2) Detectors - zones.
Select
:
Zone 1
Zone 2
Zone 1+2
Exit
Current Settings: Zone 1+2
Change -
, Confirm - <OK>
The flashing cursor denotes the selected detector. Select the correct detector with “L” and “R” keys
and then with “U” and “D” keys change assignment of a detector to a zone: “1” - detector is
assigned to zone 1; “2” - detector is assigned to zone 2; “1+2” - detector is assigned
simultaneously to both zones. To confirm the settings, press the “OK” button.
3) Detectors - parameters.
The cursor denotes the selected detector. Select the correct detector with “L” and “R” keys and
then with “U” and “D” keys select a required detector’s parameter, change the parameters with “L”
and “R” keys. To confirm the settings, press the “OK” button.
The parameter "alarm type" allows two choices: "tresholds levels" - the temporary value of alarm
thresholds A1 and A2 adjustable over the full measuring range; "time-weighted average - the
threshold of T1 corresponds to the TWA (Time-Weighted Average - 8h/day), the threshold T2
corresponds to the STEL (Short Term Exposure Limit – 15 minut)
Note!!! For connecting the threshold detector DEX/F or DG/F to MDP select “DEX - A1,A2
tresholds”, for WG and AirTECH detectors with NC contact outputs select “BIN -thresholds A1, A2”.
Cooperation with threshold detectors requires the use of cable hub K-8P or K-16P, and setting the
"Cable Hub" to "connected" (see 5.4.6, 3C)
4) Alarm inputs - zones.
Select correct option with “U” and “D”
keys and confirm with “OK” key.
Additionally a selected option is
currently displayed on the LCD screen.
To exit the settings, select the “Exit”
option with “U” and “D” keys and then
press “OK”.
5)
Inputs delay
(default = 10 sec.) is a time, for which alarm status should be maintained at the
detector’s input, so it could be registered by MDP and signalled with proper message on the LCD
screen. That delay can be set within the range of: 1
÷
120 seconds with “L” and “R” keys.
6)
Detectors heating time
(default = 60 sec.) is a time after each start of MD, during which stabilization
of the detectors’ operation point necessary for their correct operation occurs. The heating time can be
adjusted within the range of: 1
÷
15 minutes with “L” and “R” keys.
5.4.2
Output settings
perform the following functions.
Detector no.:
03
- alarm A1 :
TWA
- alarm A2 :
STEL
- alarm type :
time average values
- calibration gas. :
carbon monoxide
- measur. range:
500 ppm
Change - press
, Exit - press <OK>
Denotes:
measuring detector no. 3,
alarm T1 = TWA,
alarm T2 = STEL,
meauring range 0-500ppm
Feature selection with “U” and “D” keys,
Confirmation with “OK” key
Select:
Outputs Off – auto / manual
Outputs On
– delay
:
10 sec.
Outputs Off – zone1 delay
:
3 sec.
Outputs Off – zone2 delay
:
3 sec.
Outputs On
– zone1 logic
:
1 alarm
Outputs On
– zone2 logic
:
2 alarms
Exit
DETECTOR:
1 2 3 4 5 6 7 8
Zone:
1 1 1
1+2
1
+2
1 2
1+2
DETECTOR:
9 10 11 12 13 14 1516
Zone: 1
1+2
2 2
1+2
1 2 2
Change – press
, Exit – press <OK>
Denotes:
Detector 8 - assigned to zone 1
and
zone
2
MDP-4(8,16)… Instruction Manual
edition 6PU63en
©gazex’2011 v1101
Page 12