Programming 

FireShield Technical Reference Manual 

 

3.13 

3.  Press Reset to select tone or pulse dialing for line 2. 

4.  Press Panel Silence to save and advance to the next 

program option. 

 

The trouble buzzer sounds a long beep as confirmation. 

22. Select AC fail delay time 

Description: The AC fail delay lets you set the amount of time 
before the panel signals that it is operating with insufficient or 
no AC power. 

Settings: 6 hours (central station) 
 

15 hours (remote station) 

Default: 6 hours 

To select the AC fail delay time: 

1.  Press Reset to select the desired AC fail delay time. 

2.  Press Panel Silence to save and advance to the next step. 

 

The trouble buzzer sounds a long beep as confirmation. 

23. Enter the transmission test time 

Description: Specifies the time of day the transmission test 
message is sent to the CMS. Values are in 24-hour time. 

Format: 0000 – 2359 

Default: 0217 

To enter the transmission test time: 

1.  Press Reset to enter the hour. 

2.  Press Panel Silence to save. 

 

The trouble buzzer sounds a long beep as confirmation. 

3.  Press Reset to enter the minutes. 

4.  Press Panel Silence to save and advance to the next 

program option. 

 

The trouble buzzer sounds a long beep as confirmation. 

24. Select the transmission test frequency 

Description: Specifies the number of days between sending a 
transmission test message to the CMS. 

Note: 

NFPA 72 and UL 864 require daily tests for commercial 

systems. 

Settings: 0  =  None 
 1 

Daily 

 

2 = 30 days 

Default: 1 (daily) 

To select the transmission test frequency: 

1.  Press Reset to select the transmission test frequency. 

2.  Press Panel Silence to save and advance to the next step. 

 

The trouble buzzer sounds a long beep as confirmation. 

25. Enter the number of rings to answer 

Description: Sets the number of rings that are ignored before 
answering an incoming modem call. 

Settings: 0 – 15 rings 

Default: 5 (rings) 

To enter the number of rings: 

1.  Press Reset to change the number of rings to answer. 

2.  Press Panel Silence to save and advance to the next 

program option. 

 

The trouble buzzer sounds a long beep as confirmation. 

26. Select the ring type 

Description: Specifies the type of ring expected when an 
incoming call is received. 

Default: Ring type (additional options to be added in future 
release). DACT answers any ring type after programmed ring 
count. 

To select the ring type: 

1.  Press Reset to select ring type. 

2.  Press Panel Silence to save and advance to the next step. 

 

The trouble buzzer sounds a long beep as confirmation. 

27. Enable (disable) call back 

Description: Call back adds increased security when uploading 
or downloading. When an incoming call is received on line 
one, the panel establishes a connection and waits for a valid 
password. If call back is not enabled, uploading or 
downloading begins. If call back is enabled, the panel 
disconnects the incoming call and dials the programmed call 
back number. Once the connection is reestablished, uploading 
or downloading can begin. 

Settings: No 
 Yes 

Default: No 

To enable (disable) call back: 

1.  Press Reset to select enable (disable) call back. 

2.  Press Panel Silence to save and advance to the next 

program option. 

 

The trouble buzzer sounds a long beep as confirmation. 

Summary of Contents for FireShield FS302

Page 1: ...FireShield Technical Reference Manual P N 3100353 Rev 3 0 12MAY03...

Page 2: ...Code Underwriters Laboratories Standard 864 8th Edition Underwriters Laboratories of Canada Standard ULC S527 99 Canadian Electrical Code Part I Standard for Installation of Fire Alarm Systems ULC S5...

Page 3: ...ode any time an event is introduced into the system When this happens the panel Changes contact positions on appropriate common relays Activates alarm outputs for alarm events only Turns on the approp...

Page 4: ...mode Selects an IDC to place it into or remove it from walk test mode Programming mode Selects an IDC so that settings can be viewed or changed 4 Notification Appliance Circuits NACs LEDs and controls...

Page 5: ...FSDACT to the circuit board 7 Operator Interface Includes operator controls LED indicators and circuit identification labels 8 Cabinet enclosure Houses the panel electronics and standby batteries In...

Page 6: ...ilence an FSRSI buzzer 1 Press the Silence button on the FSRSI 2 Determine the type of condition that caused the buzzer to sound alarm trouble supervisory or monitor 3 Determine the cause of the condi...

Page 7: ...command You can use the drill command to activate all of the notification appliance circuits Pressing Drill activates all audibles and visuals according to the panel programming but does not activate...

Page 8: ...once 2 Press the Disable button for the IDC you want to test 3 Conduct your walk test for the IDC 4 When you are finished testing an IDC press the Disable button to turn off the walk test for that IDC...

Page 9: ...panel detected a ground fault Transformer 2 TR The panel detected a trouble condition in the Power Expander Transformer AUX Power Troub The panel detected a trouble condition in the AUX power circuit...

Page 10: ...System overview and operation 1 8 FireShield Technical Reference Manual...

Page 11: ...is off before connecting wires to the terminal block Connect batteries See Appendix C or the panel label Program the panel Refer to Chapter 3 Test for proper operation Installing the cabinet Cabinets...

Page 12: ...d fault Buzzer On On temporal On slow pulse On intermittent Off System trouble Alarm condition Supervisory condition AC fail Normal or silenced Jumper setup Jumper Name Description J2 Group jumper All...

Page 13: ...es conditions for five IDCs The IDC groups are set by jumpers to indicate zones 1 5 or zones 6 10 Paper inserts are provided for labeling the LEDs Note You must run the Find Annunciators program optio...

Page 14: ...ution Make sure all power is disconnected from the panel before installing Observe static sensitive handling practices To install the FSRZI A 1 Verify that all field wiring is free of opens shorts and...

Page 15: ...e 0 03 F Max circuit resistance 13 ohms Relay ratings 30 Vdc 1 A resistive load Wire size Minimum 18 AWG 0 75 sq mm Maximum 12 AWG 2 5 sq mm Mounting MFC A cabinet or listed fire alarm enclosure Opera...

Page 16: ...track Mount in first slot only 5 Verify that all wiring is free of opens shorts and ground faults 6 Connect the FSRRM to the panel or other peripheral devices 7 Power up the panel and confirm that all...

Page 17: ...d serviceable Note Input current rating is included with the overall ten zone ratings Installation instructions Caution Make sure all power is disconnected from the panel before installing Observe sta...

Page 18: ...mote station systems Cutting the JP1 wire loop configures the FSDACT for unattended downloading This means that the program jumper need not be inserted to accept any panel or dialer configuration chan...

Page 19: ...ocedures that could affect the operation of the dialer If this happens the telephone company will provide advance notice in order for you to make necessary modifications to maintain uninterrupted serv...

Page 20: ...g the RPM Note The RPM must be mounted in an MFC A enclosure immediately adjacent to the panel and in conduit Alarm transmitted only TRBL C NC SUP NO ALM C C 24VOUT FireShield TB3 NO NO From ALRM on R...

Page 21: ...ammed for Signal Silence Specifications Power Nominal 24 Vdc 200 mA Municipal box operation Nominal 24 Vdc Maximum wiring resistance 25 Trip current 200 mA into 14 5 coil Maximum current 300 mA Standb...

Page 22: ...ame with the auxiliary power supply FireShield FACP Aux Power UL Listed Aux Power Source To Devices 24 Vdc 0 5 A Max To Devices Requiring Additional Power Installing the terminal shield The terminal s...

Page 23: ...e total value of the bottom row equals the setting number The values of all LEDs lit on a single row are added to determine the option or setting number For example if the Gnd Fault Walk Test and Sign...

Page 24: ...oad the default settings 1 Install program jumper PRG The panel common LEDs flash and the panel enters a trouble state The trouble buzzer sounds 2 Press Remote Disconnect to select the Load Defaults p...

Page 25: ...ed for a particular option it can be skipped You can use Remote Disconnect to advance to the next option or Walk Test to return to the previous option To save your changes you must press Panel Silence...

Page 26: ...g Sil Inhibit None Signal Silence Reset operational immediately after NACs turn on Inhibit one min Signal Silence Reset operational one minute after NACs turn on To program the signal silence reset in...

Page 27: ...the program option For new panels the Trouble LED of IDC 1 lights Otherwise the Trouble LED of the last IDC programmed lights To select an IDC for programming press the IDC Disable button 2 Press Rese...

Page 28: ...When the Trouble LED is lit you can program the NAC class by repeating steps 2 and 3 above Note Make sure you set the NAC jumpers to match the class for which you program the NAC 9 Program NAC outputs...

Page 29: ...CT Description Initiates the FSDACT for programming This option is not displayed if you do not have a FSDACT you can proceed to Finishing up below Program option Top LEDs LCD Setting Bottom LEDs LCD D...

