10.4.
Bump Test Conditions
Bump tests must be carried out with the detector operating within its specified limits. Operating the
detector outside of its limits could cause performance problems or functional failure.
10.5.
Bump Test Procedure
Bump testing involves applying test gas to the detector and observing the readings from it.
Readings should be obtained either from the detector's display or the controller display.
If it is required to monitor the current loop signal and there is no provision for accessing it within the installation
wiring, the detector enclosure must be opened to gain access to the test terminals on the main circuit board.
Current Loop Test Points
Do not short the test points to ground or connect to the shield or the signal return terminals. Doing so
may cause damage to the detector electronics.
Do not operate the unit with the cover removed if the installation area and or conditions do not
permit it. Current loop access must then be via connections in the safe area.
The bump test procedure should be carried out as follows (example assumes a 0 - 100ppm H
2
S detector) :-
Decide on the appropriate method for viewing the readings.
Remove the splash-guard from the detector gas entry port - the splash-guard is removed via two 4mm
Allen key type screws. Attach the calibration plug (with attached 6mm hose) to the detectors gas
inlet port by gently pushing it into place.
Connect the hose to the purge gas cylinder regulator outlet.
Turn on the nitrogen supply and allow to run for about 60 seconds.
Observe the detector response (nitrogen still running).
The display reading should be 0.0 ± 0.1. The current loop output should be 4.00mA with a maximum
variation from ideal of ± 0.03mA.
Switch off the purge gas
Summary of Contents for D-Guard2
Page 2: ...D Guard2 1 This Page Left Intentionally Blank ...
Page 65: ...D Guard2 62 23 APPENDIX F 23 1 System Menu Map ...
Page 68: ...D Guard2 65 25 APPENDIX H Product Certificates 25 1 IECEx Product Certificate ...
Page 69: ...D Guard2 66 ...
Page 70: ...D Guard2 67 ...
Page 71: ...D Guard2 68 ...
Page 72: ...D Guard2 69 25 2 ATEX Product Certificate ...
Page 73: ...D Guard2 70 ...
Page 74: ...D Guard2 71 ...
Page 75: ...D Guard2 72 ...
Page 76: ...D Guard2 73 26 APPENDIX I Product Dimensions ...
Page 77: ...D Guard2 74 Doc_Rev 03 12 15 ...