gazex MDP-4 Instruction Manual Download Page 15

Outputs are switched sequentially at time = 1 sec. Currently switched on input is displayed on 
the LCD screen. After all the outputs are tested, MDP automatically switches to the service 
menu. The outputs are switched on in the following order: 
1. Relay output – zone 1, alarm 1, 

6. Valve output – zone 1 

2. Relay output – zone 1, alarm 2, 

7. Valve output – zone 2 

3. Relay output – zone 2, alarm 1, 

8. Alarm output – zone 1, alarm 1, 

4. Relay output – zone 2, alarm 2, 

9. Alarm output – zone 1, alarm 2, 

5. Relay output – fault, 

10. Alarm output – zone 2, alarm 1, 

 

11. Alarm output – zone 2, alarm 2; 

 

5.4.5 

User password

 - allows changing user password. 

 

 Change user password 
 

Enter old password:    

******* 

 

Enter new password:   

****   

 

Repeat new password:   

**** 

 
 

Password should contain 2-8 characters

 

 
 
 
 

 

 

In order to change the password: 

- enter old password,  

- enter new password 
- repeat new password 

After the new password has been correctly entered, a message “The password has been 
changed” will be displayed. The password is a combination of “U”, “D”, “L” and “R” keys and 
can contain from two to eight characters. When the password is being entered, it is masked 
with characters shown on the screen above.  

The new password should be saved and secured. This password will be required at 
each entrance to the unit settings. Losing the password will prevent subsequent 
modification of the unit by the user! The password can only be unlocked by GAZEX 
service employees (extra paid service). 

 

5.4.6 

System settings 

are protected with admin password and allow changing additional settings 

only by a skilled used or system installer.  
To make changes as an administrator, select this option and press “OK”. Then enter

 admin 

password: “PPPPP” 

(press the “P” button five times).  

Note!!! The above password is a standard password assigned to each unit. To protect 

against unauthorized access of third parties to additional unit settings, change the 

password.

 

Admin password should differ from user password. Only then access to additional unit 

features will be protected. 

The changed password should be remembered and kept in a 

safe place. Lost password will make it impossible to change the unit’s additional 
configuration. The password can only be unlocked by GAZEX service (extra paid).

 

 

After a correct password had been entered, the administrator menu will be displayed on the 
LCD with available functions: 

 

Select:  

Time Settings 

  

RS232 Port Settings  

  

Operating Parameters 

 Factory 

Settings 

  

Special Functions 

  

Administrator Password 

  

Exit

 

 

 
 
 
 
 
 
 

 1) 

Time Settings

 - allows changing current date and time settings: 

 

 Current time settings: 
 
2002-12-30 17:55:40 
 
 
Change - press 

, Exit - press <OK>

 

 

 

 
 
 

MDP-4(8,16)… Instruction Manual  

edition 6PU63en   

©gazex’2011 v1101

  

Page 15

 

/ 24

 

Summary of Contents for MDP-4

Page 1: ...E This device is equipped with a function blocking in the case of interference in the internal circuits 1 General purpose and selection table page 2 2 Description and manner of connecting in the syste...

Page 2: ...ich group of detectors alarm occurred in fact it creates two detection systems the MDP unit in version Z controls operation of two shut off valves and controls the efficiency of the wired connection o...

Page 3: ...relay OUTPUTS 1 1 1 1 1 1 1 1 12V voltage alarm OUTPUTS 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 12V voltage insulated alarm INPUTS 2 2 2 2 2 2 2 2 High current 12V OUTPUT for control of shut off valve 2 2 2 S...

Page 4: ...vel 2 alarm at output in zone 1 level 2 alarm at output in zone 2 pulses closing the valve at zone 1 output were generated pulses closing the valve at zone 2 output were generated level 1 alarm at ala...