Page 30: ...ollowing table describes the function of each digit that can be entered in FSDACT programming fields Digit Telephone number 4 2 event codes 0 to 9 Numeric digits Numeric digits A DTMF A Hexadecimal A...

Page 31: ...your passcode 1 Press Reset or Signal Silence Drill to scroll through the setting list until the first digit of your passcode is displayed 2 Press Panel Silence to save and advance to the next digit T...

Page 32: ...e buzzer sounds a long beep as confirmation Note If Single Line DACT is selected dual line programming is skipped If Modem LCD only is selected all account and receiver related programming is skipped...

Page 33: ...ores No restores Default Send restores To select the restore option 1 Press Reset to select the restore option for CMS one 2 Press Panel Silence to save The trouble buzzer sounds a long beep as confir...

Page 34: ...To select the DACR2 alarm format 1 Press Reset to select the desired format 2 Press Panel Silence to save and advance to the next step The trouble buzzer sounds a long beep as confirmation 18 Select t...

Page 35: ...ssion test frequency 1 Press Reset to select the transmission test frequency 2 Press Panel Silence to save and advance to the next step The trouble buzzer sounds a long beep as confirmation 25 Enter t...

Page 36: ...ng option after completing Select the restore option is Panel Tst Rcvr Twenty one event receiver locations must be programmed using steps described below under Select CMS locations for event reporting...

Page 37: ...ry Monitor Alarm X X Waterflow X X Waterflow Supervisory X X X Supervisory X X Monitor X X Settings None CS 1 CS 2 CS 1 and 2 Default CS 1 To select the receiver for each IDC event 1 Select an IDC for...

Page 38: ...e restoration code Description Sets the 4 2 event code that is transmitted to the CMS for an IDC restoral event Format 1 digit 0 9 and A F Default See Appendix E Default event codes This can be change...

Page 39: ...ess Remote Disconnect to advance to the programming option you want to change The currently stored data is displayed 7 Edit the program option with the desired setting Use the program buttons to enter...

Page 40: ...Programming 3 18 FireShield Technical Reference Manual...

Page 41: ...be periodically inspected tested and replaced at a minimum every four years Preventive maintenance schedule Refer to NFPA 72 Chapter 7 Inspection Testing and Maintenance Canadian Electrical Code Part...

Page 42: ...Maintenance 4 2 FireShield Technical Reference Manual...

Page 43: ...12180 NB or equivalent Refer to Panel specifications in Chapter 2 for more information If batteries over 7 Ah are required for the three and five zone panels you must use the BC 2 battery cabinet Ref...

Page 44: ...e of FSRSI FSRZI A and FSRRM is limited as follows Three and five zone panels support 2 FSRSIs 2 FSRZI As and 4 FSRRMs ten zone panels support 2 FSRSIs 4 FSRZI As and 6 FSRRMs 2 See the FireShield UL...

Page 45: ...t length Total circuit current 2 Wire resistance per 1000 ft 1 Voltage drop feet x amps x 1000 Panel voltage Voltage drop End of line voltage 3 Voltage drop Panel voltage Voltage drop 4 4 NAC 4 voltag...

Page 46: ...ed 18 AWG 16 AWG 14 AWG 12 AWG 0 25 584 950 1460 2170 0 50 292 474 730 1084 0 75 194 316 486 722 1 00 146 236 364 542 1 25 116 190 292 434 1 50 92 158 242 362 Maximum signal loss allowed 1 V 1000 Wire...

Page 47: ...tard supervisory latching 5 Waterflow no retard supervisory latching 6 Supervisory latching 7 Monitor 8 NAC Assignment IDC1 IDC2 IDC3 IDC4 IDC5 IDC6 IDC7 IDC8 IDC9 IDC10 NAC1 NAC2 NAC3 NAC4 7 IDC clas...

Page 48: ...Restores Retry Count 05 10 05 Retry Time 05 10 05 Receiver 2 DACR2 Setup Phone 1 Ex 19415551212 Phone 2 Ex 19415551212 Account 0 9 A F FFFF Format Contact ID EST 4 2 Restores Send Restores No Restore...

Page 49: ...6E DACT delivery trouble None CS 1 CS 2 CS 1 2 67 System trouble restoral 4 2 code 0 F D Zone settings IDC 1 Note For IDCs program only those events that apply to the IDC zone type you specified on th...

