1)
Outputs Off – auto / manual
.
Select:
Ouptut Off – zone1, alarm1
:
manual/auto
Ouptut Off – zone1, alarm2
:
manual/auto
Ouptut Off – zone2, alarm1
:
manual/auto
Ouptut Off – zone2, alarm2
:
manual/auto
Exit
Change - press
.
Select correct output with “U” and “D” keys and then with “L” and “R” keys change the manner of
switching the output off. Manual shutdown means that the output will be switched off ONLY after
external intervention of the user (unit reset with “OK” button). By this time, emergency state will be
maintained ay that output, even after the event that caused the alarm had ended.
Automatic shutdown means that the output will be switched off independently by the MDP after the
alarm that caused the output to switch on had ended. Information about the alarm condition is indicated
by the pulsating sound and relevant messages on the LCD screen until the user resets the MDP.
2)
Outputs On – delay
(delay of switching the outputs off) is a time (10 sec. by default) from the
moment the MDP registers an alarm condition at detector’s input to the moment, when the MDP
switches appropriate outputs on depending on location of the alarm. That delay can be set within the
range of: 1
÷
120 seconds
3)
Outputs Off – zone1 delay
(delay of switching outputs of zone 1 off) is a time (3 sec. by default)
from the moment of alarm decay to the moment outputs of zone 1 are switched off. That delay can be
set within the range of: 1 sec.
÷
15 minutes (only when automatic shutdown of zone 1 inputs is
selected).
4)
Outputs Off – zone2 delay
(delay of switching outputs of zone 2 off) is a time (3 sec. by default)
from the moment of alarm decay to the moment outputs of zone 2 are switched off. That delay can be
set within the range of: 1 sec.
÷
15 minutes (only when automatic shutdown of zone 2 inputs is
selected).
Alarm Alarm signalling switching of outputs “AutoReset” mode
Alarm decay
unit reset
input status
signalling
outputs status
storing alarms on outputs in memory
(switched off manually)
switching outputs off with delay
(switched off automatically - delay of 3 min)
switching outputs off after alarm decay
(switched off automatically - delay of 1 sec.)
Delay of
switching outputs on
D
el
ay
o
f
inputs
D
el
ay
o
f
switching outputs off
time
5)
Outputs Off – zone1 logic
defines the minimum quantity of a given type of alarms (A1, A2) on
outputs of detectors activating outputs of zone 1. Two options available: at least 1 or two alarm states.
6)
Outputs Off – zone1 logic
defines the minimum quantity of a given type of alarms (A1, A2) on
outputs of detectors activating outputs of zone 2. Two options available: at least 1 or two alarm states.
5.4.3
Events history
performs the following functions.
MDP-4(8,16)… Instruction Manual
edition 6PU63en
©gazex’2011 v1101
Page 13
/ 24
Feature selection with “U” and “D” keys,
Confirmation with “OK” key
Select:
Events - viewing on LCD
Events – data transmission
Exit