Page 5: ...R T M M ZAW1 ZAW2 S1 S2 A2 A1 A2 A1 A2 AWARIA FAULT STREFA ZONE S1 STREFA ZONE S2 S1 S2 WYJ CIA STYKOWE RELAYS GAZEX 2006 MDP 4 8 16 v U4 MD 8 16 v U4 WYJ NAP 12V I 0 2A OUT N L 01 02 03 04 05 06 07...

Page 6: ...of alarm state from the damaged detector until manual reset of MDP forced by status of detectors at MDP inputs Description of MDP statuses Activation of outputs from a specific zone occurs when the n...

Page 7: ...1m interrupted tone signalling of finished alarm continuous tone indication of the ongoing alarm or emergency optional without sound signalling SILENT MODE activated from the menu Supplying detectors...

Page 8: ...ting DEX detectors with the hub TABLE 4 3 Selection of conduits for detectors depending on the model of detector with a semiconductor sensor nn infra red P nR catalytic Pn Conduit fig 2 2 Conductor s...

Page 9: ...ng of the conduit in the gland should be solid enough to keep the conduit inside the MDP during the attempt of manual pulling it out and to prevent the conduit from transferring mechanical forces into...

Page 10: ...3 power supply unit MDP 4 8 A or PS 6 MDP 16 A with the battery connected maintain proper polarization the unit is protected by inverted polarization to terminal 02 to terminal 01 TIME LOCK ACTIVATIO...

Page 11: ...ailable functions 5 4 1 Detectors and alarm inputs perform the below features 01 2011 Control Unit MDP 8 U6 3 Serial number 00457328 Date of changes made to the software Type and version of the unit U...

Page 12: ...elect correct option with U and D keys and confirm with OK key Additionally a selected option is currently displayed on the LCD screen To exit the settings select the Exit option with U and D keys and...

Page 13: ...tputs of zone 1 are switched off That delay can be set within the range of 1 sec 15 minutes only when automatic shutdown of zone 1 inputs is selected 4 Outputs Off zone2 delay delay of switching outpu...

Page 14: ...wer supply fault Udex1 9VDC Internal power supply fault Udex2 9VDC Control Unit reset Control Unit power on Control Unit power off Internal accumulator fault no charging Internal accumulator fault U 1...

Page 15: ...he unit settings Losing the password will prevent subsequent modification of the unit by the user The password can only be unlocked by GAZEX service employees extra paid service 5 4 6 System settings...

Page 16: ...ol 3 Operation parameters allows changing unit s functionality Change SERVICE MODE enabled disabled AUTO RESET enabled disabled CABLE HUB none connected Exit Change press a SERVICE MODE allows blockin...

Page 17: ...ed with characters shown on the screen above The new password should be saved and secured This password will be required at each entrance to the administrator s settings Losing the password will preve...

Page 18: ...s and units of detectors depending on the measured medium Measuring range scaled to 4 20 mA The accuracy of the threshold alarm adjustment Medium 0 100 meas range 1 undefined medium the default type 0...

Page 19: ...t installation while switched on detectors should ndic ed with N sign on the LCD screen be i at Control of MDP unit s operation is conducted by means of the keyboard located in the front panel During...

Page 20: ...nt accuracy of the unit detector and test mixture 6 3 2 For MDP Z Simultaneously with generation of the alarm state at the control output A2 of the corresponding zone two electromagnetic pulses on VAL...

Page 21: ...turned off or main fuse damaged next to the main switch the unit supplied from internal battery turn the power on and reset the unit with OK button or change the fuse for identical one time delay cut...

Page 22: ...N The MDP unit and DEX DG detectors are electronic devices devoid of operating moving parts They were built on the basis of very durable semiconductor elements Therefore maintenance is reduced to Peri...

Page 23: ...t be stored with other wastes Therefore it was marked with a special symbol 8 STORAGE In order to care for the internal battery and a possible rechargeable battery in version MDP 4 8 16 B Z ZA ZB it i...

Page 24: ...MDP 4 8 16 Instruction Manual edition 6PU63en gazex 2011 v1101 Page 24 24 NOTICE...

Reviews: