SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
345 MODBUS MEMORY MAP
CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES
42535
0x9E6
Neutral Time OC 2 Function 0
3
1
---
FC197
0
1
42536
0x9E7
Neutral Time OC 2 Pickup
5
2000
1
x CT
F3
100
1
42537
0x9E8
Neutral Time OC 2 Curve
0
14
1
---
F36
0
1
42538
0x9E9
Neutral Time OC 2 Multiplier 5
5000
1
---
F3
100
1
42539
0x9EA
Neutral Time OC 2 Reset
0
1
1
---
F68
0
1
GROUND TOC2
42541
0x9EC
Ground Time OC 2 Function 0
3
1
---
FC197
0
1
42542
0x9ED
Ground Time OC 2 Pickup
5
2000
1
x CT
F3
100
1
42543
0x9EE
Ground Time OC 2 Curve
0
14
1
---
F36
0
1
42544
0x9EF
Ground Time OC 2 Multiplier 5
5000
1
---
F3
100
1
42545
0x9F0
Ground Time OC 2 Reset
0
1
1
---
F68
0
1
SENSITIVE GROUND TOC1
42547
0x9F2
Sensitive Ground Time OC
Function
0
3
1
---
FC197
0
1
42548
0x9F3
Sensitive Ground Time OC
Pickup
5
3000
1
x CT
F17A
1000
1
42549
0x9F4
Sensitive Ground Time OC
Curve
0
14
1
---
F36
0
1
42550
0x9F5
Sensitive Ground Time OC
Multiplier
5
5000
1
---
F3
100
1
42551
0x9F6
Sensitive Ground Time OC
Reset
0
1
1
---
F68
0
1
SENSITIVE GROUND IOC1
42598
0xA25
Sensitive Ground IOC
Function
0
3
1
---
FC197
0
1
42599
0xA26
Sensitive Ground IOC Pickup 5
3000
1
x CT
F17A
1000
1
42600
0xA27
Sensitive Ground IOC Delay 0
30000
1
s
F3
0
1
SENSITIVE GROUND IOC2
42601
0xA28
Sensitive Ground 2 IOC
Function
0
3
1
---
FC197
0
1
42602
0xA29
Sensitive Ground 2 IOC
Pickup
5
3000
1
x CT
F17A
1000
1
42603
0xA2A
Sensitive Ground 2 IOC
Delay
0
30000
1
s
F3
0
1
TRANSFORMER PERCENT DIFFERENTIAL
42608
0xA2F
XFMR Pcnt Func
0
3
1
---
FC197
0
1
42609
0xA30
Minimum Diff Pkp
5
100
1
x CT
F3
10
1
42610
0xA31
Slope1
15
100
1
%
F1
30
1
42611
0xA32
Break 1
50
400
1
x CT
F3
150
1
42612
0xA33
Break 2
100
1000
1
x CT
F3
150
1
42613
0xA34
Slope 2
50
100
1
%
F1
95
1
42614
0xA35
Inrush Inhbit Func
0
1
1
---
FC408
1
1
42615
0xA36
Inrush Level
1
400
1
% fo
F2
200
1
42616
0xA37
Inrush Inhibit Mode
0
3
1
---
FC409
0
1
42617
0xA38
Overexcitation Func
0
1
1
---
FC410
0
1
42618
0xA39
Overexcitation Level
10
400
1
% fo
F2
100
1
42619
0xA3A
Output Relays
0
0x7F
1
---
FC198
0
1
RESTRICTED GROUND FAULT1
42620
0xA3B
RGF 1 Pickup
2
2000
1
x CT
F17A
5
1
Modbus
Address
Hex
Address
Description
Min
Max
Step Units
Format
Code
Factory
Default
Size in
words