
CHAPTER 13: MODBUS MEMORY MAP
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
13-277
76690
0x8F51 Relays
0
0xFFFFFFFF
1
FC198
0
2
Y
76692
0x8F53 Block
0
0xC6CD00
1
FC142
0
2
Y
76694
0x8F55 Events
0
1
1
FC126
1
1
Y
76695
0x8F56 Targets
0
2
1
FC101
1
1
Y
Wattmetric Ground Fault 3
76709
0x8F64 Function
0
4
1
FC100
0
1
Y
76710
0x8F65 VT Input
0x12
0x28
1
FC103B 0x12
1
Y
76711
0x8F66 Voltage
0
1
1
FC272A 0
1
Y
76712
0x8F67 Operating Voltage Pickup 2
300
1
x VT
F2
20
1
Y
76713
0x8F68 CT Input
1
5
1
FC102A 1
1
Y
76714
0x8F69 Current
0
1
1
FC276
0
1
Y
76715
0x8F6A Operating Current Pickup 2
30000
1
x CT
F3
60
1
Y
76716
0x8F6B Power Pickup
1
1200
1
CTxVT
F3
100
1
Y
76717
0x8F6C Reference Power Pickup
1
1200
1
CTxVT
F3
500
1
Y
76718
0x8F6D ECA
0
359
1
°Lag
F0
0
1
Y
76719
0x8F6E
Power Pickup Delay
0
6000000
1
s
F13
200
2
Y
76721
0x8F70 Curve
5
19
1
FC161B 7
1
Y
76722
0x8F71 Multiplier
1
200
1
s
F2
100
1
Y
76723
0x8F72 Relays
0
0xFFFFFFFF
1
FC198
0
2
Y
76725
0x8F74 Block
0
0xC6CD00
1
FC142
0
2
Y
76727
0x8F76 Events
0
1
1
FC126
1
1
Y
76728
0x8F77 Targets
0
2
1
FC101
1
1
Y
Wattmetric Ground Fault 4
76742
0x8F85 Function
0
4
1
FC100
0
1
Y
76743
0x8F86 VT Input
0x12
0x28
1
FC103B 0x12
1
Y
76744
0x8F87 Voltage
0
1
1
FC272A 0
1
Y
76745
0x8F88 Operating Voltage Pickup 2
300
1
x VT
F2
20
1
Y
76746
0x8F89 CT Input
1
5
1
FC102A 1
1
Y
76747
0x8F8A Current
0
1
1
FC276
0
1
Y
76748
0x8F8B Operating Current Pickup 2
30000
1
x CT
F3
60
1
Y
76749
0x8F8C Power Pickup
1
1200
1
CTxVT
F3
100
1
Y
76750
0x8F8D Reference Power Pickup
1
1200
1
CTxVT
F3
500
1
Y
76751
0x8F8E
ECA
0
359
1
°Lag
F0
0
1
Y
76752
0x8F8F
Power Pickup Delay
0
6000000
1
s
F13
200
2
Y
76754
0x8F91 Curve
5
19
1
FC161B 7
1
Y
76755
0x8F92 Multiplier
1
200
1
s
F2
100
1
Y
76756
0x8F93 Relays
0
0xFFFFFFFF
1
FC198
0
2
Y
76758
0x8F95 Block
0
0xC6CD00
1
FC142
0
2
Y
76760
0x8F97 Events
0
1
1
FC126
1
1
Y
76761
0x8F98 Targets
0
2
1
FC101
1
1
Y
Reactive Power
76910
0x902D Trip Function
0
4
1
FC100D 0
1
Y Y
76911
0x902E Positive var Trip Pickup
2
200
1
x Rated F2
80
1
Y
76912
0x902F Negative var Trip Pickup
2
200
1
x Rated F2
80
1
Y
76913
0x9030 Positive var Trip Delay
0
60000
1
s
F2
1000
1
Y Y
Modbus
Address
Hex
Address
Description
Min
Max
Step Units
Format
Code
Factory
Default
Size in
Words
8
5
0
8
6
9
8
8
9
8
4
5