Page 50: ...CS 2 CS 1 2 76 Supervisory activation None CS 1 CS 2 CS 1 2 36 Monitor activation None CS 1 CS 2 CS 1 2 56 Zone settings IDC 7 Event Where to report the event 4 2 event code Alarm activation None CS...

Page 51: ...code Trouble activation None CS 1 CS 2 CS 1 2 61 NAC settings NAC 2 Event Where to report the event 4 2 event code Trouble activation None CS 1 CS 2 CS 1 2 62 NAC settings NAC 3 Event Where to report...

Page 52: ...Programming templates B 6 FireShield Technical Reference Manual Contact ID codes Code Description Code Description...

Page 53: ...Vfwr Operating current 1 5 A circuit 1 5 A total EOLR Circuit impedance 13 0 03 F max 4 7 k 1 2 W P N EOL4 7 NAC1 NAC2 NAC2 NAC1 EOLR EOLR IDC1 IDC1 IDC2 IDC2 IDC3 IDC3 PRG MAIN SUPPLY CIRCUIT 120 V 6...

Page 54: ...EMOTE MODULE AND REMOTE RELAY WIRING 6 POWER ALARM SUP TBL GND FLT SILENCE LMPTST C C 24VDC 24VDC REMOTE RELAY MODULE RRM WATERFLOW SUPERVISORY COMBINATION CIRCUIT 4 8 6 Requires continuous 24 Vdc fro...

Page 55: ...ircuit may damage the equipment if NAC jumpers are missing or set incorrectly See DETAIL A NAC1 NAC2 NAC2 NAC1 EOLR EOLR IDC1 IDC1 IDC2 IDC2 IDC3 IDC3 IDC4 IDC4 IDC5 IDC5 DETAIL A L N LINE EARTH GND N...

Page 56: ...EMOTE MODULE AND REMOTE RELAY WIRING 6 POWER ALARM SUP TBL GND FLT SILENCE LMPTST C C 24VDC 24VDC REMOTE RELAY MODULE RRM WATERFLOW SUPERVISORY COMBINATION CIRCUIT 4 8 6 Requires continuous 24 Vdc fro...

Page 57: ...anical connection to the chassis even with the ground wire removed CAUTION The panel does not indicate when JP13 or JP14 are missing A shorted NAC circuit may damage the equipment if NAC jumpers are m...

Page 58: ...k and 3 6 k resistors 5 Marking indicates output signal polarity when the circuit is active Polarity reverses when the circuit is not active Wire notification appliances accordingly Notification appl...

Page 59: ...batteries will fit in the panel Note If batteries greater than 7 Ah are required you must use the BC 2 battery cabinet Refer to installation sheet P N 3100027 Up to two 18 Ah batteries will fit in the...

Page 60: ...Panel specifications D 2 FireShield Technical Reference Manual...

Page 61: ...0007 37300008 37300009 37300010 Fire trouble 380 Sensor trouble IDC 1 Fire trouble 380 Sensor trouble IDC 2 Fire trouble 380 Sensor trouble IDC 3 Fire trouble 380 Sensor trouble IDC 4 Fire trouble 380...

Page 62: ...eset AC Signal silence activated AD Drill activated AE DACT disabled AF Walk test activated B N 1 4 NAC enabled not configurable B5 FSRRM outputs enabled not configurable BB Panel reset restore not co...

Page 63: ...tact ID codes E 1 CTM description 2 11 installing 2 11 wiring 2 11 D default event codes FSDACT E 1 defaults factory defaults 3 2 reloading the factory defaults 3 2 disable IDC 1 2 1 5 LED 1 2 NAC 1 2...

Page 64: ...lue 3 1 FSRSI 2 2 FSRZI A 2 3 programming 3 1 system 1 2 load defaults description 3 3 3 9 programming 3 3 3 9 M maintenance 4 1 metal dead front installing 2 12 MFC A FSRRM 2 6 monitor IDC zone type...

Page 65: ...mode 1 2 programming mode 1 2 3 1 silencing FSRSI buzzer 1 4 notification appliances 1 4 panel buzzer 1 4 specifications FSRRM 2 5 FSRSI 2 2 FSRZI A 2 3 panel D 1 power expander transformer 2 7 super...

Page 66: ...Index Z 4 FireShield Technical Reference Manual...

Page 67: ...ts turn on This function will not automatically notify the fire department TO PERFORM A LAMP TEST panel and remote annunciators 1 Press and hold the Remote Disconnect and Walk Test buttons simultaneou...

Page 68: ......

Reviews: