Page
23
©
2008
Gastech
Australia
Pty
Ltd
Flicking
the
Isolation
switch
over
to
“ISOLATE”
will
drop
the
mA
signal
down
to
3mA
and
invert
the
display,
the
gas
reading
will
flash,
and
the
word
“ISOLATED”
is
shown.
This
mode
is
permanent
until
the
switch
is
changed
over.
Note:
No
gas
readings
will
be
transmitted
in
the
“ISOLATE”
mode
.
3.2.2
Normal/Invert
Jumper
This
jumper
is
set
to
invert
for
Oxygen
sensors
and
any
other
sensor
that
has
a
reducing
sensor
output.
Contact
the
factory
for
confirmation
on
the
sensor
that
is
being
fitted.
The
table
below
lists
some
common
sensors
which
require
the
jumper
set
to
invert
mode.
Gas
Sensor
Model
GasTech
Part
Number
Chlorine
4CL
7CLH
65
‐
8009
‐
4CL
65
‐
8009
‐
7CLH
Nitrogen
Dioxide
4ND
7NDH
65
‐
8004
‐
4ND
65
‐
8004
‐
7NDH
Ozone
7OZ
65
‐
8005
‐
7OZ
Chlorine
Cl2
3E
10/50
65
‐
9097
‐
CL2
‐
1
65
‐
9097
‐
CL2
‐
2
Chlorine
Dioxide
ClO2
3E
1
65
‐
9097
‐
CL02
Fluorine
F2
3E
1
65
‐
9097
‐
F2
Hydrogen
Fluoride
HF
3E
10
&
HF
3E
10S
65
‐
9097
‐
HF
Nitrogen
Dioxide
NO2
3E
50
65
‐
9097
‐
NO2
Ozone
O3
3E
1
65
‐
9097
‐
O3
‐
2
Isolated
mode
Reading
inverted
Summary of Contents for D-Guard