REV
.03-(16.03.2015)
Ma ntenance
30
Generally, the normal serv ce per od s one year. Each year the
bo ler should be cleaned and checked accord ng to the
ma ntenance procedure and ınstruct ons. If there s any doubt
whether the bo ler w ll operate w th the correct water or
combust on a r qual ty, t s adv sable that a first check s done
after half a year to determ ne future serv ce per od.
6
MAINTENANCE
6.1
GENERAL
WARNING: Damage to the nstallat on due to
nsuffic ent or mproper clean ng and ma ntenance.
Inspect and clean the heat ng system once a year.
Carry out ma ntenance as requ red. Immed ately remedy
faults. Th s w ll
avo d further damage to the system!
6.2
MAINTENANCE PROCEDURE
Inspect on, ma ntenance and the replacement of parts should be
done by Gassero techn cal serv ce. Bes des do ng
ma ntenance we adv se to create a log chart belong ng to each
bo ler on wh ch at least the follow ng should be wr tten:
- Ser al number of the bo ler
- Ma ntenance date
- Respons ble personnel of ma ntenance.
- Parts and/or sett ngs changed dur ng ma ntenance.
- Spec al remarks
- Important po nts n the future.
Dur ng ma ntenance the follow ng po nts should be checked
and/or parts must be nspected and ma nta ned.
Before do ng any work on the bo ler:
- Sw tch off the power to the bo ler by serv ce sw tch or pull
out plug from wall socket
- Close the gas valve
Customer comments
Comments and notes from the customer should be taken
ser ously and an effort should be made to find the cause of any
problems.
Serv ce h story
Faults and work ng h story can be read from bo ler nterface or
w th a computer n comb nat on w th the software and nterface
cable of the PCB.
Water leakage
The pressure of the nstallat on must be h gher than 0,8 bar,
and max mum 6 bar. F nd poss ble leaks n the system and have
these fixed.
Flue gas leakage
The flue gas d scharge and a r ntake p p ng need to be checked
for gas leakage. Also check f the p p ng s properly mounted and
not damaged. Inspect the top of the bo ler hous ng for traces of
water leakage or traces of water from the a r vent, or leak ng
condensate from the flue gas p p ng.
Gas l nes/-connect ons
The gas l nes need to be checked for gas leakage. Also check f
the p p ng s properly mounted and not damaged.
Un-assembl ng the Burner
Un-assembl ng the burner un t: Remove the 6 x M6 nuts and the
electrode cables, and move the burner un t forward. Remove the
plug of the fan cable from the fan when the burner has been
pulled half-way from the heat exchanger. D smantle the a r gas
m x ng box on the ntake s de of the fan and check the blade
wheel of the fan.
Insulat on
The nsulat on of the heat exchanger (located on the rear wall
ns de n the heat exchanger) must be nspected. If th s nsulat on
d sk shows any s gn of damage or mpa rment t should be
replaced w th a new one. Also check f there are any s gns of a
too h gh condensate level (caused by a blocked s phon) that
m ght have wetted the nsulat on several t mes. When these
s gns can be seen, the rear wall nsulat on should be replaced.
Only use the burner door nsulat on that s suppl ed by the
manufacturer.
The same procedure must be appl ed on the nsulat on and
gaskets fitted on the burner door.
Burner- and burner door gaskets
When these show any s gns of damage they must be replaced.
S phon
D s-assemble the bottom cover s phon and clean t. Check f the
s phon connect on on the heat exchanger s not blocked, and clean f
necessary. Check afterwards f the s phon funct ons properly.
Th s can be done by pour ng clean tap water n the furnace
(when burner door s removed) so t w ll ex t the heat exchanger
through the s phon. Make sure the nsulat on s not wetted.
Heat exchanger/combust on room
Check f there s any debr s/depos t n the heat exchanger. The
heat exchanger co ls can be cleaned by us ng a non metall c
brush. Afterwards the loose part cles may be removed w th a
vacuum cleaner and/or flush ng w th water. Check flow of water
out of s phon, and clean s phon f necessary. Any clean ng of the
combust on chamber w th ac d or alkal products s proh b ted!
Gas/a r rat o
Always check the gas/a r rat o by check ng the combust on figure
CO on max mum and m n mum nput. If necessary adjust these
2
figures.
Pump
If the pump s becom ng no sy (certa nly when the pump has
been work ng for more than five years) t s recommended to
replace the pump as a precaut on.