GE Multilin
239 Motor Protection Relay
7-29
7 COMMUNICATIONS
7 COMMUNICATIONS
7
119B
2
nd
Motor Full Load Current
1-1500
1
***
F1
100 A
119C
2
nd
Phase Timed O/L Curve No
1-15
1
---
F1
4
119D
2
nd
Phase S/C Trip
0-3
1
---
F19
0 = OFF
119E
2
nd
Phase S/C Pickup
10-110
1
0.1 xCT
F1
100 = 10.0 xCT
119F
2
nd
Phase S/C Delay
0-60000
10
ms
F1
‡
0 ms
11A0
Reserved
to
↓
11AF
Reserved
11B0
OPTION
SWITCH 2
Option Switch 2 characters 1 and 2
32-127
1
ASCII
F8
"OP"
11B1
Option Switch 2 characters 3 and 4
32-127
1
ASCII
F8
"TI "
11B2
Option Switch 2 characters 5 and 6
32-127
1
ASCII
F8
"ON"
1193
Option Switch 2 characters 7 and 8
32-127
1
ASCII
F8
" S"
11B4
Option Switch 2 characters 9 and 10
32-127
1
ASCII
F8
"WI"
11B5
Option Switch 2 characters 11 and 12
32-127
1
ASCII
F8
"TC"
11B6
Option Switch 2 characters 13 and 14
32-127
1
ASCII
F8
"H "
11B7
Option Switch 2 characters 15 and 16
32-127
1
ASCII
F8
"2 "
11B8
Option Switch 2 characters 17 and 18
32-127
1
ASCII
F8
" "
11B9
Option Switch 2 characters 19 and 20
32-127
1
ASCII
F8
" "
11BA
3
rd
Phase CT Primary
5-1500
5
A
F1
100 A
11BB
3
rd
Motor Full Load Current
1-1500
1
***
F1
100 A
11BC
3
rd
Phase Timed O/L Curve No
1-15
1
---
F1
4
11BD
3
rd
Phase S/C Trip
0-3
1
---
F19
0 = OFF
11BE
3
rd
Phase S/C Pickup
10-110
1
0.1 xCT
F1
100 = 10.0 xCT
11BF
3
rd
Phase S/C Delay
0-60000
10
ms
F1
‡
0 ms
11C0
4
th
Phase CT Primary
5-1500
5
A
F1
100 A
11C1
4
th
Motor Full Load Current
1-1500
1
***
F1
100 A
11C2
4
th
Phase Timed O/L Curve No
1-15
1
---
F1
4
11C3
4
th
Phase S/C Trip
0-3
1
---
F19
0 = OFF
11C4
4
th
Phase S/C Pickup
10-110
1
0.1 xCT
F1
100 = 10.0 xCT
11C5
4
th
Phase S/C Delay
0-60000
10
ms
F1
‡
0 ms
11C6
Reserved
11C7
Reserved
11C8
Reserved
11C9
Reserved
11CA
Reserved
11CB
Reserved
Table 7–1: 239 MEMORY MAP (Sheet 17 of 18)
REG
ADDR
(HEX)
GROUP
DESCRIPTION
REGISTER
VALUE
RANGE
STEP
VALUE
UNITS &
SCALE
FOR-
MAT
FACTORY
DEFAULT VALUE
(CONVERTED)
1, 2, 3,
*
,
**
,
***
,
****
,
†, ‡
See page 7–30 for explanation of Table notes.
Summary of Contents for 239
Page 2: ......
Page 4: ......
Page 16: ...1 10 239 Motor Protection Relay GE Multilin 1 OVERVIEW 1 OVERVIEW 1 ...
Page 104: ...6 14 239 Motor Protection Relay GE Multilin 6 239PC SOFTWARE 6 239PC SOFTWARE 6 ...
Page 150: ...8 10 239 Motor Protection Relay GE Multilin 8 TESTING 8 TESTING 8 ...
Page 152: ...A 2 239 Motor Protection Relay GE Multilin A 1 239 WARRANTY APPENDIX A A ...
Page 157: ...GE Multilin 239 Motor Protection Relay NOTES ...