp4
1,2
What is the slow retransmission time
Is it fixed or configurable
Configured by Enervista on GoCB MaxTime (0-60000 ms)
Gp5
1,2
What is the fastest retransmission time
Is it fixed or configurable
Fixed. MinTime = 4 ms
Gp6
-
Can the GOOSE publish be turned on / off by using
SetGoCBValues(GoEna)
Y
Gp7
1,2
What is the initial GOOSE sqNum after restart
sqNum = 1
Gp8
1
May the GOOSE data set contain:
- structured data objects (FCD)
- timestamp data attributes
Y
Y
Gp9
1
How is the retransmission curve after a change.
- sqNum = 0 New change
- sqNum = 1 -> 4ms later with TAL = 1000
- sqNum = 2 -> 8ms later with TAL = 1000
- sqNum = 3 -> 16ms later with TAL = 4000
- sqNum = 4 -> 1000ms later with TAL = Update time* x 4
- sqNum = 5 -> Update time* later with TAL = Update time* x 4
- sqNum = 6-> Update time* later with TAL = Update time* x 4
- sqNum = 7 ……..
- ………….
*Update time is configured in the Enervista 3 Series Setup