For example, serious trips such as Short Circuit and Ground Fault may be assigned to the
2 AUXILIARY relay so that they can only be reset via the remote reset terminals (D18 and
D23) or the communication port. The remote reset terminals should be connected to a
keyswitch so that only authorized personnel could reset such a critical trip.
• Assign only Short Circuit and Ground Fault to the 2 AUXILIARY relay
• Program
2 AUXILIARY
to “Remote Reset Only”
5.5.3
Force Output Relay
PATH: SETTINGS
ZV
S4 OUTPUT RELAYS
ZV
FORCE OUTPUT RELAYS
The output relays can be independently forced in static or dynamic mode. In static mode
the selected relay will operate as long as it is in the “Enabled” state. Only when the user
enters “Disabled” will the selected relay reset. In dynamic mode the user specifies the
operate time (1 to 300 seconds) and the selected relay will operate for the specified
duration.
The
FORCE OUTPUT RELAY
option is NOT allowed when the selected relay output is already
active due to trip or alarm condition, when the 469 is in start block condition, or when the
469 is not in service.
Note
IMPORTANT NOTE
: The forced relay will override any trip or alarm conditions. (i.e. when the
relay is forced and trip occurs, the relay will still be enabled when the trip condition is reset).
Control power loss in the 469 will
reset
all forced relays.
FORCE
[
FORCE 1 TRIP
RELAY: Disabled
Range: Disabled, Enabled
MESSAGE
FORCE TRIP RELAY
DURATION: Static
Range: Static, 1 to 300 s in steps of 1
MESSAGE
FORCE 2 AUXILIARY
RELAY: Disabled
Range: Disabled, Enabled
MESSAGE
FORCE 2 AUX RELAY
DURATION: Static
Range: Static, 1 to 300 s in steps of 1
MESSAGE
FORCE 3 AUXILIARY
RELAY: Disabled
Range: Disabled, Enabled
MESSAGE
FORCE 3 AUX RELAY
DURATION: Static
Range: Static, 1 to 300 s in steps of 1
MESSAGE
FORCE 4 ALARM
RELAY: Disabled
Range: Disabled, Enabled
MESSAGE
FORCE ALARM RELAY
DURATION: Static
Range: Static, 1 to 300 s in steps of 1
MESSAGE
FORCE 5 BLOCK
START
Range: Disabled, Enabled
MESSAGE
FORCE BLOCK RELAY
DURATION: Static
Range: Static, 1 to 300 s in steps of 1
Summary of Contents for 469
Page 62: ...2 16 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 2 INTRODUCTION ...
Page 90: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 292: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 313: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 7 HGF5C 808841A1 HGF8 808842A1 ...
Page 315: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 9 808712A1 CDR ...
Page 320: ...A 14 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A APPENDIX ...