
CHAPTER 13: MODBUS MEMORY MAP
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
13-287
78290
0x9591 Relays
0
0xFFFFFFFF
1
FC198
0
2
Y
78292
0x9593 Block
0
0xC6CD00
1
FC142
0
2
Y
78294
0x9595 Events
0
1
1
FC126
1
1
Y
78295
0x9596 Targets
0
2
1
FC101
1
1
Y
Frequency Rate Of Change 9
78309
0x95A4 Function
0
4
1
FC100
0
1
Y
78310
0x95A5 Trend
0
2
1
FC253
0
1
Y
78311
0x95A6 Pickup
10
1500
1
Hz/sec
F2
50
1
Y
78312
0x95A7 Pickup Delay
0
6000000
1
s
F13
2000
2
Y
78314
0x95A9 Minimum Frequency
2000
8000
1
Hz
F2
4500
1
Y
78315
0x95AA Maximum Frequency
2000
8000
1
Hz
F2
6500
1
Y
78317
0x95AC Minimum Voltage
0
1250
1
x VT
F13
700
2
Y
78320
0x95AF Minimum Current
0
30000
1
x CT
F13
200
2
Y
78322
0x95B1 Relays
0
0xFFFFFFFF
1
FC198
0
2
Y
78324
0x95B3 Block
0
0xC6CD00
1
FC142
0
2
Y
78326
0x95B5 Events
0
1
1
FC126
1
1
Y
78327
0x95B6 Targets
0
2
1
FC101
1
1
Y
Frequency Rate Of Change 10
78341
0x95C4 Function
0
4
1
FC100
0
1
Y
78342
0x95C5 Trend
0
2
1
FC253
0
1
Y
78343
0x95C6 Pickup
10
1500
1
Hz/sec
F2
50
1
Y
78344
0x95C7 Pickup Delay
0
6000000
1
s
F13
2000
2
Y
78346
0x95C9 Minimum Frequency
2000
8000
1
Hz
F2
4500
1
Y
78347
0x95CA Maximum Frequency
2000
8000
1
Hz
F2
6500
1
Y
78349
0x95CC Minimum Voltage
0
1250
1
x VT
F13
700
2
Y
78352
0x95CF Minimum Current
0
30000
1
x CT
F13
200
2
Y
78354
0x95D1 Relays
0
0xFFFFFFFF
1
FC198
0
2
Y
78356
0x95D3 Block
0
0xC6CD00
1
FC142
0
2
Y
78358
0x95D5 Events
0
1
1
FC126
1
1
Y
78359
0x95D6 Targets
0
2
1
FC101
1
1
Y
Frequency Rate Of Change 11
78373
0x95E4 Function
0
4
1
FC100
0
1
Y
78374
0x95E5 Trend
0
2
1
FC253
0
1
Y
78375
0x95E6 Pickup
10
1500
1
Hz/sec
F2
50
1
Y
78376
0x95E7 Pickup Delay
0
6000000
1
s
F13
2000
2
Y
78378
0x95E9 Minimum Frequency
2000
8000
1
Hz
F2
4500
1
Y
78379
0x95EA Maximum Frequency
2000
8000
1
Hz
F2
6500
1
Y
78381
0x95EC Minimum Voltage
0
1250
1
x VT
F13
700
2
Y
78384
0x95EF
Minimum Current
0
30000
1
x CT
F13
200
2
Y
78386
0x95F1 Relays
0
0xFFFFFFFF
1
FC198
0
2
Y
78388
0x95F3 Block
0
0xC6CD00
1
FC142
0
2
Y
78390
0x95F5 Events
0
1
1
FC126
1
1
Y
78391
0x95F6 Targets
0
2
1
FC101
1
1
Y
Frequency Rate Of Change 12
78405
0x9604 Function
0
4
1
FC100
0
1
Y
Modbus
Address
Hex
Address
Description
Min
Max
Step Units
Format
Code
Factory
Default
Size in
Words
8
5
0
8
6
9
8
8
9
8
4
5