4-48
SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
IEC61850 SERVER
CHAPTER 4: 3 SERIES IEC61850 GOOSE
Functionality
CLIENT CONNECTIONS
The 3 Series relay supports up to three IEC61850 concurrent client connections.
LOGICAL DEVICES AND REPORTS
Supported buffered and un-buffered report, and the report triggers are shown in the
Supported Triggers
list.
Supported Triggers
•
Data-change
•
Integrity
•
General-interrogation
Supported buffered and un-buffered report option fields are shown in the
Field
list.
Field
•
Sequence number
•
Report time stamp
•
Reason for inclusion
•
Data set name
•
Data-ref
•
Buffer-overflow (Buffered reports only)
•
Entry id (Buffered reports only)
•
Conf- revision
Report control block configuration settings are modified from the IEC61850 advanced
configurator writing directly to a CID file.
The datasets for reports are fully configurable with CDCs from any Logical Node.