On  Board  Version  2.3  or  later,  there  is  a  Travel  Timer  –  yellow  L.E.D.  trimpot.    This  should  be  set 
approximately 5 to 10 seconds after full operation after gates reach full travel on limits in open and closed 
position. 

 

Travel times can be adjusted by turning trimpot anticlockwise to extend travel time and vice versa. 

 

Green LED – Open Position (located above relay 4) 
Red LED – Close Position 
 

A

NTI

-C

LASH 

L

EAF 

D

ELAY

 

To  avoid  jamming,  there  is  a  time  delay  between  the  movement  of  each  gate.    This  delay  may  be 
independently adjusted for the opening sequence and the closing sequence. 

 

Dial R24 changes the closing delay and dial R27 changes the opening delay.  In situations where the master 
unit is on the right hand side from inside looking out, R24 sets the opening delay and R27 sets the closing 
delay. 

 

Turning the dials anticlockwise gives the minimum delay. 
 

O

PTIONS

 

P

USH 

B

UTTON

,

 

K

EY 

P

AD ETC

 

A variety of hard wired input devices can be used to operate the Light Industrial Operators.  Input should be 
in the form of a momentary closed circuit. 

 

Warning: Voltage must not be applied to these terminals or damage to the circuitry will result.  Devices that 
send a voltage pulse (as some intercoms do) must be connected to the circuit board through a relay. 

 

 

Figure 10: Push-button connection 

E

LECTRIC 

L

OCK

 

Connections for an electric lock are provided on the circuit board (Figure 11)  This connection block will 
supply 12 volts to energise and lock at the beginning of the opening and closing cycles. 

 

 

Figure 11: Electric Lock Connection 

Summary of Contents for 3

Page 1: ...1 Installation and Maintenance Manual Light Industrial Swing Gate Operators Model GDS 3 A B N 62 059 806 405 March 2017 V1 01 ...

Page 2: ...age Standard Installation 3 Side Mount Installation 5 Restricted Side Room Outswing Installation 6 Circuit Board Settings 6 Options 7 Transmitter Poor Range 8 Specifications Emergency Release Maintenance Warranty 9 ...

Page 3: ...from the operators to access the slotted fixing holes in the rear of the chassis Bend the tabs out and back against the rear of the chassis In this position they act as spacers allowing clearance for the cover 3 Position each unit on the gate pillars or posts approximately 50mm from the edge of the pillar The vertical position is found by locating the gate bracket This is best placed where there i...

Page 4: ... of the gate brackets first disengage the main arm from the drive shaft using the spanner provided unscrew the bolt until the arm swings freely Clamp the gate bracket in position Open and close the gate to ensure the gate bracket is appropriately located Pillar Figure 4 Arm position when gate closed 5 Connect Receiver Board 6 Connect power to the master operator 7 The limit switches may now be adj...

Page 5: ... the side room available In most situations this problem can be overcome by cutting down the Secondary arm the link joining the gate bracket to the Primary arm The new length can be approximated by the following procedure 1 Move the Primary arm to a position suitable for the close gate Remembering that in the closed position the Primary and Secondary arms must stop short of straight line alignment...

Page 6: ...matically close after a specific period This feature is activated by fitting a jumper across the appropriate connection block Figure 9 and adjusting the Auto Close dial to the required time delay Turning the dial anticlockwise increases the time until the gates automatically close Figure 9 Settings OVERLOAD The overloads Figure 9 are preset to maximum sensitivity i e slight pressure on the gate du...

Page 7: ...ations where the master unit is on the right hand side from inside looking out R24 sets the opening delay and R27 sets the closing delay Turning the dials anticlockwise gives the minimum delay OPTIONS PUSH BUTTON KEY PAD ETC A variety of hard wired input devices can be used to operate the Light Industrial Operators Input should be in the form of a momentary closed circuit Warning Voltage must not ...

Page 8: ...olved by using special frequency transmitters and a matching receiver These may be ordered through your supplier OTHER FAULTS Other faults may be due to incorrect settings Refer to the Settings and Options sections of this manual to ensure the settings are correct SPECIFICATIONS Dimensions Case 245mm high x 140mm wide x 335mm deep Primary arm pivot centres 550mm Secondary arm pivot centres 570mm W...

Page 9: ...ircumstances i If no proof of date of purchase can be produced ii If the product has been used in a manner beyond its design parameters iii If the product is tampered with or repaired by personnel not authorised to do so iv In respect of loss or damage caused by rough treatment v If the product is not used and maintained in accordance with instructions or recommendations listed in this Installatio...

Reviews: