The program will now prepare the relay to receive the new firmware file. The 239 will display the
UPLOAD MODE message. If the 239 has boot code revision 2.00 or earlier and a liquid crystal
display, the UPLOAD MESSAGE may not appear. Also, if the 239 has boot code revision 3.00 or
later and a vacuum fluorescent display, the UPLOAD MESSAGE may not appear. In both cases,
the display returns to normal after the firmware upload has successfully completed.
7. A dialog box will appear indicating the file transfer progress and time elapsed. The entire down-
load process takes approximately three minutes.
8. The following dialog box will appear when the firmware has been successfully loaded into the
relay.
9. Carefully read any notes indicated in the box and click on
OK
to return to the main screen. If the
relay does not communicate with the 239PC program, ensure the following setpoints agree with
the 239PC settings shown in the
COMMUNICATION/COMPUTER
window.
c) STEP 3—LOADING SAVED SETPOINTS
1. Select
Open
from the
File
menu.
2. Select the file containing the setpoints to be loaded into the relay (saved in Step 1).
3. Select
Properties
from the
File
menu. The following dialog box will appear:
4. Change the
Version
and
Options
to match the firmware version and options of the 239 relay. The
relay firmware and options can be in
$352'8&7,1)2),50:$5(9(56,216
and
$352'8&7,1)2
Summary of Contents for 239
Page 2: ......
Page 4: ......
Page 16: ...1 10 239 Motor Protection Relay GE Multilin 1 OVERVIEW 1 OVERVIEW 1 ...
Page 104: ...6 14 239 Motor Protection Relay GE Multilin 6 239PC SOFTWARE 6 239PC SOFTWARE 6 ...
Page 150: ...8 10 239 Motor Protection Relay GE Multilin 8 TESTING 8 TESTING 8 ...
Page 152: ...A 2 239 Motor Protection Relay GE Multilin A 1 239 WARRANTY APPENDIX A A ...
Page 157: ...GE Multilin 239 Motor Protection Relay NOTES ...