- 13 -
TYPE B
a / INDIVIDUAL FLUTING OF EACH UNIT OUTSIDE THE BUILDING
- Remove grill at exhaust pipe (1).
- And replace with connection piece Ø100 (2) for Ø97 tube.
- Do not use grill as protection for a flue pipe end.
- Air inlets must be sufficient in the premises in order to
allow a good supply of the burner with air of combustion
Plan for an external air flow of at least 1,75 m3/h per
installed kW.
SAFETY INSTRUCTIONS CONCERNING THE INDIVIDUAL EVACUATION DUCT :
- No reduction of diameter can be accepted after the connection piece.
- It must be made out of stainless steel or aluminium with
smooth
and
rigid
duct.
- The evacuation must be realized according to the norms in force in each concerned country.
- The maximum lenght of the exaust pipe do not be up than 8 meters + 3 bends 90° + 1
terminal ( see on the spreadsheet herunder).
- The duct must not include low point.
- Any accessory made out of plastic or PVC is absolutely prohibited.
Air flow
Fumes
temperature
Volumic flow
Massic flow
BTH25
44 m
3
/h
177 °C
76 m/
3
h
57 kg/h
Flue system pipe lengths
Elbow 90°
2 m
Ebow 45°
1 m
Std protection cap against rain
2 m
1m rigid hose
1 m
CAREFUL : refer to the rules in force.
1
2