B-64
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
PICS
CHAPTER B: IEC 61850 IMPLEMENTATION DETAILS
S39
1,2 SetGoCBValues
TP
Y
GSSE (Ed2:61850-7-2 Annex C)
S40
1,2 SendGSSEMessage
MC
Deprecated
GSSE Control Block (Ed2:61850-7-2 Annex C)
S41
1,2 GetGsReference
TP
Deprecated
S42
1,2 GetGSSEDataOffset
TP
Deprecated
S43
1,2 GetGsCBValues
TP
Deprecated
S44
1,2 SetGsCBValues
TP
Deprecated
Transmission of sampled value model (SVC)
Multicast SV
S45
1,2 SendMSVMessage
MC
Use for 9-2LE or IEC 61869-9
Multicast Sampled Value Control Block
S46
1,2 GetMSVCBValues
TP
S47
1,2 SetMSVCBValues
TP
Unicast SV
S48
1,2 SendUSVMessage
TP
Unicast Sampled Value Control Block
S49
1,2 GetUSVCBValues
TP
S50
1,2 SetUSVCBValues
TP
Control
S51
1,2 Select
TP
Y
SBO Normal Security
S52
1,2 SelectWithValue
TP
Y
SBO Enhanced Security
S53
1,2 Cancel
TP
Y
S54
1,2 Operate
TP
Y
S55
1,2 CommandTermination
TP
Y
S56
1,2 TimeActivatedOperate
TP
File transfer
S57
1,2 GetFile
TP
Y
S58
1,2 SetFile
TP
S59
1,2 DeleteFile
TP
S60
1,2 GetFileAttributeValues
TP
S61
1,2 GetServerDirectory (FILE)
TP
Y
Time
T1
1,2 Time resolution of internal clock
-
2 ms
nearest negative power of 2 in seconds
T2
2
Time accuracy of internal clock
-
TL (ms) (low accuracy), T3 < 7) (only Ed2)
1,2
-
T0 (ms) (<= 10 ms), 7 <= T3 < 10)
1,2
-
T1 (µs) (<= 1 ms), 10 <= T3 < 13
1,2
-
T2 (µs) (<= 100 µs), 13 <= T3 < 15
1,2
-
T3 (µs) (<= 25 µs), 15 <= T3 < 18
1,2
-
T4 (µs) (<= 4 µs), 18 <= T3 < 20
1,2
-
T5 (µs) (<= 1 µs), T3 >= 20)
T3
1,2 Supported TimeStamp resolution
-
1 µs
nearest negative power of 2 in seconds
Ed
ACSI Service
AA:
TP/MC
Client Sub
(C)
Server Pub
(S)