6.4. Menu Configuration Table
LEVEL1
LEVEL2
DEFAULT
NAME
PARAMETER
PROGRAM
MODE
GAS TYPE (Gas Type)
[DEFIN./USER]
DEFIN.
GAS SEL(Gas Select)
Built-in gas name selection
COMB.
UNIT SEL (Unit Select)
%/%LEL/PPM/PPB
%LEL
D-POINT(Decimal Point)
0.100/1.00/10.0/100
100
HIGH SCL (High Scale)
1~10000
100
PASSWORD
00~99
00
CALIBRA.
MODE
(Calibration Mode)
CALIBRA.
[ZERO]
(Calibration Zero)
ZERO CAL
[NO,YES]
[NO]
ZERO GAS
[ 0]
ZERO >>>>
[SUCCESS / FAIL]
CAL. DATA
[ 0/ FAIL]
CALIBRA.
[SPAN]
(Calibration Span)
SPAN CAL
[NO , YES]
[NO]
SPAN GAS
[ 0]
SPAN SET
[ 50/ FAIL]
50
SPAN >>>>
[SUCCESS / FAIL ]
CAL. DATA
[ 0]
ALARM
MODE
ALM USED (Alarm Used)
[OFF / ON]
OFF
AL LATCH (Alarm Latch)
[OFF / ON]
OFF
A1 LEVEL (Alarm-1 Level)
[1 ~ Full SCL]
20
A1 TYPE(Alarm-1 Type)
[INC / DEC]
INC
A1 DBAND (Alarm-1 Dead Band)
[0.0 ~ 10.0%F.S]
0
A1 TIME (Alarm-1 Time)
[0~ 60]SEC
1
A2 LEVEL (Alarm-2 Level)
[1 ~ Full SCL]
40
A2 TYPE(Alarm-2 Type)
[INC / DEC]
INC
A2 DBAND (Alarm-2 Dead Band)
[0.0 ~ 10.0%F.S]
0
A2 TIME (Alarm-2 Time)
[0~ 60]SEC
1
SENSOR MODE
Factory Setting
MAINTEN.MODE
Factory Setting
DEVICE MODE
Factory Setting
VERSION MODE
Factory Setting
TEST MODE
Factory Setting
6. Detector Operation Flow