gazex MDP-4 Instruction Manual Download Page 20

Overload or shorting of any voltage outputs “

12V ALARM OUTPUTS

 

during

 A1 

or

 A2 

status

 

will cause 

automatic switching off of automatically reset fuse. After removal of overload or shorting the internal fuse 
automatically restarts the normal work after not longer that several seconds. 

 

NOTE!!! To disable the unit in MDP-…B version equipped with internal battery support, 

disconnect the external power supply with main switch, then press "OK" button 

located on the front panel and hold it down until you disable the MDP unit (for about 

10 seconds).

 

 

6.3  The final stage of the control system’s operation is to check the MDP unit and generate all  

alarm states for all connected detectors and to control the efficiency of external devices. 

REQUIRED ASSUMPTIONS OF SYSTEM INSPECTION:

 

- The 

MDP 

unit is in normal state (after elapse of the time necessary for burn-in of sensors), the 

[POWER 

SUPPLY]

 light is on, detectors indicated with 

“N”

 sign are on, the value of concentrations displayed on 

LCD screen comply with the “zero level” specified in the instruction manuals of individual detectors.  

-  The unit was stored for not longer than 2 months or was connected to power supply for at least 24 hours 

(version B). 

DEX/DG 

detectors do not generate alarm signals (output current is consistent with the "zero level" 

specified in the detector manual);  

-  In order to obtain a measurement accuracy of the system specified in the manual, should be taken during 

inspection of detectors to meet the additional conditions specified in the individual manual for each 
detector DEX/P. 

6.3.1  Generate alarms of each detector by means o test gas with a known concentration value according to 

the instruction manual of the detector. After a time consistent with 

input delay 

the indication next to the 

tested detector should change into 

A1, A2 

or 

A3

 on the LCD screen, which is a sufficient confirmation 

of correct cooperation of detector set with unit.  
If the alarm signal A1 and A2 from the DEX detector will continue for at least the time corresponding to 

output delay, 

alarm signal on correct contact outputs will be generated in the zone, to which the 

specific detector had been assigned (message on LCD screen 

A1Z1 

and 

A1Z2

, green 

ALARM1 

and 

ALARM2 

lights will be turned off and a constant sound signal will be activated. 

In addition to measuring detectors switch on the LCD measuring screen and see if it appears with the 
appropriate detector measured gas concentration is compatible with the given test gas concentration (in 
the comparison should take into account the measurement accuracy of the unit, detector and test 
mixture).

 

6.3.2 For MDP-Z - Simultaneously with generation of the alarm state at the control output A2 of the 

corresponding zone, two electromagnetic pulses on 

VALVE

 terminals (message 

VAL1

 or 

VAL2

 on LCD 

screen) should be generated. Generation of the next A2 state 

must

 be preceded by a break for 

regeneration of internal batteries. The length of that break depends on the initial charging of the battery, 
the type of shut-off valves, the number of A2 states generated directly before the next attempt and on 
ambient temperature. It needs to be assumed that the break should not be shorter than 5 minutes (10 
minutes for two valves) and it should be DOUBLED after each successive attempt (independently of the 
fact whether A2 was generated from detectors or with the TEST procedure). After a series of ca. 5 
attempts wait for one hour or longer. 

6.3.3  After removal of the test gas reduction of gas concentration in the detector takes place, which causes a 

change of condition of detector on the LCD screen from 

H2 

and/or 

H1

, depending on completed alarm 

state and transition of red lights from constant lighting (if they were lit up) to flashing: first 

ALARM2

then

 ALARM1

. The control outputs are back to normal (alarm messages disappear from the LCD 

screen), while the sound signal is changed to intermittent. Information about alarms remains on the 
display until willingly cleared by a user. 

6.3.4  Check the operation of other detectors in a similar manner. When the status of all alarms is marked on 

the LCD screen with 

"H2"

 - reset the unit by pressing and holding the "OK" button located on the front 

panel for 3 seconds. Red lights of “

ALARM1

” and

 “ALARM2

 

should go off and the unit should switch 

to normal. 

Open the valve/shut-off valves!!!

 

6.3.5  The control procedure 6.3.1 should be complemented with output test conducted with software from the 

user menu described in section 5.4.4. 
Results of control or start-up should be registered in the attached Periodical Control Protocol. 

 

After a positive test result the GX 

Active Gas Installation Safety System

 or the 

Double-

threshold Gas Detection System 

can be considered activated and functional

.

 

 

6.4  Screw the cover of the unit’s terminal chamber: 

tight gland ducts (strong enough to prevent them from transmitting mechanical loads during the attempt 
of pull the cable out); 

seal not used gland ducts (e.g. by tightening short sections of the conduit on them);  

tightly close the transparent unit cover. Secure opening of the cover by turning the blocking pin with a flat 
screwdriver into horizontal position. 

it is recommended to seal the unit’s cover (to restrict outsiders’ access to MDP unit); 

 
 

MDP-4(8,16)… Instruction Manual  

edition 6PU63en   

©gazex’2011 v1101

  

Page 20

 

/ 24

 

Summary of Contents for MDP-4

Page 1: ...E This device is equipped with a function blocking in the case of interference in the internal circuits 1 General purpose and selection table page 2 2 Description and manner of connecting in the syste...

Page 2: ...ich group of detectors alarm occurred in fact it creates two detection systems the MDP unit in version Z controls operation of two shut off valves and controls the efficiency of the wired connection o...

Page 3: ...relay OUTPUTS 1 1 1 1 1 1 1 1 12V voltage alarm OUTPUTS 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 12V voltage insulated alarm INPUTS 2 2 2 2 2 2 2 2 High current 12V OUTPUT for control of shut off valve 2 2 2 S...

Page 4: ...vel 2 alarm at output in zone 1 level 2 alarm at output in zone 2 pulses closing the valve at zone 1 output were generated pulses closing the valve at zone 2 output were generated level 1 alarm at ala...

Page 5: ...R T M M ZAW1 ZAW2 S1 S2 A2 A1 A2 A1 A2 AWARIA FAULT STREFA ZONE S1 STREFA ZONE S2 S1 S2 WYJ CIA STYKOWE RELAYS GAZEX 2006 MDP 4 8 16 v U4 MD 8 16 v U4 WYJ NAP 12V I 0 2A OUT N L 01 02 03 04 05 06 07...

Page 6: ...of alarm state from the damaged detector until manual reset of MDP forced by status of detectors at MDP inputs Description of MDP statuses Activation of outputs from a specific zone occurs when the n...

Page 7: ...1m interrupted tone signalling of finished alarm continuous tone indication of the ongoing alarm or emergency optional without sound signalling SILENT MODE activated from the menu Supplying detectors...

Page 8: ...ting DEX detectors with the hub TABLE 4 3 Selection of conduits for detectors depending on the model of detector with a semiconductor sensor nn infra red P nR catalytic Pn Conduit fig 2 2 Conductor s...

Page 9: ...ng of the conduit in the gland should be solid enough to keep the conduit inside the MDP during the attempt of manual pulling it out and to prevent the conduit from transferring mechanical forces into...

Page 10: ...3 power supply unit MDP 4 8 A or PS 6 MDP 16 A with the battery connected maintain proper polarization the unit is protected by inverted polarization to terminal 02 to terminal 01 TIME LOCK ACTIVATIO...

Page 11: ...ailable functions 5 4 1 Detectors and alarm inputs perform the below features 01 2011 Control Unit MDP 8 U6 3 Serial number 00457328 Date of changes made to the software Type and version of the unit U...

Page 12: ...elect correct option with U and D keys and confirm with OK key Additionally a selected option is currently displayed on the LCD screen To exit the settings select the Exit option with U and D keys and...

Page 13: ...tputs of zone 1 are switched off That delay can be set within the range of 1 sec 15 minutes only when automatic shutdown of zone 1 inputs is selected 4 Outputs Off zone2 delay delay of switching outpu...

Page 14: ...wer supply fault Udex1 9VDC Internal power supply fault Udex2 9VDC Control Unit reset Control Unit power on Control Unit power off Internal accumulator fault no charging Internal accumulator fault U 1...

Page 15: ...he unit settings Losing the password will prevent subsequent modification of the unit by the user The password can only be unlocked by GAZEX service employees extra paid service 5 4 6 System settings...

Page 16: ...ol 3 Operation parameters allows changing unit s functionality Change SERVICE MODE enabled disabled AUTO RESET enabled disabled CABLE HUB none connected Exit Change press a SERVICE MODE allows blockin...

Page 17: ...ed with characters shown on the screen above The new password should be saved and secured This password will be required at each entrance to the administrator s settings Losing the password will preve...

Page 18: ...s and units of detectors depending on the measured medium Measuring range scaled to 4 20 mA The accuracy of the threshold alarm adjustment Medium 0 100 meas range 1 undefined medium the default type 0...

Page 19: ...t installation while switched on detectors should ndic ed with N sign on the LCD screen be i at Control of MDP unit s operation is conducted by means of the keyboard located in the front panel During...

Page 20: ...nt accuracy of the unit detector and test mixture 6 3 2 For MDP Z Simultaneously with generation of the alarm state at the control output A2 of the corresponding zone two electromagnetic pulses on VAL...

Page 21: ...turned off or main fuse damaged next to the main switch the unit supplied from internal battery turn the power on and reset the unit with OK button or change the fuse for identical one time delay cut...

Page 22: ...N The MDP unit and DEX DG detectors are electronic devices devoid of operating moving parts They were built on the basis of very durable semiconductor elements Therefore maintenance is reduced to Peri...

Page 23: ...t be stored with other wastes Therefore it was marked with a special symbol 8 STORAGE In order to care for the internal battery and a possible rechargeable battery in version MDP 4 8 16 B Z ZA ZB it i...

Page 24: ...MDP 4 8 16 Instruction Manual edition 6PU63en gazex 2011 v1101 Page 24 24 NOTICE...

Reviews: