2.3 EXTERNAL CONNECTIONS
Signal wiring is to box terminals that can accommodate wire as large as 12 gauge. CT connections
are made using #8 screw ring terminals that can accept wire as large as 8 gauge (see Figure 2–3:
TYPICAL WIRING DIAGRAM on page 2–4). A minimal configuration will include connections for
control power, phase CTs and the trip relay. Other features can be wired as required. Considerations
for wiring each feature are given in the sections that follow.
Table 2–2: EXTERNAL CONNECTIONS
CT ROW
SIGNAL LOWER ROW
SIGNAL UPPER ROW
1
Phase A CT 5A
13
Safety ground
36
Control live (+)
2
Phase A CT 1A
14
Filter ground
37
Control neutral (–)
3
Phase A CT COM
15
RS485 A+
38
Sw com
4
Phase B CT 5A
16
RS485 B–
39
Sw com
5
Phase B CT 1A
17
RS485 ground
40
Sw com
6
Phase B CT COM
18
Analog out +
41
Sw com
7
Phase C CT 5A
19
Analog out –
42
Sw com
8
Phase C CT 1A
20
Analog out shield
43
Access sw +
9
Phase C CT COM
21
Thermistor in +
44
Restart sw +
10
Ground CT 5A
22
Thermistor com
45
Reset sw +
11
Ground CT 50:0.025
23
Trip NO
46
Option 1 sw +
12
Ground CT COM
24
Trip COM
47
Option 2 sw +
25
Trip NC
48
RTD shield
26
Alarm NO
49
RTD1 hot
27
Alarm COM
50
RTD1 comp
28
Alarm NC
51
RTD1 ret
29
Auxiliary NO
52
RTD2 hot
30
Auxiliary COM
53
RTD2 comp
31
Auxiliary NC
54
RTD2 ret
32
Service NO
55
RTD3 hot
33
Service COM
56
RTD3 comp
34
Service NC
57
RTD3 ret
35
Unused
58
Unused
Summary of Contents for 239
Page 2: ......
Page 4: ......
Page 16: ...1 10 239 Motor Protection Relay GE Multilin 1 OVERVIEW 1 OVERVIEW 1 ...
Page 104: ...6 14 239 Motor Protection Relay GE Multilin 6 239PC SOFTWARE 6 239PC SOFTWARE 6 ...
Page 150: ...8 10 239 Motor Protection Relay GE Multilin 8 TESTING 8 TESTING 8 ...
Page 152: ...A 2 239 Motor Protection Relay GE Multilin A 1 239 WARRANTY APPENDIX A A ...
Page 157: ...GE Multilin 239 Motor Protection Relay NOTES ...