CHAPTER 13: MODBUS MEMORY MAP
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
13-239
70660
0x77C3 Signal Input
1
5
1
FC102A 1
1
Y
70662
0x77C5 Pickup
50
30000
1
x CT
F13
1000
2
Y
70664
0x77C7 Direction
0
16
1
FC164D 0
1
Y
70665
0x77C8 Pickup Delay
0
6000000
1
s
F13
0
2
Y
70667
0x77CA Dropout Delay
0
6000000
1
s
F13
0
2
Y
70669
0x77CC Relays
0
0xFFFFFFFF
1
FC198
0
2
Y
70671
0x77CE Block
0
0xC6CD00
1
FC142
0
2
Y
70673
0x77D0 Events
0
1
1
FC126
1
1
Y
70674
0x77D1 Targets
0
2
1
FC101
1
1
Y
Neutral IOC 16
70688
0x77DF Function
0
4
1
FC100
0
1
Y
70689
0x77E0 Signal Input
1
5
1
FC102A 1
1
Y
70691
0x77E2 Pickup
50
30000
1
x CT
F13
1000
2
Y
70693
0x77E4 Direction
0
16
1
FC164D 0
1
Y
70694
0x77E5 Pickup Delay
0
6000000
1
s
F13
0
2
Y
70696
0x77E7 Dropout Delay
0
6000000
1
s
F13
0
2
Y
70698
0x77E9 Relays
0
0xFFFFFFFF
1
FC198
0
2
Y
70700
0x77EB Block
0
0xC6CD00
1
FC142
0
2
Y
70702
0x77ED Events
0
1
1
FC126
1
1
Y
70703
0x77EE
Targets
0
2
1
FC101
1
1
Y
Neutral Directional OC 1
70843
0x787A Function
0
1
1
FC126
0
1
Y Y Y Y
70844
0x787B Signal Input
1
5
1
FC102D 1
1
Y
Y Y
70845
0x787C Polarizing Mode
1
3
1
FC156
1
1
Y Y Y Y
70846
0x787D Polarizing Voltage
0
1
1
FC272
0
1
Y Y Y Y
70847
0x787E Pos-Seq Restraint
0
500
1
F3
63
1
Y Y Y Y
70849
0x7880 Forward ECA
-90
90
1
°
F20
75
1
Y Y Y Y
70850
0x7881 Forward Limit Angle
40
90
1
°
F0
90
1
Y Y Y Y
70851
0x7882 Forward Pickup
50
30000
1
x CT
F3
50
1
Y Y Y Y
70852
0x7883 Reverse Limit Angle
40
90
1
°
F0
90
1
Y Y Y Y
70853
0x7884 Reverse Pickup
50
30000
1
x CT
F3
50
1
Y Y Y Y
70854
0x7885 Block
0
0xC6CD00
1
FC142
0
2
Y Y Y Y
70856
0x7887 Events
0
1
1
FC126
1
1
Y Y Y Y
70857
0x7888 Targets
0
2
1
FC101
1
1
Y Y Y Y
Neutral Directional OC 2
70871
0x7896 Function
0
1
1
FC126
0
1
Y
70872
0x7897 Signal Input
1
5
1
FC102D 1
1
Y
70873
0x7898 Polarizing Mode
1
3
1
FC156
1
1
Y
70874
0x7899 Polarizing Voltage
0
1
1
FC272
0
1
Y
70875
0x789A Pos-Seq Restraint
0
500
1
F3
63
1
Y
70877
0x789C Forward ECA
-90
90
1
°
F20
75
1
Y
70878
0x789D Forward Limit Angle
40
90
1
°
F0
90
1
Y
70879
0x789E Forward Pickup
50
30000
1
x CT
F3
50
1
Y
70880
0x789F Reverse Limit Angle
40
90
1
°
F0
90
1
Y
70881
0x78A0 Reverse Pickup
50
30000
1
x CT
F3
50
1
Y
Modbus
Address
Hex
Address
Description
Min
Max
Step Units
Format
Code
Factory
Default
Size in
Words
8
5
0
8
6
9
8
8
9
8
4
5